background image

9

Fig. 13 —Using a Main Drain to Serve Multiple Indoor Units with Internal Condensate Pumps

• Condensate  piping  should  slope  downward  in  the

direction of condensate flow with a minimum gradient of

1 inch per 100 inches.

• When  multiple  units  are  connected  to  a  common

condensate drain, ensure that the drain is large enough to

accommodate the volume of condensate from all units. It

is  also  recommended  to  have  an  air  vent  in  the

condensate piping to prevent air lock.

• Condensate piping must not be installed where it may be

exposed to freezing temperatures.

REFRIGERANT PIPING

Follow these procedures when connecting from an indoor unit

to an outdoor unit:
• Check  maximum  height  drop  and  length  of  refrigerant

piping between the indoor and outdoor units. To ensure

the  drop  and  length  are  acceptable,  refer  to  the

refrigerant  piping  allowable  limits  in  the  outdoor  unit

installation manual.

• The number of bends in the refrigeration piping must be

less than 15.

• Refrigerant  piping  connection  between  indoor  and

outdoor  units  should  be  performed  once  the  units  are

secured at their respective installation locations.

• The refrigeration piping starts at the indoor unit and ends

at the outdoor unit or Multiport Distribution Controller

(MDC) for Heat Recovery systems. 

• The refrigerant piping should be dry and free of dust and

other impurities.

• The  bending  angle  of  the  refrigerant  pipe  should  not

exceed 90º and the bending radius should be as large as

possible to prevent any breakage in piping.

• Use proper cutting and flaring tools to avoid leakage.
• Use a torque wrench for flare nuts. Refer to Table for

flare nut torque recommendations.

Table 4 — Flare Nut Torque Recommendations

• Before  insulating  the  suction  and  liquid  refrigeration

pipes,  perform  pressure  and  leak  tests.  For  details,  see

the  outdoor  unit  installation  manual.  Insulating  both

suction and liquid refrigerant pipes is mandatory. 

• Vacuuming and charging of the system should be carried

out as described in the outdoor unit installation manual.

Step 5 — Complete Electrical Connections —

Installation of wiring must conform to local building codes. In

absence of local codes, wiring must conform to the National

Electric  Code  ANSI/NFPA  (American  National  Standards

Institute/  National  Fire  Protection  Association)  70,  current

editions. Units must be electrically grounded in conformance

with  the  code.  In  Canada,  wiring  must  comply  with  CSA

(Canadian Standards Association) C22.1, Electrical Code.

This  equipment  in  its  standard  form  is  designed  for  an

electrical supply of 208/230-1-60. Any damage to or failure of

units caused by incorrect wiring or voltage is not covered by

the warranty.

Electric wiring must be sized to carry the full load amp draw of

the motor, starter, and any other controls that are used with the

unit. See Table 5 for electrical data.

2“~4” 

2“~4” 

2“~4” 

Max. 3-3/4 ft. 

”

7-7/8” 

”

7-7/8” 

”

7-7/8” 

Connection assembly of water outlet  Main drainage pipe 

Gradient: 1/50~1/100  

CAUTION

When connecting from an indoor unit to an outdoor unit,

the isolation valve at outdoor unit should be in the closed

position throughout the refrigerant piping process. Failure

to follow this procedure may result in equipment damage.

OUTSIDE DIAMETER (in.) RECOMMENDED TORQUE (ft-lb)

1/4

15

3/8

26

1/2

41

5/8

48

WARNING

Electrical  shock  can  cause  personal  injury  and  death.

Disconnect  power  supply  before  making  wiring

connections.  There  may  be  more  than  one  disconnect

switch. Tag all disconnect locations to alert others not to

restore power until work is completed. 

WARNING

All  units  must  be  wired  strictly  in  accordance  with  the

wiring  diagram  furnished  with  the  unit.  Any  wiring

different from the wiring diagram could result in personal

injury and property damage.

CAUTION

Any original factory wiring that requires replacement must

be  replaced  with  wiring  material  having  a  temperature

rating of at least 221ºF.

Ensure supply voltage to the unit, as indicated on the serial

plate, is not more than 10% over the rated voltage or 10%

under the rated voltage.

Failure  to  follow  these  recommendations  may  result  in

equipment damage.

Summary of Contents for 40VMF

Page 1: ...in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or p...

Page 2: ...2 shows unit dimensions Table 2 shows components that may or may not be used for a particular installation Fig 1 Model Number Nomenclature CAUTION DO NOT re use compressor oil or any oil that has bee...

Page 3: ...Low 32 1 33 0 37 0 40 2 40 2 42 1 47 3 50 5 Medium 34 0 37 3 41 5 43 1 42 5 45 1 50 4 54 0 High 36 7 41 4 45 6 52 5 44 7 49 5 53 9 55 4 UNIT Unit Dimensions W x H x D in 33 1 8 x 9 x 33 1 8 33 1 8 x 1...

Page 4: ...ulation 1 For covering the condensate drain Clamp 1 For connecting the drain Tie rope 5 For insulation Condensate connection 1 For connecting drain PQE connection wire 2 To connect outdoor unit indoor...

Page 5: ...A 048A Dimensions NOTE All dimensions shown in inches 40VMF UNIT SIZE DIMENSION A 009A 9 012A 015A 018A 11 3 4 024A 030A 036A 048A 37 3 8 30 3 4 37 3 8 26 3 4 33 1 8 4 1 8 2 3 4 33 1 8 5 3 4 1 3 4 34...

Page 6: ...ation in a typical room at jobsite Check all critical dimensions such as pipe wire and duct connections requirements Refer to job drawings and product dimension drawings as required Instruct all trade...

Page 7: ...rod For unit weight see Table 3 Fig 7 Mounting Hole Locations Table 3 Unit Weight Includes grille weight MOUNTING UNIT The unit can now be lifted on to the hanging rods for mounting 1 Use rods and fas...

Page 8: ...ing Panel 5 When the panel is secure insert the grille at a 45 angle and latch it in place Step 4 Connect Piping CONDENSATE PIPING The unit is supplied with a 1 1 4 inch OD drain connection to connect...

Page 9: ...ould be carried out as described in the outdoor unit installation manual Step 5 Complete Electrical Connections Installation of wiring must conform to local building codes In absence of local codes wi...

Page 10: ...ACB Auxiliary Control Board AUXH Output For Auxiliary Heat CS Condensate Switch CTON Output for Cooling Operation EEV Electronic Expansion Valve FAN Output for Fan Operation FM Indoor Fan Motor GM Lou...

Page 11: ...Fig 17 below Fig 17 Stripping the Wire 3 Use a suitable screwdriver to fix the communication wire on the outdoor unit communication terminal as shown in Fig 18 below Fig 18 Connecting Communication Wi...

Page 12: ...r unit 2 HA HB Indoor unit 3 HA HB Indoor unit 4 HA HB Indoor unit 5 HA HB Indoor unit 6 HA HB HA HB Touch screen NOTE 24 v DC Power wired controller Field Supplied wired controller HA HB NOTE Power f...

Page 13: ...oor unit 6 HA HB P Q Network Resistor HA HB Touch screen NOTE 24 v DC Power wired controller Field Supplied wired controller HA HB NOTE Power from IDU MAXIMUM WIRING LENGTH L1 L3 3937 ft 18 AWG 2 Core...

Page 14: ...th maintenance schedule In addition Clean condensate tray with suitable cleaning agent Clean the grille and panel EVERY 12 MONTHS Follow 6 month maintenance schedule In addition Be sure all electrical...

Page 15: ...26 Press OK to confirm and exit the setting interface Fig 26 Non Programmable Controller Setting IDU Address Programmable Controller When setting an address connect only one wired controller to an in...

Page 16: ...u want to set See Fig 28 Press MENU OK to send this address to the IDU Fig 28 Programmable Controller Setting IDU Address 4 Press BACK twice or wait 30 seconds to automatically exit the parameter sett...

Page 17: ...ing Mode Conflict Error E1 Communication Error Between Indoor and Outdoor Unit E2 Check Indoor Temperature Sensor T1 E4 Check Evaporator Outlet Temperature Sensor T2B E5 Check Evaporator Temperature S...

Page 18: ...t and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance signal wires from electromagnetic source PC boar...

Page 19: ...ETTINGS Fig B SW8 SETTINGS OFF Auto Addressing Mode Default ON Factory Test Mode OFF Normal Mode Default ON Factory Self Checking Mode OFF Standard Indoor Unit Default ON Mode Priority Indoor Unit HP...

Page 20: ...20...

Page 21: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 20 40VMF002 01 Printed in U S A Form 40VMF 4SI Pg 21 07 20 Replaces 40VMF...

Reviews: