Fig. 4 —Distance from Wall or Obstruction

• Do not  position the  unit where the  discharge  air could

blow directly on the thermostat.

• Recommended  distance  between  2  units  is  10  feet  to

avoid conflicting airflow and recirculation.

• The  unit  should  not  be  positioned  directly  above  any

obstruction.

• The unit must be installed square and level.
• Condensate drain should have sufficient downward slope

(1  inch  per  100  inches)  in  any  horizontal  run  between

unit and drain. Maximum condensate lift is 29-

1

/

2

 inches.

In case of new construction, once the unit is installed, cover the

fan motor opening using the construction cover board to avoid

any dust and debris from settling inside the unit. Use the M6

bolt, washer and nut as shown in Fig. 5 below.

Fig. 5 —Paper Board Mounting Hole Locations

See Fig. 6 for an example of some buffer locations.

Fig. 6 —Example of Buffer Locations

Step 3 — Mount the Unit

INSTALLING HANGER BOLTS — Install the hanger bolts

at the locations shown in Fig. 7. Use 3/8-inch all-threaded rod.

For unit weight, see Table 3.

Fig. 7 —Mounting Hole Locations

Table 3 — Unit Weight

*Includes grille weight.

MOUNTING UNIT — The unit can now be lifted on to the

hanging rods for mounting.

1. Use rods and fasteners to suspend the unit at the factory-

provided mounting holes. 

2. Adjust  the  height of  the  unit until the  bottom (without

grille) is level with the false ceiling.

3. Secure the unit in position with locknuts and washers on

both sides of the unit bracket. Ensure that the threaded

rod  does  not  protrude  more  than  2  inches  below  the

mounting brackets as shown in Fig. 8.

IMPORTANT: Be sure that the ceiling grid is supported

separately from the unit. The ceiling grid must not be

supported  by  an  part  of  the  unit  or  any  associated

wiring or piping work.

CAUTION

Remove all buffers between the fan and the flared mouth

before installing the indoor unit. Failure to do so will cause

damage to the fan motor. 

CAUTION

To  avoid  equipment  damage,  ensure  the  unit  is  placed

horizontally.

40 in. MIN.

40 in. MIN.

40 in. MIN.

40 in. MIN.

a40-1720

Unit body

Install the paper board

Central hole

Screw M6×12

40VMF UNIT

WEIGHT (lb)*

009A

71.0

012A

71.0

015A

71.0

018A

86.0

024A

86.0

030A

86.0

036A

86.0

048A

86.0

Buffer 

í

í

í

í

Summary of Contents for 40VMF

Page 1: ...in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or p...

Page 2: ...2 shows unit dimensions Table 2 shows components that may or may not be used for a particular installation Fig 1 Model Number Nomenclature CAUTION DO NOT re use compressor oil or any oil that has bee...

Page 3: ...Low 32 1 33 0 37 0 40 2 40 2 42 1 47 3 50 5 Medium 34 0 37 3 41 5 43 1 42 5 45 1 50 4 54 0 High 36 7 41 4 45 6 52 5 44 7 49 5 53 9 55 4 UNIT Unit Dimensions W x H x D in 33 1 8 x 9 x 33 1 8 33 1 8 x 1...

Page 4: ...ulation 1 For covering the condensate drain Clamp 1 For connecting the drain Tie rope 5 For insulation Condensate connection 1 For connecting drain PQE connection wire 2 To connect outdoor unit indoor...

Page 5: ...A 048A Dimensions NOTE All dimensions shown in inches 40VMF UNIT SIZE DIMENSION A 009A 9 012A 015A 018A 11 3 4 024A 030A 036A 048A 37 3 8 30 3 4 37 3 8 26 3 4 33 1 8 4 1 8 2 3 4 33 1 8 5 3 4 1 3 4 34...

Page 6: ...ation in a typical room at jobsite Check all critical dimensions such as pipe wire and duct connections requirements Refer to job drawings and product dimension drawings as required Instruct all trade...

Page 7: ...rod For unit weight see Table 3 Fig 7 Mounting Hole Locations Table 3 Unit Weight Includes grille weight MOUNTING UNIT The unit can now be lifted on to the hanging rods for mounting 1 Use rods and fas...

Page 8: ...ing Panel 5 When the panel is secure insert the grille at a 45 angle and latch it in place Step 4 Connect Piping CONDENSATE PIPING The unit is supplied with a 1 1 4 inch OD drain connection to connect...

Page 9: ...ould be carried out as described in the outdoor unit installation manual Step 5 Complete Electrical Connections Installation of wiring must conform to local building codes In absence of local codes wi...

Page 10: ...ACB Auxiliary Control Board AUXH Output For Auxiliary Heat CS Condensate Switch CTON Output for Cooling Operation EEV Electronic Expansion Valve FAN Output for Fan Operation FM Indoor Fan Motor GM Lou...

Page 11: ...Fig 17 below Fig 17 Stripping the Wire 3 Use a suitable screwdriver to fix the communication wire on the outdoor unit communication terminal as shown in Fig 18 below Fig 18 Connecting Communication Wi...

Page 12: ...r unit 2 HA HB Indoor unit 3 HA HB Indoor unit 4 HA HB Indoor unit 5 HA HB Indoor unit 6 HA HB HA HB Touch screen NOTE 24 v DC Power wired controller Field Supplied wired controller HA HB NOTE Power f...

Page 13: ...oor unit 6 HA HB P Q Network Resistor HA HB Touch screen NOTE 24 v DC Power wired controller Field Supplied wired controller HA HB NOTE Power from IDU MAXIMUM WIRING LENGTH L1 L3 3937 ft 18 AWG 2 Core...

Page 14: ...th maintenance schedule In addition Clean condensate tray with suitable cleaning agent Clean the grille and panel EVERY 12 MONTHS Follow 6 month maintenance schedule In addition Be sure all electrical...

Page 15: ...26 Press OK to confirm and exit the setting interface Fig 26 Non Programmable Controller Setting IDU Address Programmable Controller When setting an address connect only one wired controller to an in...

Page 16: ...u want to set See Fig 28 Press MENU OK to send this address to the IDU Fig 28 Programmable Controller Setting IDU Address 4 Press BACK twice or wait 30 seconds to automatically exit the parameter sett...

Page 17: ...ing Mode Conflict Error E1 Communication Error Between Indoor and Outdoor Unit E2 Check Indoor Temperature Sensor T1 E4 Check Evaporator Outlet Temperature Sensor T2B E5 Check Evaporator Temperature S...

Page 18: ...t and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance signal wires from electromagnetic source PC boar...

Page 19: ...ETTINGS Fig B SW8 SETTINGS OFF Auto Addressing Mode Default ON Factory Test Mode OFF Normal Mode Default ON Factory Self Checking Mode OFF Standard Indoor Unit Default ON Mode Priority Indoor Unit HP...

Page 20: ...20...

Page 21: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 20 40VMF002 01 Printed in U S A Form 40VMF 4SI Pg 21 07 20 Replaces 40VMF...

Reviews: