21
INDOOR UNIT ACCESSORY COILS — HYDRONIC
HEATING CAPACITIES
LEGEND
*Based on 5 psig steam, 60 F entering-air temperature. All steam coils
are non-freeze type.
†Based on 200 F entering water, 20 F water temperature drop, 60 F
entering-air temperature.
NOTES:
1. Maximum operating limits for heating coils: 175 psig at 400 F.
3. See Heating Correction Factors table.
INDOOR UNIT ACCESSORY COILS — HEATING
CORRECTION FACTORS
NOTE: Multiply capacity given in the Hydronic Heating Capacities table
by the correction factor for conditions at which unit is actually operating.
Correct leaving-air temperature using formula in Note 2 of Hydronic
Heating Capacities table.
INDOOR UNIT FAN PERFORMANCE DATA — 0.0-1.2 ESP
LEGEND
Bold
indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive is required. Refer to fan motor
and drive tables, pages 35 and 36, to complete the selection.
NOTES:
1. Maximum allowable fan speed is 1200 rpm for all sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in. fil-
ters, and unit casing. See table at right for factory-supplied filter
pressure drop.
INDOOR UNIT FACTORY-SUPPLIED
FILTER PRESSURE DROP (in. wg)
UNIT
40RMQ
AIRFLOW
(Cfm)
1-ROW
STEAM*
2-ROW
HOT WATER COIL†
Cap.
Ldb
Cap.
Ldb
Gpm
PD
008
2,250
3,000
3,750
168
209
240
129
123
117
174.0
206.0
238.0
133
124
118
17.4
20.6
23.8
4.0
5.2
6.5
012
3,000
4,000
5,000
209
243
279
123
115
111
299.0
275.0
316.0
152
124
119
29.9
27.5
31.6
5.0
6.6
8.2
016
4,500
6,000
7,500
402
458
479
141
129
118
412.0
471.0
529.0
145
133
125
41.2
47.1
52.9
4.5
5.5
6.6
Cap. —
Capacity (Btuh in thousands)
Ldb —
Leaving-Air Dry-Bulb Temp (F)
PD
—
Pressure Drop (ft water)
2. Leaving db = ent db (F) +
Capacity (Btuh)
1.1 x cfm
HOT WATER COIL
Water Temp
Drop (F)
Ent Water
Temp (F)
Entering-Air Temp (F)
40
50
60
70
80
10
140
0.72
0.64
0.57
0.49
0.41
160
0.89
0.81
0.74
0.66
0.58
180
1.06
0.98
0.90
0.83
0.75
200
1.22
1.15
1.07
1.00
0.92
220
1.39
1.32
1.24
1.17
1.09
20
140
0.64
0.57
0.49
0.41
0.33
160
0.81
0.74
0.66
0.58
0.51
180
0.98
0.91
0.83
0.75
0.68
200
1.15
1.08
1.00
0.93
0.85
220
1.32
1.25
1.17
1.10
1.02
30
140
0.56
0.49
0.41
0.33
0.24
160
0.74
0.66
0.58
0.51
0.43
180
0.91
0.83
0.76
0.68
0.60
200
1.08
1.00
0.93
0.85
0.78
220
1.25
1.18
1.10
1.03
0.95
STEAM COIL
Steam Pressure
(psig)
Entering-Air Temp (F)
40
50
60
70
80
0
1.06
0.98
0.91
0.85
0.78
2
1.09
1.02
0.95
0.89
0.82
5
1.13
1.06
1.00
0.93
0.87
UNIT
40RMQ
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
008
2,250
359
0.32
472
0.44
560
0.55
634
0.65
700
0.75
759
0.86
814
0.96
2,600
415
0.45
516
0.57
599
0.68
669
0.79
732
0.90
790
1.01
843
1.11
3,000
478
0.62
569
0.75
645
0.86
712
0.98
773
1.09
828
1.20
879
1.32
3,400
542
0.82
624
0.95
695
1.08
758
1.20
815
1.31
869
1.43
918
1.55
3,750
598
1.03
673
1.17
740
1.29
800
1.42
855
1.60
906
1.66
954
1.78
012
3,000
471
0.61
564
0.74
642
0.86
710
0.97
771
1.09
827
1.20
878
1.31
3,500
550
0.87
632
1.00
703
1.13
766
1.25
824
1.37
877
1.49
926
1.60
4,000
628
1.17
701
1.31
766
1.44
825
1.57
879
1.69
930
1.82
978
1.94
4,500
706
1.53
772
1.67
832
1.81
887
1.94
938
2.07
987
2.20
1032
2.33
5,000
785
1.93
845
2.08
900
2.22
952
2.36
1000
2.50
1045
2.63
1089
2.76
016
4,500
405
0.54
507
0.79
592
1.03
667
1.28
735
1.54
797
1.80
854
2.06
5,300
476
0.85
566
1.13
643
1.40
713
1.68
776
1.97
835
2.26
890
2.55
6,000
539
1.20
620
1.50
691
1.81
756
2.11
816
2.42
872
2.73
924
3.05
6,800
611
1.69
683
2.03
748
2.36
809
2.69
865
3.03
918
3.37
968
3.71
7,500
674
2.22
740
2.58
800
2.93
857
3.29
910
3.65
960
4.02
1008
4.38
Bhp —
Brake Horsepower Input to Fan
ESP —
External Static Pressure
UNIT
40RMQ
AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
008
2,250
3,000
3,750
0.07
0.11
0.15
012
3,000
4,000
5,000
0.11
0.17
0.23
016
4,500
6,000
7,500
0.08
0.12
0.17