18
NOMINAL CAPACITIES
NOTES:
1. Gross cooling capacity is based on 67 F wb, 80 F db air entering indoor unit and 95 F db air enter-
ing outdoor unit.
2. Net heating capacity is based on 70 F db air entering indoor unit and 47 F db, 43 F wb air entering
outdoor unit. Includes indoor fan heat and defrost effects.
INTEGRATED HEATING CAPACITIES
LEGEND
NOTES:
1. To obtain total outdoor unit power, add outdoor fan kW shown to compressor draw:
38AQS008 — .96 kW; 38AQS012 and 016 — 1.4 kW.
2. Ratings are without supplementary heat and are based on 70 F db air entering indoor unit.
Wet-bulb temperature entering outdoor unit varies with dry bulb; at 47 F db, wb is 43 F; at
17 F db, wb is 15 F.
OUTDOOR UNIT
38AQS
INDOOR UNIT
40RMQ
AIRFLOW
(Cfm)
GROSS COOLING
CAPACITY (Btuh)
NET HEATING
CAPACITY (Btuh)
008
008
3000
89,000
83,000
012
012
4000
113,000
111,000
016
016
6000
179,000
164,000
OUTDOOR
UNIT
38AQS
INDOOR
UNIT
40RMQ
AIRFLOW
(Cfm)
TEMPERATURE OF AIR ENTERING OUTDOOR UNIT (F db)
–10
0
10
17
20
Cap.
kW
Cap.
kW
Cap.
kW
Cap.
kW
Cap.
kW
008
008
3000
21.7
3.4
30.4
3.8
39.4
4.3
45.8
4.6
48.3
4.8
012
012
4000
33.3
4.2
43.4
4.8
54.2
5.4
61.8
5.8
65.1
6.0
016
016
6000
54.1
7.2
68.3
8.0
83.2
8.8
93.8
9.4
98.9
9.7
OUTDOOR
UNIT
38AQS
INDOOR
UNIT
40RMQ
AIRFLOW
(Cfm)
TEMPERATURE OF AIR ENTERING OUTDOOR UNIT (F db)
30
40
47
50
60
Cap.
kW
Cap.
kW
Cap.
kW
Cap.
kW
Cap.
kW
008
008
3000
56.2
5.3
75.9
5.9
83.4
6.3
86.8
6.5
98.4
7.1
012
012
4000
74.5
6.7
100.0
7.5
111.0
8.1
116.0
8.4
132.0
9.2
016
016
6000
112.0
10.6
149.0
11.7
163.0
12.3
171.0
12.7
194.0
13.7
Cap. —
Integrated Heating Capacity (1000 Btuh) — includes
indoor-fan motor heat and effects of defrost.
kW
—
Total Compressor Motor Power Input
Performance data