Installation, Start-Up

and Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13

Step 1 − Complete Pre-Installation Checks

. . . 3

• UNPACK UNIT
• INSPECT SHIPMENT
• BEFORE INSTALLATION

Step 2 − Select Location

. . . . . . . . . . . . . . . . . . . . 4

Step 3 − Mount Unit

. . . . . . . . . . . . . . . . . . . . . . . . 6

• TO MOUNT UNIT
• TO INSTALL REMOTE THERMOSTAT

Step 4 − Connect Refrigerant Piping

. . . . . . . . 7

Step 5 − Connect Condensate Drain Line

. . . 10

Step 6 − Make Electrical Connections

. . . . . . 11

Step 7 − Install Remote Thermostat

. . . . . . . . 12

Step 8 — Make Connections Between

Indoor and Outdoor Units

. . . . . . . . . . . . . . . . 12

• COOLING ONLY SYSTEMS
• HEAT PUMP SYSTEMS

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-15

After Extended Shutdown

. . . . . . . . . . . . . . . . . . 13

Seasonal Changeovers

. . . . . . . . . . . . . . . . . . . . . 13

Adjusting Airflow

. . . . . . . . . . . . . . . . . . . . . . . . . . 14

Operating Mode Memory

. . . . . . . . . . . . . . . . . . . 14

Automatic Operation (Auto.) Mode

. . . . . . . . . . 14

Operating Sequence

. . . . . . . . . . . . . . . . . . . . . . . 14

• FAN OPERATION
• COOLING MODE OPERATION
• HEAT PUMP OPERATION (40QAE ONLY)
• DEFROST (40QAE ONLY)
• SYSTEM SAFETIES
• SPECIAL OPERATION, HEATING

CLEANING AND MAINTENANCE

. . . . . . . . . . . 15,16

Lubrication

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

To Remove and Clean or Replace

Air Filters

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

• TO REMOVE AIR FILTERS
• TO CLEAN OR REPLACE FILTERS

To Clean Indoor Unit Bottom Panel

. . . . . . . . . 16

To Clean Indoor Coil

. . . . . . . . . . . . . . . . . . . . . . . 16

To Clean Outdoor Coil (Outdoor Unit)

. . . . . . . 16

To Clean Condensate Drains

. . . . . . . . . . . . . . . . 16

• TO CLEAN OR REPLACE DRAIN PAN

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Before Calling for Service

. . . . . . . . . . . . . . . . . . 16

• IF SYSTEM FAILS TO OPERATE

FRESH AIR INSTALLATION OPTIONS

. . . . . . . 16

Ventilation-Air Accessory

. . . . . . . . . . . . . . . . . . . 16

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . 17-20

START-UP CHECKLIST

. . . . . . . . . . . . . . CL-1, CL-2

SAFETY CONSIDERATIONS

Installing and servicing air-conditioning equipment can be

hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install or service air-conditioning equipment.

Untrained personnel can perform basic maintenance, such

as cleaning and replacing filters. All other operations should
be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in lit-
erature and on tags and labels attached to unit.

Follow all safety codes. Wear safety glasses and work gloves.

Use quenching cloth for brazing operations. Have fire ex-
tinguisher available. Read these instructions thoroughly. Con-
sult local building codes and National Electrical Code (NEC)
for special installation requirements.

Before installing or servicing system, always turn off
main power to system. There may be more than one dis-
connect switch. Turn off accessory heater power if ap-
plicable. Electrical shock can cause personal injury.

INSTALLATION

The 40QAB ceiling-suspended fan coil unit (Fig. 1) is typi-

cally installed with the 38HDC or 38HDS outdoor condens-
ing unit, and the 40QAE unit is typically installed with the
38QRC heat pump.
NOTE: The 40QAE unit can also be installed with either the
38HDC or HDS condensing units. Refer to Table 1 to make
sure the correct indoor unit(s) is installed with the correct
outdoor unit.

Installation instructions for 40QA fan coil units are con-

tained in this manual. Refer to this manual for proper in-
stallation of the complete system. Note that the outdoor units
are shipped with installation and service instructions for ba-
sic installation of the outdoor section. Be sure to make the
connections in Cooling-Only Systems and Heat Pump Sys-
tems sections on page 12 of this literature so that the unit
will operate properly with the 40QA mircoprocessor control
system.

Fig. 1 — 40QA Ceiling-Suspended Fan Coil Unit

40QA024-060

Ceiling-Suspended Fan Coil Units

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

3d 2d

PC 111

Catalog No. 534-052

Printed in U.S.A.

Form 40QA-3SI

Pg 1

4-96

Replaces: 40QA-1SI

Summary of Contents for 40QA

Page 1: ...ns should be performed by trained service personnel When working on air conditioning equipment observe precautions in lit erature and on tags and labels attached to unit Follow all safety codes Wear s...

Page 2: ...ure is below 55 F the accessory low ambient or win ter start kit will be required Systems using 38HDS units can operate down to 40 F outdoor air temperature as shipped from the factory If operation at...

Page 3: ...r ft 150 30 CONDENSATE DRAIN CONNECTION Pipe Thread MPT CONDENSATE DRAIN SIZE in 3 4 LEGEND TXV Thermostatic Expansion Valve Field reconfigured to 18 000 Btuh 11 2 tons See Before Installa tion sectio...

Page 4: ...ove ft 65 Maximum Lift Fan Coil Below ft 150 CONDENSATE DRAIN CONNECTION Pipe Thread MPT CONDENSATE DRAIN SIZE in 3 4 Field reconfigured to 18 000 Btuh 11 2 tons See Before Installation section on pag...

Page 5: ...369 on bottom When facing unit discharge UNIT 40QA WEIGHT lb A B E F G QAB QAE ft in mm ft in mm ft in mm ft in mm ft in mm 024 108 110 4 215 16 1294 3 10 1169 4 15 8 1260 1 95 8 549 036 117 119 4 10...

Page 6: ...t of the unit Wooden Structure Install hanging bolts on a square wooden piece placed over beams Newly Built Concrete Slab Install hanging bolts with in serts embedded bolts etc Metal Structure Install...

Page 7: ...cooler buried section during extended periods of unit shutdown causing refrigerant slugging and possible com pressor damage at start up To connect piping 1 Install insulation Insulate supply and retu...

Page 8: ...nstall factory supplied piston enclosed in a bag taped inside the out door unit into the AccuRater metering device located in the service valve on the outdoor unit Fig 14 IMPORTANT The factory supplie...

Page 9: ...ls Check outdoor unit name plate for required charge NOTES 1 All pistons are Chattleff 9B9 type 2 All cooling units have a full factory charge for the smallest possible system combination 3 Service va...

Page 10: ...ndensate pump may be ordered as a field installed accessory Table 6 Required Piston Size for AccuRaterT Metering Device Cooling Only Condensing Units With Heat Pump Fan Coil Units INDOOR UNIT 40QAE OU...

Page 11: ...nect to the fan coil unit Place wire through hole on the control box Fig 18 Connect wire to high voltage ter minal board TB1 and ground screw When routing the wire in the unit use care to keep the wir...

Page 12: ...rminal block Connect the wires Y1 to Y and C to C See Fig 20 HEAT PUMP SYSTEMS The following connections must be made to the 38QRC unit for it to operate as a system with the indoor unit Route 6 wires...

Page 13: ...ave been installed and that the discharge louvers are positioned correctly After Extended Shutdown If the system has been turned off for more than 12 hours turn on the indoor and outdoor unit disconne...

Page 14: ...r COOLING MODE OPERATION When the room ther mostat senses a demand for cooling the fan coil relay board is energized The indoor fan s will start in the selected speed if it is not already operating Th...

Page 15: ...o prevent possible reverse rotation of the compressor Should any of these devices trip after the compressor is energized the Cycle LOC protection device will lock out the outdoor unit turn it off to p...

Page 16: ...ins to flush out debris To Clean Condensate Drains Clean all drains and drain pans at the start of each cooling season Check the flow by pouring water into the drain TO CLEAN OR REPLACE DRAIN PAN 1 Pl...

Page 17: ...hermostat Outdoor unit outdoor coil restricted Remove obstruction Fan speed is set too low Adjust fan speed to high or auto using the Fan button on the thermostat System does not heat properly Air fil...

Page 18: ...S Pump Shutoff Switch RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay SSDR Safety Switch Delay Relay TB Terminal Block TDR Time Delay Relay TRAN Transformer Terminal Marked Terminal Unm...

Page 19: ...Heat pump fan coil units only Fig 25 Typical System Wiring Cooling Only Systems or Condensing Unit with Heat Pump Fan Coil Unit Systems 19...

Page 20: ...Fig 26 Typical System Wiring Heat Pump Systems 20...

Page 21: ......

Page 22: ...l programs include a video cassette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 9...

Page 23: ...GLE PHASE POWER HAS GROUND WIRE BEEN CONNECTED HAS THE CORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SI...

Page 24: ...BEEN ON FOR 24 HOURS MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG...

Reviews: