background image

2

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air−conditioning equipment
can be hazardous due to system pressures, electrical components,
and equipment location (roofs, elevated structures, etc.).

Only trained, qualified installers and service mechanics should
install, start−up, and service this equipment.

Untrained personnel can perform basic maintenance functions such
as cleaning coils. All other operations should be performed by
trained service personnel.

When working on the equipment, observe precautions in the
literature and on tags, stickers, and labels attached to the
equipment.

Follow all safety codes. Wear safety glasses and work gloves. Keep
quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.

Read these instructions thoroughly and follow all warnings or
cautions included in literature and  attached to the unit. Consult
local building codes and National Electrical Code (NEC) for
special requirements. Recognize safety information.

This is the safety−alert symbol . When you see this symbol on the
unit and in instructions or manuals, be alert to the potential for
personal injury. Understand these signal words: DANGER,
WARNING, and CAUTION. These words are used with the
safety−alert symbol. DANGER identifies the most serious hazards
which  will result in severe personal injury or death. WARNING
signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices which may result in
minor personal injury or product and property damage. NOTE is
used to highlight suggestions which will result in enhanced
installation, reliability, or operation.

WARNING

The 9 and 12K units are for single room application only.

!

WARNING

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal
injury or death.

Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.

EXPLOSION HAZARD

Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.

Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.

!

WARNING

CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment
damage or improper operation.

Do not bury more than 36 in. (914 mm) of refrigerant pipe
in the ground. If any section of pipe is buried, there must be
a 6 in. (152 mm) vertical rise to the valve connections on
the outdoor units. If more than the recommended length is
buried, refrigerant may migrate to the cooler buried section
during extended periods of system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start−up.

!

CAUTION

Summary of Contents for 40MBDQ series

Page 1: ...rposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 INSTALLATION CLEARANCES 7 MAINTENANCE CLEARANCES 7...

Page 2: ...injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property...

Page 3: ...s If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wal...

Page 4: ...ues exist a 14 2 stranded shielded wire can be used to replace L2 and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only Sizes 36 58 Recommended Connection...

Page 5: ...mm 700 200 506 450 137 537 30 152 599 186 50 741 360 84 140 84 84 18 1 18 In 34 65 8 27 26 54 23 62 5 51 27 80 1 97 5 35 30 79 7 48 1 57 36 22 20 3 07 5 83 3 46 4 41 54 mm 880 210 674 600 140 706 50...

Page 6: ...6 DIMENSIONS CONT Airflow Airflow Fig 5 Indoor Unit Sizes 58K...

Page 7: ...in 45cm 7 8 in 20cm 11 81 in 30cm 4 in 10cm Bottom Return Blower Motor Service Clearance Filter Service Clearance Blower Motor Service Clearance PCB Board Service Clearance Fig 7 Maintenance Clearance...

Page 8: ...ely from the unit The ceiling grid must not be supported by any part of the unit or any associated wiring or piping work CAUTION MOUNTING THE UNIT 1 INSTALLING HANGER BOLTS Install the hanger bolts at...

Page 9: ...as close to the unit as possible see Fig 17 S Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 100 S When multiple units are connected to a com...

Page 10: ...nect the drainpipe to the connector D see Fig 20 d Plug the power cable of the external pump to CN13 PUMP pin and plug the water level sensor cable to the CN5 WATER to enable the pump see Fig 23 Fig 1...

Page 11: ...w these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 27 2 Using a piece of tubing or pipe fill the condensate lift pump reservoir with 70 oz of wa...

Page 12: ...1 T2 T26 T3 T4 are sub menus for thermistors Do not select for setting external static pressure Fig 30 Wired Controller Menu Selection 1 If setting the external static pressure manually select SP and...

Page 13: ...WG 0 10 0 216 0 336 0 528 0 0 64 Pa 25 54 84 132 0 160 36 In WG 0 168 0 312 0 48 0 62 0 0 64 Pa 42 78 120 155 0 160 48 In WG 0 18 0 404 0 616 0 64 0 0 64 Pa 45 101 154 160 0 160 58 In WG 296 0 416 58...

Page 14: ...14 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 32 Fan Performance 40MBDQ09...

Page 15: ...15 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 33 Fan Performance 40MBDQ12...

Page 16: ...16 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 34 Fan Performance 40MBDQ18...

Page 17: ...17 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 35 Fan Performance 40MBDQ24...

Page 18: ...18 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 36 Fan Performance 40MBDQ36...

Page 19: ...19 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 37 Fan Performance 40MBDQ48...

Page 20: ...20 FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 38 Fan Performance 40MBDQ58...

Page 21: ...3 65 0 952 1000 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS Fig 39 Connection Diagrams sizes 09 to 24 Fig 40 Connection Diagrams sizes 36 and 58 Fig 41 Control and Power Wiring on Indoor Unit sizes...

Page 22: ...ces Table 9 Flare Nut Spacing OUTER DIAM mm A mm Max Min 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 5 8 15 88 0 09 2 2 0 08 2 0 Bar Copper pipe Clamp handle Red a...

Page 23: ...is used relocate the IR receiver within line of sight of remote location using the 6 ft cable included The factory location of the IR receiver is inside the control box see Fig 48 A150642 Fig 48 Contr...

Page 24: ...unit 4 Push the manual switch once to energize the unit The set conditions of manual operation are as follows Preset set point 76_F 24_C Fan speed AUTO Discharge air direction Pre set position based...

Page 25: ...otection H 4 times X E3 Indoor fan speed has been out of control H 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit H 6 times X E5 Evaporator coil temperature sensor T2 ope...

Page 26: ...7310 W Morris St D Indianapolis IN 46231 Edition Date 09 18 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM 40MBD...

Reviews: