background image

42

this rule is violated, even at very low face velocities. The same

result is often experienced if after-market fin coatings are

applied.

If a NuFin hydronic coil is installed with correct airflow, but

opposite piping hand, and counterflow is maintained, steps

must be taken to ensure that the coil is continuously vented,

and that the water velocity is maintained to prevent the coil

from air-binding. 

Hot or cold areas of the coil face (or otherwise broad tem-

perature differences and stratification) are usually indications

that one or more circuits are air-locked internally. This can

result in coil freeze-up (a condition NOT covered by warranty).

Refrigerant coils may be rotated for opposite hand applica-

tions, maintaining the proper airflow direction. 

Do not reposition the distributor(s), they will perform equal-

ly well in upflow or downflow positions. When soldering

expansion valves to up-feed distributors, use the minimum

satisfactory amount of solder to prevent damaging the valve or

plugging passages.
DIRECT EXPANSION COILS — Rotate the coil in vertical

plane and reinstall. Distributor must be on downstream side of

coil. (Refer to Fig. 51).
CHILLED WATER AND HOT WATER COILS  — These

coils can be rotated. If coil is rotated in vertical plane and rein-

stalled with counterflow maintained, supply will be at the top of

the coil and return will be at the bottom. Ensure coil is continu-

ously vented and water velocity is maintained to prevent air

binding.

STEAM INNER DISTRIBUTING TUBE COILS  —  Rotate

in horizontal plane and reinstall. See Fig. 51.
PIPING — Direct expansion, chilled water, and hot water

coils should always be piped for counterflow. (Fluid should

enter the coil at the leaving-air side.) Steam coils must have the

condensate connection at bottom of coil.

To determine intervals for cleaning coils in contaminated air

operations, pressure taps should be installed across the coils

and checked periodically. Abnormal air pressure drop will indi-

cate a need for cleaning the coils.
Annual maintenance should include:

1. Clean the line strainers.
2. Blow down the dirt leg.
3. Clean and check operation of steam traps.
4. Check operation of control valves. 
5. Check the operation of check valves to prevent conden-

sate flowback.

6. Check operation of thermostatic air vents, if used. A float

and thermostatic trap will contain a thermostatic air vent.

When the bellows is ruptured, it will fail closed.

7. Check operation of vacuum breakers.
8. Check operation of the thermal protection devices used

for freeze-up protection.

9. Steam or condensate should not be allowed to remain in

the coil during the off season.This will prevent the forma-

tion and build up of acids.

There are additional precautions and control strategies, as

found in various catalogues and in the ASHRAE Fundamentals

Handbook and in the Carrier System Design Guide — Piping

Section, when the entering-air temperature to the coil falls be-

low 35 F. These conditions occur when IDT coils are used for

pre-heat and/or face and bypass applications.
Freeze up protection:

1. Use a strainer in the supply line and the dirt leg ahead of

the trap.

2. Use a vacuum breaker in the return.
3. Do not use overhead returns from the coil. A floodback

can occur.

4. An immersion thermostat to control outdoor-air dampers

and the fan motor is recommended. This control is acti-

vated when the steam supply fails or the condensate

temperature drops below a predetermined temperature,

usually 120 F.

5. On low pressure and vacuum systems, the immersion

thermostat may be replaced by a condensate drain with a

thermal element. This element opens and drains the coil

when the condensate temperature drops below 165 F.

Note the thermal condensate drain is limited to 5 psig

pressure. At greater coil pressures they will not open.

In spite of the precautions listed above, a coil may still

freeze up. An oversize capacity coil, at partial load, with a

modulating steam control valve will occasionally freeze.

Freezing occurs in the 20 F to 35 F range of entering-air

temperatures. A better installation would be an undersize coil,

with an on/off control valve with thermostatic control in the

outside air, set at 35 F air temperature, installed downstream of

the first coil; or setting the minimum steam pressure at 5 psig.

Filters

FILTER SECTIONS — See Table 14 for filter data. Filters

are field supplied.

Flat filter section can use 2-in. or 4-in. thick filters. The flat

filter section as shipped accepts 2-in. filters. Remove spacer in

each filter track to provide the 4-in. space required to accom-

modate 4-in. filters.

On all filter sections, filters are pushed into the track until

they touch the opposite side of the unit. Any remaining space is

taken up by the adjustable 2-piece sheet metal spacer.  See Fig.

52 for filter arrangements.

CAUTION

Chilled and hot water coils must not be rotated horizon-

tally. If coils are rotated horizontally, severe water blow-off

will result.

DX AND ALL

WATER COILS

STEAM COILS

ONLY

Fig. 51 — Coil Rotation

Summary of Contents for 39LH

Page 1: ...jury to personnel and damage to equipment or property when operating this equipment use good judgment and follow safe practices as outlined below DANGER NEVER enter an enclosed fan cabinet or reach in...

Page 2: ...ant system open to air any longer than the actual time required to service the equipment Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cann...

Page 3: ...39 4441 28N 28N Coil Model Number Coil Type A Chilled Water Coil Orientation S Slant V Vertical F Full A S 4 Rows 4 6 8 12 12 16 20 22 26 32 Tubes in Face 24 30 36 38 Q Circuiting Q Quarter H Half D D...

Page 4: ...N Coil Model Number Coil Type E Direct Expansion Coil Orientation V Vertical B Face Split Half Circuit E V 4 Rows 4 6 16 12 16 20 26 Tubes in Face 30 36 H Circuiting A Face Split Quarter Circuit Fin M...

Page 5: ...A 1250 Position 12 is 0 if rpm is 3 digits 1 Motor Horsepower Constant Speed K Forward Curve without VFD 2 Forward Curve with VFD 03 06 08 10 12 15 18 21 25 01 02 03 04 05 06 07 08 09 10 11 12 13 hp h...

Page 6: ...6 PRE HEAT WATER OR PRE HEAT STEAM PHW LEGEND Fig 8 Position 4 Unit Configuration Model Component Sequence Also Shown COMB Combination PH Preheat POS Position Factory installed option components...

Page 7: ...LY 6 A B C 39LH VERTICAL HEATING SMALL FACE AREA A B C 7 ACCESSORY SECTIONS MIXING BOX 8 10 FILTER MIXING BOX 9 FILTER MIXING BOX FLAT FILTER 11 ANGLE FILTER 12 PLENUM 13 HOT WATER OR STEAM PREHEAT CO...

Page 8: ...29 1 29 1 37 0 40 9 40 9 48 8 120 168 246 282 324 372 417 444 492 7 39LH 21 3 25 2 29 1 29 1 29 1 37 0 40 9 40 9 48 8 220 308 452 517 594 682 764 814 902 ACCESSORIES Unit Size 03 06 08 10 12 15 18 21...

Page 9: ...which fits inside the larger one This allows the channel to be adjusted to the required length for installation Channels are shipped on top of the unit The 2 sections of each channel are shipped one...

Page 10: ...16 3 1 2 119 16 0 77 8 1 33 4 2 39 16 18 5 51 16 5 55 16 3 415 16 3 33 8 0 77 8 1 33 4 2 117 16 21 6 51 4 6 51 8 3 415 16 3 33 8 0 77 8 1 33 4 2 117 16 25 6 51 4 6 51 8 4 015 16 2 39 16 0 77 8 1 33 4...

Page 11: ...10 1 11 7 14 2 16 3 Chilled Water 1 2 in OD Tube Small Face Area 4 Row 2 1 3 3 3 9 4 1 5 1 6 3 7 3 8 7 9 8 6 Row 2 4 3 7 5 1 5 9 6 6 8 3 9 5 11 8 13 5 8 Row 2 7 4 1 6 4 7 4 8 4 10 7 12 1 14 7 17 2 Hot...

Page 12: ...ENSION ROD FIELD SUPPLIED SUSPENSION CHANNEL FACTORY SUPPLIED OPTION MOUNT UNIT TO SUSPENSION CHANNELS THROUGH PROVIDED IN LIFTING BRACKET 7 16 IN DIAM HOLES FACTORY SUPPLIED BOLTS CONNECTING SUSPENSI...

Page 13: ...flanges top and sides around the coil fan section and the accessory section See Fig 15 NOTE If the section to section gasket installed at the factory is damaged while splitting the unit obtain the re...

Page 14: ...ust be connected to the 1 in hollow jackshaft that drives the interconnecting linkage bar Connection to any other shaft is not recommended DUCTWORK ATTACHMENT Ductwork should be flanged out and attach...

Page 15: ...7BJ033 24 4 0 375 0 625 150 N A N A 133 90 725 33AMACTGV 266 HF27BJ034 24 6 0 475 0 750 135 N A N A 266 90 450 DIMENSIONS ft in Fig 19 Mixing Box Duct Connections UNIT 39L A B C D E F G H J K L 03 2 3...

Page 16: ...ct Use a nonconductive nonhardening sealant Permagum manufactured by Schnee Morehead or sealing compound thumb grade manufactured by Calgon are acceptable materials POWER KNOCKOUTS Panels are not prov...

Page 17: ...ion on factory supplied drive 1 Always adjust the motor position so that V belts can be installed without stretching over grooves Forcing belts can result in uneven stretching and a mismatched set of...

Page 18: ...n accordance with Steps 1 6 Running the drive for a few revolutions or minutes will help seat the belt s in the groove s This relatively early re tensioning may reduce or minimize the amount of re ten...

Page 19: ...illustrates the normal piping components and the suggested locations for high medium or low pressure steam coils The low pressure application zero to 15 psig can dispense with the in petcock for conti...

Page 20: ...g the following precautions Install a drip line and trap on the pressure side of the inlet control valve Connect the drip line to the return line downstream of the return line trap To prevent scale or...

Page 21: ...1 2 D 48 21 2 57 21 2 57 21 2 66 21 2 D Double Circuit F Full Circuit H Half Circuit Q Quarter Circuit SMALL FACE AREA 39LB 39LC 39LF COIL TYPE CIRCUITING UNIT SIZE 03 06 08 10 12 Face Area sq ft 2 72...

Page 22: ...il Run full size to the trap reduce at the trap 2 Use float and thermostatic traps only for condensate re moval Trap size selection should be based on the differ ence in pressure between the steam sup...

Page 23: ...peration is necessary 2 Bypass to be the same size as trap orifice but never less than 1 2 inch Fig 27 Dripping Steam Supply to Condensate Return NOTES 1 Flange or union is located to facilitate coil...

Page 24: ...coil bank Fig 29 Multiple Coil Low Pressure Piping Gravity Return NOTES 1 Flange or union is located to facilitate coil removal 2 To prevent water hammer drain coil before admitting steam 3 Do not ex...

Page 25: ...prevent excessive heat from reaching diaphragm and internal parts Do not allow water to enter system Disassemble expansion valve before soldering if accessible for easy reassembly Use 95 5 tin antimo...

Page 26: ...w Split 13 15 16 18 18 18 18 18 18 Distributor Nozzle Size 2 2 3 4 4 5 5 6 6 6 ROW COIL Circuit Equivalent Length ft 39 20 47 24 51 26 59 30 67 34 Distributor Tube Length in Face Split 11 11 11 13 13...

Page 27: ...lit 111 2 111 2 111 2 111 2 111 2 13 111 2 13 111 2 13 Row Split 111 2 13 15 16 16 181 2 16 181 2 16 181 2 Distributor Nozzle Size 11 2 11 2 21 2 3 4 4 5 5 5 5 8 ROW COIL Circuit Equivalent Length ft...

Page 28: ...7 Fig 35 Expansion Valve Piping Fig 36 Distributor and Hot Gas Bypass Auxiliary Side Connector SPORLAN TYPE CARRIER PART NO CONNECTION SIZES in USED WITH DISTRIBUTOR TYPE NOZZLE SIZE Inlet ODM Solder...

Page 29: ...COIL Manifolding for 2 Face Splits Refer to Fig 38 and exter nally manifold as follows 1 Connect the 4 expansion valves to the 4 distributors on each coil and connect the 4 suction lines to the 15 dia...

Page 30: ...30 TXV Thermostatic Expansion Valve Fig 38 Face Split Coil Manifolding Typical TXV Thermostatic Expansion Valve Fig 39 Row Split Coil Manifolding Typical...

Page 31: ...ct switch or main circuit breaker in accor dance with NEC and other applicable codes Locate so that it is easily accessible and within sight of heater control box per NEC Article 424 19 and 424 65 Wea...

Page 32: ...32 NOTE All wiring must be copper and must conform to the NEC National Electrical Code Fig 41 Typical Electric Heater Wiring Schematic...

Page 33: ...175 114 142 3 150 57 71 2 80 72 90 2 90 51 8 500 53 144 180 3 200 125 156 3 175 62 78 2 80 79 98 2 100 59 8 500 62 72 90 2 100 91 114 2 125 12 7 3 6 19 9 500 17 55 69 2 70 48 60 1 60 24 30 1 30 30 38...

Page 34: ...port must be removed To change from upblast to horizontal discharge or from horizontal to upblast discharge the bearings must be relocated to keep the wheel centered in the housing To change from upbl...

Page 35: ...r freedom of movement 2 Check tightness of bearing setscrews or locking collars Fig 44 Also check tightness of setscrews on fan wheels and sheaves 3 Check tightness of fan shaft bearing mounting 4 Rec...

Page 36: ...ff motor power 2 Disconnect and tag power wires at motor terminals 3 Loosen motor brace to mounting rail attaching bolts Loosen belt tensioning bolts to adjust the motor position so V belts can be rem...

Page 37: ...are shipped see Fig 46 bottom coil baffle side hairpin baffle side header baffle top coil baffle These parts should be field installed onto the coil before placing the coil into the unit Once the baf...

Page 38: ...g 46 Field Installed Coils 39LA and LD only LEGEND Fig 47 Horizontal Unit Slant Coil Removal 39LA Units Sizes 03 21 1 Accessory Side Panel 8 Condensate Baffle 2 Left Side Panel 9 Holddown Screws 3 Top...

Page 39: ...er 6 Remove screws from inside baffle item 14 Leave baffle attached to left side panel Item 16 7 Remove left side panel Item 16 NOTE Support of fan section may be required after re moval of side panel...

Page 40: ...baffle to coil 4 Remove side panel s Item 6 NOTE Vertical units may require support of fan section after removal of side panels 5 If accessory is present remove accessory side panel Item 1 on left sid...

Page 41: ...om end of unit New holes must be cut in coil cover panel Original holes must be plugged and insulated New side panels may be necessary when changing coil hand NU FIN COILS The NuFin coil is airflow di...

Page 42: ...ill fail closed 7 Check operation of vacuum breakers 8 Check operation of the thermal protection devices used for freeze up protection 9 Steam or condensate should not be allowed to remain in the coil...

Page 43: ...tighten holddown bolts and then tighten bearing locking collar and setscrews 12 Make certain fan wheel does not rub sides of fan housing after installing new bearings 13 Recoat fan shaft with a rust i...

Page 44: ...44 16 20 25 16 20 25 25 25 16 20 20 SIZE 21 SIZE 25 Fig 52 Filter Arrangement 2 in and 4 in Flat...

Page 45: ...eel is recommended Lubrication MOTORS Lubricate in accordance with nameplate at tached to motor or with manufacturer s recommendations included with motor BEARINGS Fan Bearings Lubricate fan bearings...

Page 46: ...fan discharge panel Fig 56 2 Remove all of the panels from the fan section Fig 57 3 Remove the fan by removing the 4 screws on the corner of the fan sled On larger units the fan sled may be ex tremely...

Page 47: ...47 METRIC CONVERSION CHART...

Page 48: ...ght to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53390016 01 Printed in U S A Form 39L 7SI Pg 48 816 3 14 Replaces 39L...

Reviews: