
34
Table 13 — Field Wiring for Incoming Conductors
Sized for 125% of Heater Load
LEGEND
*Values are based on Table 310-16 of the NEC (National Electrical
Code) for 75 C insulated copper wire. Not more than 3 conductors
in a raceway.
NOTES:
1. Be sure to consider length of wiring run and possible voltage
drops when sizing wires.
2. Field power wiring — Heaters are furnished with a terminal
block sized for incoming copper conductors with 75 C insulation
rated to carry at least 125% of the heater load. However, con-
ductors can be sized to carry 100% of the heater load if the
heater is rated at 50 kW or more, and the heater is controlled by
a cycling device such as a multi-stage thermostat, step control-
ler, or SCR (silicon control rectifier) power controller. Terminal
blocks and knockouts are sized to handle either 100% or 125%
conductors.
Discharge Modification —
If field modification of
discharge position is required, 39L fans can be converted (by a
skilled mechanic) to any standard hand and discharge without
any additional parts. (NOTE: This does not apply to a model
change conversion.) All mounting holes are prepunched.
To convert a 39L fan, note the following:
1. Sizes 03-18 w — See Fig. 42. It is not necessary to re-
move the bearing support channels from the fan housing.
Sizes 21 and 25 — See Fig. 43. The “A” frame support
must be removed. To change from upblast to horizontal
discharge or from horizontal to upblast discharge, the
bearings must be relocated to keep the wheel centered in
the housing. To change from upblast front (UBF) to up-
blast rear (UBR) or from top horizontal front (THF) to
top horizontal rear (THR) or vice versa, turn the entire fan
housing 180 degrees about its base.
2. The fan shaft may be driven out and reinstalled to place
the drive pulley on the opposite end.
3. The fan scroll is prepunched for horizontal or vertical dis-
charge to match the support angles at the base of the unit.
4. The motor and motor base may be rotated to place the
motor at the front or rear of the unit. Proper location is
that which results in the longest drive center line distance.
The motor conduit box location may need to be reversed.
5. When hand of fan is changed, it may be necessary to turn
the discharge panel inside-out to fit correctly with the fan
discharge. In this case, remove the existing insulation and
install new duct-liner type insulation on the opposite side
of the discharge panel.
6. Rebalancing of the unit is recommended.
WIRE SIZE
(AWG or kcmil)
LOAD AMPS*
WIRE SIZE
(AWG or kcmil)
LOAD AMPS*
Copper
Copper
12
16
1/0
120
10
24
2/0
140
8
40
3/0
160
6
52
4/0
184
4
68
250
204
3
80
300
228
2
92
350
248
1
104
400
268
500
304
AWG — American Wire Gage
kcmil — Thousand Circular Mils
Fig. 42 — Fan Discharge Positions, Sizes 03-18
LEGEND
THF
— Top Horizontal Front
THR — Top Horizontal Rear
UBF — Upblast Front
UBR — Upblast Rear
Summary of Contents for 39LH
Page 47: ...47 METRIC CONVERSION CHART...