26
Table 9 — Direct Expansion Coil Circuiting Data
LEGEND
* Where each TXV has the same number of circuits, that number is
shown once. When coil has an uneven number of circuits per TXV,
both values are shown.
†Factory-supplied distributors have factory-selected nozzle sizes
shown. If necessary, replace factory-supplied nozzles with field-
supplied and installed nozzles. Consult Electronic Catalog AHU
selection program for correct nozzle selection.
**May be field manifolded for either face split or row split.
LARGE FACE AREA (39LA, 39LD)
UNIT SIZE
03
06
08
10
12
CIRCUITING TYPE
Qtr
Half
Full
Qtr
Half
Full
Qtr
Half
Full
Qtr
Half
Full
Half
Full
CFM AT 550 FPM
1996
3245
4345
5247
6149
FACE AREA (sq ft)
3.63
5.90
7.90
9.54
11.18
TUBE FACE
16
20
24
24
24
TUBE LENGTH (in.)
26.1
34.0
37.9
45.8
53.7
NUMBER OF CIRCUITS
4
8
16
—
10
20
—
12
24
—
12
24
12
24
NUMBER OF TXVs
2
2
2
—
2
2
—
2
2
—
2
2
2
2
NUMBER OF CIRCUITS/TXV*
2
4
8
—
5
10
—
6
12
—
6
12
6
12
SUCTION CONNECTIONS
(in. OD)
7
/
8
1
1
/
8
1
3
/
8
—
1
1
/
8
1
3
/
8
—
1
1
/
8
1
5
/
8
—
1
1
/
8
1
5
/
8
1
1
/
8
1
5
/
8
DISTRIBUTOR CONNECTIONS
(in. OD)
7
/
8
7
/
8
1
1
/
8
—
7
/
8
1
1
/
8
—
7
/
8
1
5
/
8
—
7
/
8
1
5
/
8
7
/
8
1
1
/
8
4-ROW COIL
Circuit Equivalent Length (ft)
52
26
—
—
32
—
—
34
18
—
40
20
45
23
Distributor Tube Length (in.)
Face Split
11
11
—
—
11
—
—
13
15
—
13
15
13
15
Row Split
13
15
—
—
16
—
—
18
18
—
18
18
18
18
Distributor Nozzle Size†
2
2
—
—
3
—
—
4
4
—
5
5
6
6
6-ROW COIL
Circuit Equivalent Length (ft)
—
39
20
—
47
24
—
51
26
—
59
30
67
34
Distributor Tube Length (in.)
Face Split
—
11
11
—
11
13
—
13
15
—
13
15
13
15
Row Split
—
15
16
—
16
18
—
18
21
—
18
21
18
21
Distributor Nozzle Size†
—
2
3
—
3
3
—
4
4
—
5
5
6
6
LARGE FACE AREA (39LA, 39LD)
UNIT SIZE
15
18
21
25
CIRCUITING TYPE
Half
Full
Half
Full
Half
Full
Double
Half
Full
Double
CFM AT 550 FPM
8200
9740
11,880
13,750
FACE AREA (sq ft)
14.91
17.71
21.6
25.0
TUBE FACE
32
38
38
22U-22L
TUBE LENGTH (in.)
53.7
53.7
65.5
65.5
NUMBER OF CIRCUITS
16
32
19
38
19
38
—
22
44
88
NUMBER OF TXVs
2
4**
2
4**
2
4**
—
2
2
2
2
4
4
NUMBER OF CIRCUITS/TXV*
8
8
9-10
9-10
9-10
9-10
—
5-6
5-6
11
11
11
11
SUCTION CONNECTIONS
(in. OD)
1
3
/
8
1
3
/
8
1
3
/
8
1
3
/
8
1
3
/
8
1
1
/
8
—
1
1
/
8
1
1
/
8
1
3
/
8
1
3
/
8
1
5
/
8
1
5
/
8
DISTRIBUTOR CONNECTIONS
(in. OD)
1
1
/
8
1
1
/
8
1
1
/
8
1
1
/
8
1
1
/
8
1
1
/
8
—
7
/
8
7
/
8
1
3
/
8
1
3
/
8
1
3
/
8
1
3
/
8
4-ROW COIL
Circuit Equivalent Length (ft)
45
23
45
23
54
26
—
54
54
26
26
—
—
Distributor Tube Length (in.)
Face Split
15
16
16
16
16
16
3
/
4
—
12
12
15
15
—
—
Row Split
26
16
28
16
28
16
3
/
4
—
21
21
23
23
—
—
Distributor Nozzle Size†
8
4
10
5
10
5
—
8
8
5
5
—
—
6-ROW COIL
Circuit Equivalent Length (ft)
67
34
67
34
81
40
—
—
—
40
40
—
—
Distributor Tube Length (in.)
Face Split
15
16
16
18
16
18
1
/
2
—
—
—
15
15
—
—
Row Split
23
16
28
18
28
18
1
/
2
—
—
—
22
22
—
—
Distributor Nozzle Size†
8
4
10
5
10
5
—
—
—
5
5
—
—
AHU
— Air-Handling Unit Selection Program
TXV
— Thermostatic Expansion Valve (Field-supplied)
Summary of Contents for 39LH