background image

16

Condensate Drain — 

Install a trapped condensate drain

line at unit drain connection. Use 1-in. standard pipe.

Measure maximum design negative static pressure up-

stream from the fan. Referring to Fig. 20, height “H” must be

equal to or larger than negative static pressure at design operat-

ing conditions. Prime enough water in trap to prevent losing

seal (Differential 1). When the fan starts, Differential 2 is equal

to the maximum negative static pressure.

Provide freeze-up protection and insulation as required.

Variable Frequency Drive (VFD)  — 

Variable fre-

quency drives (VFDs) are used to modulate fan motor speed in

response to air volume requirements. To vary the motor speed,

a VFD changes the input frequency and line voltage into a

wide range of frequency and voltage outputs, while maintain-

ing a constant ratio of frequency to voltage. 

Since 2001, all 1-hp and greater motors supplied by Carrier

for the 39L series air handling units are designed and construct-

ed for use with variable frequency drives. If a field-supplied

motor is installed, ensure the motor is suitable for use with a

VFD.

If the lead length from the VFD to the motor is greater than

25 ft, Shaft Grounding Rings (SGR) are necessary to help dis-

sipate induced shaft voltages to ground and prevent motor

bearing damage.

Install Fan Motor — 

For field installation of motors, be

sure electrical junction box is toward the center of the unit.

This is necessary for drive and belts to be properly tightened.

Use smallest slots in motor mounting base that will accommo-

date motor and allow minimum overhang (Fig. 21). Be sure

that motor holddown bolts are tight on field-installed motor.
JUNCTION BOX CONDENSATE PREVENTION —

When air handlers are installed outdoors in a high humidity

environment or indoors where the apparatus room is used as a

fresh air plenum, precautions must be taken to prevent conden-

sation from forming inside the junction box of the internally

mounted motor.

Standard installation practice is to mount the motor starter

or fused disconnect box adjacent to the air handler and enclose

the power wiring to the motor in flexible conduit.

The sheet metal housing of the disconnect switch or motor

starter is not airtight (even when a box meeting NEMA

[National Electrical Manufacturers Association] IV standards

is used). Thus, warm moist air can migrate through the flexible

conduit to the junction box on the motor. With the motor

located inside the unit, the motor temperature is that of the cool

supply air; thus, condensate can form inside the junction box

and, possibly, on the live terminal lugs.

To prevent the moist air from migrating through the conduit

to the motor, seal the power wires inside the flexible conduit at

the motor starter or fused disconnect.

Use a nonconductive, nonhardening sealant. Permagum

(manufactured by Schnee Morehead) or sealing compound,

thumb grade (manufactured by Calgon), are acceptable

materials.
POWER KNOCKOUTS — Panels are not provided with

knockouts for the fan motor power wiring. Openings must be

drilled or punched in the exterior panels of the unit. It is recom-

mended that power wiring be routed through the discharge

panel whenever possible, as this panel is rarely removed for

service access.

Install Sheaves on Motor and Fan Shafts —

Factory-supplied drives are prealigned and tensioned, however,

Carrier recommends that you check the belt tension and align-

ment before starting the unit. Always check the drive align-

ment after adjusting belt tension.

When field installing or replacing sheaves, install sheaves

on fan shaft and motor shaft for minimum overhang. (See

Fig. 21.) Use care when mounting sheave on fan shaft; too

much force may damage bearing. Remove rust-preventative

coating or oil from shaft. Make sure shaft is clean and free of

burrs. Add grease or lubricant to bore of sheave before

installing.

The 39L fan, shaft, and drive pulley are balanced as a com-

plete assembly to a high degree of accuracy. If excessive unit

vibration is present after fan pulley replacement, the unit must

be rebalanced. For drive ratio changes, always reselect the mo-

tor pulley — do not change the fan pulley.

ALIGNMENT — Make sure that fan shafts and motor shafts

are parallel and level. The most common causes of mis-

alignment are nonparallel shafts and improperly located

sheaves. Where shafts are not parallel, belts on one side are

drawn tighter and pull more than their share of the load. As a

result, these belts wear out faster, requiring the entire set to be

replaced before it has given maximum service. If misalignment

is in the sheave, belts will enter and leave the grooves at an

angle, causing excessive belt cover and sheave wear.

1. Shaft alignment can be checked by measuring the

distance between the shafts at 3 or more locations. If the

distances are equal, then the shafts will be parallel.

2. Sheave alignment:

Fixed sheaves — To check the location of the fixed

sheaves on the shafts, a straightedge or a piece of string

can be used. If the sheaves are properly lined up the string

will touch them at the points indicated by the arrows in

Fig. 22.
Adjustable sheave — To check the location of adjustable

sheave on shaft, make sure that the centerlines of both

sheaves are in line and parallel with the bearing support

channel. See Fig. 22. Adjustable pitch drives are installed

on the motor shaft.

3. Rotating each sheave a half revolution will determine

whether the sheave is wobbly or the drive shaft is bent.

Correct any misalignment.

FAN OFF

TRAP CONDITION WHEN FAN 

S

TART

S

FAN RUNNING AND CONDEN

S

ATE DRAINING

DIFFERENTIAL
            1

DRAIN NIPPLE

DIFFERENTIAL
           2

COOLING COIL
DRAIN PAN

H

Fig. 20 — Condensate Drain

CAUTION

With adjustable sheave, do not exceed maximum fan rpm.

816

Summary of Contents for 39LH

Page 1: ...jury to personnel and damage to equipment or property when operating this equipment use good judgment and follow safe practices as outlined below DANGER NEVER enter an enclosed fan cabinet or reach in...

Page 2: ...ant system open to air any longer than the actual time required to service the equipment Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cann...

Page 3: ...39 4441 28N 28N Coil Model Number Coil Type A Chilled Water Coil Orientation S Slant V Vertical F Full A S 4 Rows 4 6 8 12 12 16 20 22 26 32 Tubes in Face 24 30 36 38 Q Circuiting Q Quarter H Half D D...

Page 4: ...N Coil Model Number Coil Type E Direct Expansion Coil Orientation V Vertical B Face Split Half Circuit E V 4 Rows 4 6 16 12 16 20 26 Tubes in Face 30 36 H Circuiting A Face Split Quarter Circuit Fin M...

Page 5: ...A 1250 Position 12 is 0 if rpm is 3 digits 1 Motor Horsepower Constant Speed K Forward Curve without VFD 2 Forward Curve with VFD 03 06 08 10 12 15 18 21 25 01 02 03 04 05 06 07 08 09 10 11 12 13 hp h...

Page 6: ...6 PRE HEAT WATER OR PRE HEAT STEAM PHW LEGEND Fig 8 Position 4 Unit Configuration Model Component Sequence Also Shown COMB Combination PH Preheat POS Position Factory installed option components...

Page 7: ...LY 6 A B C 39LH VERTICAL HEATING SMALL FACE AREA A B C 7 ACCESSORY SECTIONS MIXING BOX 8 10 FILTER MIXING BOX 9 FILTER MIXING BOX FLAT FILTER 11 ANGLE FILTER 12 PLENUM 13 HOT WATER OR STEAM PREHEAT CO...

Page 8: ...29 1 29 1 37 0 40 9 40 9 48 8 120 168 246 282 324 372 417 444 492 7 39LH 21 3 25 2 29 1 29 1 29 1 37 0 40 9 40 9 48 8 220 308 452 517 594 682 764 814 902 ACCESSORIES Unit Size 03 06 08 10 12 15 18 21...

Page 9: ...which fits inside the larger one This allows the channel to be adjusted to the required length for installation Channels are shipped on top of the unit The 2 sections of each channel are shipped one...

Page 10: ...16 3 1 2 119 16 0 77 8 1 33 4 2 39 16 18 5 51 16 5 55 16 3 415 16 3 33 8 0 77 8 1 33 4 2 117 16 21 6 51 4 6 51 8 3 415 16 3 33 8 0 77 8 1 33 4 2 117 16 25 6 51 4 6 51 8 4 015 16 2 39 16 0 77 8 1 33 4...

Page 11: ...10 1 11 7 14 2 16 3 Chilled Water 1 2 in OD Tube Small Face Area 4 Row 2 1 3 3 3 9 4 1 5 1 6 3 7 3 8 7 9 8 6 Row 2 4 3 7 5 1 5 9 6 6 8 3 9 5 11 8 13 5 8 Row 2 7 4 1 6 4 7 4 8 4 10 7 12 1 14 7 17 2 Hot...

Page 12: ...ENSION ROD FIELD SUPPLIED SUSPENSION CHANNEL FACTORY SUPPLIED OPTION MOUNT UNIT TO SUSPENSION CHANNELS THROUGH PROVIDED IN LIFTING BRACKET 7 16 IN DIAM HOLES FACTORY SUPPLIED BOLTS CONNECTING SUSPENSI...

Page 13: ...flanges top and sides around the coil fan section and the accessory section See Fig 15 NOTE If the section to section gasket installed at the factory is damaged while splitting the unit obtain the re...

Page 14: ...ust be connected to the 1 in hollow jackshaft that drives the interconnecting linkage bar Connection to any other shaft is not recommended DUCTWORK ATTACHMENT Ductwork should be flanged out and attach...

Page 15: ...7BJ033 24 4 0 375 0 625 150 N A N A 133 90 725 33AMACTGV 266 HF27BJ034 24 6 0 475 0 750 135 N A N A 266 90 450 DIMENSIONS ft in Fig 19 Mixing Box Duct Connections UNIT 39L A B C D E F G H J K L 03 2 3...

Page 16: ...ct Use a nonconductive nonhardening sealant Permagum manufactured by Schnee Morehead or sealing compound thumb grade manufactured by Calgon are acceptable materials POWER KNOCKOUTS Panels are not prov...

Page 17: ...ion on factory supplied drive 1 Always adjust the motor position so that V belts can be installed without stretching over grooves Forcing belts can result in uneven stretching and a mismatched set of...

Page 18: ...n accordance with Steps 1 6 Running the drive for a few revolutions or minutes will help seat the belt s in the groove s This relatively early re tensioning may reduce or minimize the amount of re ten...

Page 19: ...illustrates the normal piping components and the suggested locations for high medium or low pressure steam coils The low pressure application zero to 15 psig can dispense with the in petcock for conti...

Page 20: ...g the following precautions Install a drip line and trap on the pressure side of the inlet control valve Connect the drip line to the return line downstream of the return line trap To prevent scale or...

Page 21: ...1 2 D 48 21 2 57 21 2 57 21 2 66 21 2 D Double Circuit F Full Circuit H Half Circuit Q Quarter Circuit SMALL FACE AREA 39LB 39LC 39LF COIL TYPE CIRCUITING UNIT SIZE 03 06 08 10 12 Face Area sq ft 2 72...

Page 22: ...il Run full size to the trap reduce at the trap 2 Use float and thermostatic traps only for condensate re moval Trap size selection should be based on the differ ence in pressure between the steam sup...

Page 23: ...peration is necessary 2 Bypass to be the same size as trap orifice but never less than 1 2 inch Fig 27 Dripping Steam Supply to Condensate Return NOTES 1 Flange or union is located to facilitate coil...

Page 24: ...coil bank Fig 29 Multiple Coil Low Pressure Piping Gravity Return NOTES 1 Flange or union is located to facilitate coil removal 2 To prevent water hammer drain coil before admitting steam 3 Do not ex...

Page 25: ...prevent excessive heat from reaching diaphragm and internal parts Do not allow water to enter system Disassemble expansion valve before soldering if accessible for easy reassembly Use 95 5 tin antimo...

Page 26: ...w Split 13 15 16 18 18 18 18 18 18 Distributor Nozzle Size 2 2 3 4 4 5 5 6 6 6 ROW COIL Circuit Equivalent Length ft 39 20 47 24 51 26 59 30 67 34 Distributor Tube Length in Face Split 11 11 11 13 13...

Page 27: ...lit 111 2 111 2 111 2 111 2 111 2 13 111 2 13 111 2 13 Row Split 111 2 13 15 16 16 181 2 16 181 2 16 181 2 Distributor Nozzle Size 11 2 11 2 21 2 3 4 4 5 5 5 5 8 ROW COIL Circuit Equivalent Length ft...

Page 28: ...7 Fig 35 Expansion Valve Piping Fig 36 Distributor and Hot Gas Bypass Auxiliary Side Connector SPORLAN TYPE CARRIER PART NO CONNECTION SIZES in USED WITH DISTRIBUTOR TYPE NOZZLE SIZE Inlet ODM Solder...

Page 29: ...COIL Manifolding for 2 Face Splits Refer to Fig 38 and exter nally manifold as follows 1 Connect the 4 expansion valves to the 4 distributors on each coil and connect the 4 suction lines to the 15 dia...

Page 30: ...30 TXV Thermostatic Expansion Valve Fig 38 Face Split Coil Manifolding Typical TXV Thermostatic Expansion Valve Fig 39 Row Split Coil Manifolding Typical...

Page 31: ...ct switch or main circuit breaker in accor dance with NEC and other applicable codes Locate so that it is easily accessible and within sight of heater control box per NEC Article 424 19 and 424 65 Wea...

Page 32: ...32 NOTE All wiring must be copper and must conform to the NEC National Electrical Code Fig 41 Typical Electric Heater Wiring Schematic...

Page 33: ...175 114 142 3 150 57 71 2 80 72 90 2 90 51 8 500 53 144 180 3 200 125 156 3 175 62 78 2 80 79 98 2 100 59 8 500 62 72 90 2 100 91 114 2 125 12 7 3 6 19 9 500 17 55 69 2 70 48 60 1 60 24 30 1 30 30 38...

Page 34: ...port must be removed To change from upblast to horizontal discharge or from horizontal to upblast discharge the bearings must be relocated to keep the wheel centered in the housing To change from upbl...

Page 35: ...r freedom of movement 2 Check tightness of bearing setscrews or locking collars Fig 44 Also check tightness of setscrews on fan wheels and sheaves 3 Check tightness of fan shaft bearing mounting 4 Rec...

Page 36: ...ff motor power 2 Disconnect and tag power wires at motor terminals 3 Loosen motor brace to mounting rail attaching bolts Loosen belt tensioning bolts to adjust the motor position so V belts can be rem...

Page 37: ...are shipped see Fig 46 bottom coil baffle side hairpin baffle side header baffle top coil baffle These parts should be field installed onto the coil before placing the coil into the unit Once the baf...

Page 38: ...g 46 Field Installed Coils 39LA and LD only LEGEND Fig 47 Horizontal Unit Slant Coil Removal 39LA Units Sizes 03 21 1 Accessory Side Panel 8 Condensate Baffle 2 Left Side Panel 9 Holddown Screws 3 Top...

Page 39: ...er 6 Remove screws from inside baffle item 14 Leave baffle attached to left side panel Item 16 7 Remove left side panel Item 16 NOTE Support of fan section may be required after re moval of side panel...

Page 40: ...baffle to coil 4 Remove side panel s Item 6 NOTE Vertical units may require support of fan section after removal of side panels 5 If accessory is present remove accessory side panel Item 1 on left sid...

Page 41: ...om end of unit New holes must be cut in coil cover panel Original holes must be plugged and insulated New side panels may be necessary when changing coil hand NU FIN COILS The NuFin coil is airflow di...

Page 42: ...ill fail closed 7 Check operation of vacuum breakers 8 Check operation of the thermal protection devices used for freeze up protection 9 Steam or condensate should not be allowed to remain in the coil...

Page 43: ...tighten holddown bolts and then tighten bearing locking collar and setscrews 12 Make certain fan wheel does not rub sides of fan housing after installing new bearings 13 Recoat fan shaft with a rust i...

Page 44: ...44 16 20 25 16 20 25 25 25 16 20 20 SIZE 21 SIZE 25 Fig 52 Filter Arrangement 2 in and 4 in Flat...

Page 45: ...eel is recommended Lubrication MOTORS Lubricate in accordance with nameplate at tached to motor or with manufacturer s recommendations included with motor BEARINGS Fan Bearings Lubricate fan bearings...

Page 46: ...fan discharge panel Fig 56 2 Remove all of the panels from the fan section Fig 57 3 Remove the fan by removing the 4 screws on the corner of the fan sled On larger units the fan sled may be ex tremely...

Page 47: ...47 METRIC CONVERSION CHART...

Page 48: ...ght to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53390016 01 Printed in U S A Form 39L 7SI Pg 48 816 3 14 Replaces 39L...

Reviews: