background image

To prevent personal injury wear safety glasses, protective
clothing, and gloves when handling refrigerant and observe
the following:
• Back seating service valves are not equipped with Schrader
valves. Fully back seat (counter clockwise) valve stem before
removing gage port cap.
• Front seating service valves are equipped with Schrader
valves.

Do not vent refrigerant to atmosphere. Recover during system
repair or final unit disposal.

Follow these steps to properly pump down a system and avoid
negative suction.

1. Fully back seat (open) liquid and vapor tube service valves.

2. Unit is shipped with valve stem(s) front seated (closed) and

caps installed. Replace stem caps after system is opened to
refrigerant flow. Replace caps finger-tight and tighten with
wrench and additional 1/12 turn.

3. Close electrical disconnects to energize system.

4. Set room thermostat at desired temperature. Be sure set point

is below indoor ambient temperature.

5. Set room thermostat at COOL and fan control at ON or AUTO

mode, as desired. Operate unit for 15 minutes. Check system
refrigerant charge.

• 3-phase scroll compressors are rotation sensitive.
• A flashing LED on phase monitor indicates reverse rotation.
(See Fig. 6 and Table 3.)
• This will not allow contactor to be energized.
• Disconnect power to unit and interchange 2 field wiring
leads on unit contactor.

SEQUENCE OF OPERATION

Turn on power to indoor and outdoor units. Transformer is
energized.

On a call for cooling, thermostat makes circuits R-Y and R-G. On
three phase models with scroll compressors, the units are equipped
with a phase monitor to detect in the incoming power is correctly
phased for compressor operation. If the phasing is correct, circuit
R-Y energizes contactor, starting outdoor fan motor and compres-
sor circuit. R-G energizes indoor unit blower relay, starting indoor
blower motor on high speed.

NOTE:

If the phasing is incorrect, the contactor will not be

energized. To correct the phasing, interchange any two of the three
power connections on the field side.

When thermostat is satisfied, its contacts open, de-energizing
contactor and blower relay. Compressor and motors stop.

If indoor unit is equipped with a time-delay relay circuit, the
indoor blower runs an additional 90 sec to increase system
efficiency.

Step 11—Check Charge

UNIT CHARGE

Factory charge is shown on unit rating plate. Adjust charge by
following procedure shown on charging tables located on unit.

NOTE:

If superheat or subcooling charging conditions are not

favorable, charge must be weighed in accordance with unit rating

plate ± 0.6 oz/ft (56 g/m) of 3/8 in. (9.53mm) liquid line above or
below 15 ft (4.57m) respectively.

EXAMPLE:

25 ft - 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge

(7.62m - 4.57m = 3.05m X 56g/m = 171 g of additional charge)

COOLING ONLY PROCEDURE

The following procedure is valid when indoor airflow is within ±
21 percent of its rated CFM.

1. Operate unit a minimum of 10 minutes before checking

charge.

2. Measure suction pressure by attaching an accurate gage to

suction valve service port.

3. Measure suction temperature by attaching an accurate ther-

mistor type or electronic thermometer to suction line at service
valve.

4. Measure outdoor air dry-bulb temperature with thermometer.

5. Measure indoor air (entering indoor coil) wet-bulb tempera-

ture with a sling psychrometer.

6. Refer to Table 4 or 6. Find outdoor temperature and evapo-

rator entering air wet-bulb temperature. At this intersection,
note superheat.

7. Refer to Table 5 or 7. Find superheat temperature located in

item 6 and suction pressure. At this intersection, note suction
line temperature.

8. If unit has a lower suction line temperature than charted

temperature, add refrigerant until charted temperature is
reached.

9. If unit has a higher suction line temperature than cheated

temperature, reclaim refrigerant until cheated temperature is
reached.

10. If outdoor air temperature or pressure at suction valve

changes, charge to new suction line temperature indicated on
chart.

Fig. 6—Phase Monitor Control

A00010

Table 3—PHASE MONITOR LED INDICATORS

LED

STATUS

OFF

No call for compressor operation

FLASHING

Reversed phase

ON

Normal

7

Summary of Contents for 38TUA

Page 1: ...TALLATION RECOMMENDATIONS 1 Locate unit away from windows patios decks and so forth where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to cap...

Page 2: ...does not match replace indoor coil piston with piston shipped with this unit The piston shipped with outdoor unit is correct for any approved indoor coil combination Remove indoor coil piston if unit...

Page 3: ...braze sweat connec tions using industry accepted methods and materials Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all f...

Page 4: ...ep 8 Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hrs before starting unit To furnish power to heater only set thermostat to OFF position a...

Page 5: ...CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 Fig 5 24 v Control Circuit Connections 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C CARRIER NON PROGRAMMABLE THERMOSTAT MODEL A...

Page 6: ...OUTDOOR SENSOR CONNECTION C Y1 O C SEE NOTE 2 J2 JUMPER J1 JUMPER A97597 Fig 5 Typical 24 v Circuit Connections Continued A97368 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION C...

Page 7: ...he three power connections on the field side When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop If indoor unit is equipped with a time d...

Page 8: ...em operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE For continuing high performance and minim...

Page 9: ...be weighed in NOTE Superheat F is at low side service port Table 5 Required Suction Line Temperature English SUPERHEAT TEMP F SUCTION PRESSURE AT SERVICE PORT PSIG 61 5 64 2 67 1 70 0 73 0 76 0 79 2 8...

Page 10: ...ed Suction Line Temperature Metric C SUPERHEAT TEMP C SUCTION PRESSURE AT SERVICE PORT KPA 424 443 463 483 503 524 546 568 591 0 1 7 2 8 3 9 5 0 6 1 7 2 8 3 9 4 10 6 1 2 8 3 9 5 0 6 1 7 2 8 3 9 4 10 6...

Page 11: ...11...

Page 12: ...38tuac4si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 101 Catalog No 003 8001...

Reviews: