background image

If ANY refrigerant tubing is buried, provide a 6 in. (152 mm)
vertical rise at service valve. Refrigerant tubing lengths up to
36 in. (914mm) may be buried without further special
consideration. For lengths above 36 in. (914mm), consult
your local distributor. Failure to follow this caution could
result in unit damage.

To prevent damage to unit or service valves, observe the
following:
• Use a brazing shield.
• Wrap service valves with wet cloth or use a heat sink

material.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant tubing of correct size
and condition. For tubing requirements beyond 50 ft (15.24m),
substantial capacity and performance losses can occur. Following
the recommendations in the Residential Split System Long-Line
Application Guideline will reduce these losses. Refer to Table 1
for field tubing equivalent line length. Refer to Table 2 for
accessory requirements.

For buried-line applications greater than 36 in. (914mm), consult
your local distributor.

If refrigerant tubes of indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED
INDOOR UNIT

Outdoor unit contains correct system refrigerant charge for opera-
tion with indoor unit of same size when connected by 15 ft (4.57m)
of field-supplied or factory-accessory tubing. Check refrigerant
charge for maximum efficiency.

REFRIGERANT TUBING

Connect tubing to fittings on outdoor unit vapor and liquid service
valves. (See Table 1.) Use refrigerant grade tubing.

SWEAT CONNECTION

Service valves are closed from factory and ready for brazing. After
wrapping the service valve with a wet cloth, braze sweat connec-
tions using industry accepted methods and materials. Consult local
code requirements. Refrigerant tubing and indoor coil are now
ready for leak testing. This check should include all field and
factory joints.

To avoid valve damage while brazing, service valves must be
wrapped in a heat-sinking material such as a wet cloth.

Step 7—Make Electrical Connections

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.

NOTE:

Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage or phase imbalance may
fluctuate above or below permissible limits.

NOTE:

Use copper wire only between disconnect switch and

unit.

Table 1—Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters

UNIT SIZE

LIQUID

VAPOR

VAPOR (LONG LINE)

Connection Diameter

Tube Diameter

Connection Diameter

Tube Diameter

Connection Diameter

Tube Diameter

In.

mm

In.

mm

In.

mm

In.

mm

In.

mm

In.

mm

024

3/8

9.53

3/8

9.53

5/8

16.00

5/8

16.00

5/8

16.00

3/4

19.05

036

3/8

9.53

3/8

9.53

3/4

19.05

3/4

19.05

3/4

19.05

7/8

22.35

048

3/8

9.53

3/8

9.53

7/8

22.35

7/8

22.35

7/8

22.35

1-1/8

28.70

060

3/8

9.53

3/8

9.53

7/8

22.35

1-1/8

28.70

7/8

22.35

1-1/8

28.70

Notes: 1. Tube diameters are for lengths up to 50 ft (15.24m). For tube sets over 50 ft (15.24m), consult Long-Line Application Guideline.

2. Do not apply capillary tube indoor coils to these units.

Fig. 3—Piping Installation

A94028

INSULATION

VAPOR TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

VAPOR TUBE

INSULATION

CAULK

Avoid contact between tubing and structure

NOTE:

THROUGH THE WALL

HANGER STRAP

(AROUND VAPOR

TUBE ONLY)

JOIST

1

 MIN.

SUSPENSION

3

Summary of Contents for 38TUA

Page 1: ...TALLATION RECOMMENDATIONS 1 Locate unit away from windows patios decks and so forth where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to cap...

Page 2: ...does not match replace indoor coil piston with piston shipped with this unit The piston shipped with outdoor unit is correct for any approved indoor coil combination Remove indoor coil piston if unit...

Page 3: ...braze sweat connec tions using industry accepted methods and materials Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all f...

Page 4: ...ep 8 Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hrs before starting unit To furnish power to heater only set thermostat to OFF position a...

Page 5: ...CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 Fig 5 24 v Control Circuit Connections 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C CARRIER NON PROGRAMMABLE THERMOSTAT MODEL A...

Page 6: ...OUTDOOR SENSOR CONNECTION C Y1 O C SEE NOTE 2 J2 JUMPER J1 JUMPER A97597 Fig 5 Typical 24 v Circuit Connections Continued A97368 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION C...

Page 7: ...he three power connections on the field side When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop If indoor unit is equipped with a time d...

Page 8: ...em operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE For continuing high performance and minim...

Page 9: ...be weighed in NOTE Superheat F is at low side service port Table 5 Required Suction Line Temperature English SUPERHEAT TEMP F SUCTION PRESSURE AT SERVICE PORT PSIG 61 5 64 2 67 1 70 0 73 0 76 0 79 2 8...

Page 10: ...ed Suction Line Temperature Metric C SUPERHEAT TEMP C SUCTION PRESSURE AT SERVICE PORT KPA 424 443 463 483 503 524 546 568 591 0 1 7 2 8 3 9 5 0 6 1 7 2 8 3 9 4 10 6 1 2 8 3 9 5 0 6 1 7 2 8 3 9 4 10 6...

Page 11: ...11...

Page 12: ...38tuac4si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 101 Catalog No 003 8001...

Reviews: