background image

To avoid personal injury or death, do not supply power to unit
with compressor terminal box cover removed.

NOTE:

Install branch circuit of adequate size per NEC to handle

unit starting current. Locate disconnect within sight from and
readily accessible from unit per Section 440-14 of NEC.

The unit cabinet must have an uninterrupted or unbroken
ground to minimize personal injury if an electrical fault
should occur. The ground may consist of electrical wire or
metal conduit when installed in accordance with existing
electrical codes. Failure to follow this warning can result in an
electrical shock, fire, or death.

ROUTE GROUND AND POWER WIRES

Remove access panel and control box cover to gain access to unit
wiring. Extend wires from disconnect through power wiring hole
provided and into unit control box.

CONNECT GROUND AND POWER WIRES

Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 4.

CONNECT CONTROL WIRING

Route 24-v control wires through control wiring grommet and
connect leads to control wiring. (See Fig. 5.)

Use No. 18 AWG color-coded, insulated (35° C minimum) wire.
If thermostat is located more than 100 ft (30.48m) from unit as
measured along the control voltage wires, use No. 16 AWG
color-coded wires to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from
incoming power leads.

Use furnace transformer, fan-coil transformer, or accessory trans-
former for control power, 24-v/40va minimum.

NOTE:

Use of available 24-v accessories may exceed the mini-

mum 40-va power requirement. Determine total transformer lead-
ing and increase the transformer capacity or split the load with an
accessory transformer as required.

Step 8—Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hrs before starting unit. To furnish power to heater
only, set thermostat to OFF position and close electrical disconnect
to outdoor unit.

A crankcase heater is required if the refrigerant tubing is longer
than 50 ft (15.24m). Refer to Residential Split System Long-Line
Application Guideline.

Step 9—Install Electrical Accessories, If Any

Refer to the individual instruction packaged with the kit or
accessory when installing.

Step 10—Start-Up and Check Charge

To prevent compressor damage or personal injury, observe
the following:
• Do not overcharge system with refrigerant.
• Do not operate unit in a vacuum or at negative pressure.
• Do not disable low-pressure switch
In scroll compressor applications:
• Dome temperatures may be hot.

Table 2—Accessory Usage

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(BELOW 55°F/12.8°C)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(OVER 50 FT/15.24M)

REQUIRED FOR

SEA COAST

APPLICATIONS

(WITHIN 2 MILES/3.22KM)

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

No

MotorMaster® Control

or

Low-Ambient Pressure Switch

Yes

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feed

Recommended

No

Recommended

Liquid-Line Solenoid Valve

or

Hard-Shutoff TXV

No

See Long-Line

Application

Guideline

Yes

Ball-Bearing Fan Motor

Yes‡

No

No

* For tubing-line sets between 50 (15.24m) and 175 ft (53.34m), refer to Residential Split-System Long-Line Application Guideline.
† Only when low-pressure switch is used.
‡ Required for low-ambient controller (full-modulation feature) and MotorMaster® Control only.

Fig. 4—Line Power Connections

A94025

DISCONNECT
PER N.E.C. AND/OR
LOCAL CODES

CONTACTOR

GROUND
LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

BLUE

3 PHASE ONLY

4

Summary of Contents for 38TUA

Page 1: ...TALLATION RECOMMENDATIONS 1 Locate unit away from windows patios decks and so forth where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to cap...

Page 2: ...does not match replace indoor coil piston with piston shipped with this unit The piston shipped with outdoor unit is correct for any approved indoor coil combination Remove indoor coil piston if unit...

Page 3: ...braze sweat connec tions using industry accepted methods and materials Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all f...

Page 4: ...ep 8 Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hrs before starting unit To furnish power to heater only set thermostat to OFF position a...

Page 5: ...CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 Fig 5 24 v Control Circuit Connections 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C CARRIER NON PROGRAMMABLE THERMOSTAT MODEL A...

Page 6: ...OUTDOOR SENSOR CONNECTION C Y1 O C SEE NOTE 2 J2 JUMPER J1 JUMPER A97597 Fig 5 Typical 24 v Circuit Connections Continued A97368 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION C...

Page 7: ...he three power connections on the field side When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop If indoor unit is equipped with a time d...

Page 8: ...em operation and periodic maintenance requirements outlined in manual 4 Fill out Dealer Installation Checklist and place in customer file CARE AND MAINTENANCE For continuing high performance and minim...

Page 9: ...be weighed in NOTE Superheat F is at low side service port Table 5 Required Suction Line Temperature English SUPERHEAT TEMP F SUCTION PRESSURE AT SERVICE PORT PSIG 61 5 64 2 67 1 70 0 73 0 76 0 79 2 8...

Page 10: ...ed Suction Line Temperature Metric C SUPERHEAT TEMP C SUCTION PRESSURE AT SERVICE PORT KPA 424 443 463 483 503 524 546 568 591 0 1 7 2 8 3 9 5 0 6 1 7 2 8 3 9 4 10 6 1 2 8 3 9 5 0 6 1 7 2 8 3 9 4 10 6...

Page 11: ...11...

Page 12: ...38tuac4si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 101 Catalog No 003 8001...

Reviews: