38MGQ 
Multi-Zone Ductless System
Sizes 18, 27, 36 and 48

Installation Instructions

NOTE

:  Read the entire instruction manual before starting the installation.

NOTE

:  Image for illustration purposes only. Actual model may be

slightly different.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

2

. . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PARTS LIST

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SYSTEM REQUIREMENTS

4

. . . . . . . . . . . . . . . . . . . . . . . . . . .

PIPING REQUIREMENTS

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

DIMENSIONS

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CLEARANCES

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION GUIDE

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION TIPS

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

OUTDOOR UNIT INSTALLATION

11

. . . . . . . . . . . . . . . . . . . .

ELECTRICAL DATA

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CONNECTION DIAGRAMS

13

. . . . . . . . . . . . . . . . . . . . . . . . .

START

UP

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

OUTDOOR UNIT DIAGNOSTIC GUIDES

17

. . . . . . . . . . . . . .

Summary of Contents for 38MGQ Series

Page 1: ...illustration purposes only Actual model may be slightly different TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 GENERAL 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 PIPING REQUIREMENTS 4 DIMENSIONS 6 CLEARA...

Page 2: ...ese words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal...

Page 3: ...unit helps with vibration prevention during operation 4 Drain Hose and Drain Joint 1 Fig 1 Parts List The following units are covered in these installation instructions Table 1 Unit Sizes SYSTEM TONS...

Page 4: ...Maximum Piping Length per system Ft m 98 30 147 45 196 60 245 75 Additional refrigerant charge between Standard Max piping length Oz ft g m 0 16 15 0 16 15 0 16 15 0 16 15 Gas Pipe Size in mm 3 8 2 9...

Page 5: ...door unit The field supplied 14 3 power communication wiring from the outdoor unit to the indoor unit consists of four 4 wires and provides the power for the indoor unit Two wires are high voltage AC...

Page 6: ...6 700 31 89 810 31 89 810 36 93 1369 Width in mm 33 27 845 37 20 945 37 20 945 53 9 938 Depth in mm 12 60 320 15 55 395 15 55 395 15 43 392 Weight Net lbs kg 114 63 52 154 76 70 2 169 75 77 255 50 115...

Page 7: ...7 DIMENSIONS OUTDOOR CONTINUED Suction Fig 3 Outdoor Dimensions Size 27...

Page 8: ...8 DIMENSIONS OUTDOOR CONTINUED Suction Fig 4 Outdoor Dimensions Size 36...

Page 9: ...9 DIMENSIONS OUTDOOR CONTINUED Suction Fig 5 Outdoor Dimensions Size 48...

Page 10: ...10 CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 6 Clearances Outdoor Table 10 Clearances Outdoor Values UNIT MINIMUM VALUE in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101...

Page 11: ...ng tools to avoid kinks and flat spots S Keep the tubing free of dirt sand moisture and other contaminants to avoid damaging the refrigerant system S Avoid sags in the suction line to prevent the form...

Page 12: ...firmly Loose wiring may cause terminal to overheat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected S No wire should be allowed to touch ref...

Page 13: ...13 CONNECTION DIAGRAMS Fig 12 Connection Diagram Size 18 Fig 13 Connection Diagram Size 27...

Page 14: ...Fig 15 Connection Diagram Size 48 Notes 1 Do not use thermostat wire for any connection between indoor and outdoor units 2 All connections between indoor and outdoor units must be as shown The connect...

Page 15: ...d Line Service Valve excluding the 18 000 BTU unit 1 Completely tighten the flare nuts A B C D E Fully open all circuits service valves connect the manifold gage charge hose to the charge port of the...

Page 16: ...nue operating for an additional 15 minutes 2 Close service valves and shut off vacuum pump 3 Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig 4 Close servic...

Page 17: ...LED STATUS IDU Error IDU Error E0 Outdoor EEPROM malfunction F4 E6 E2 Communication malfunction between indoor and outdoor units E1 E2 E3 Communication malfunction between IPM board and outdoor main b...

Page 18: ...ration S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 38MGQ 03SI Replaces...