background image

11

INSTALLATION GUIDE

Up to five fan coil units can be connected to one outdoor unit.

Refer to the Product Data for approved combinations.

INSTALLATION TIPS

Ideal installation locations include:
Outdoor Unit

S

  A location which is convenient to installation and not exposed to

strong wind.

S

  A location which can bear the weight of the outdoor unit and

where  the outdoor unit can be mounted in a level position.

S

  A location with appropriate clearances as outlined in Fig. 6.

S

  Do not install the indoor or outdoor units in a location with

special environmental conditions. For those applications, contact

your Ductless representative.

OUTDOOR UNIT INSTALLATION

1. Use a rigid base to support unit in a level position.
2. Locate outdoor unit and connect piping and wiring.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Excessive torque can break flare nut depending on

installation conditions.

NOTE

:  Install the outdoor unit on a rigid base to reduce noise levels

and vibration. Determine the optimal air outlet direction to prevent
discharged air from being blocked. If the installation site is exposed to
strong winds such as a coastal areas, ensure the fan’s proper operation
by installing the unit lengthwise along the wall or use dust or shield
plates. If the unit needs to be suspended, the installation bracket should
comply with the suspension requirements in the installation bracket
diagram. The installation wall should be solid brick, concrete or the
same intensity construction, or take steps to reinforce and dampen the
support. The connection between the bracket and the wall as well as
the bracket and the air conditioner should be firm, stable and reliable.
Ensure there is no obstacle which may block the radiating air.

Strong

wind

A07350

Fig. 7

 - 

High Wind Installation

MAKE REFRIGERANT PIPING CONNECTIONS
(OUTDOOR UNIT)
IMPORTANT

: Use refrigeration grade tubing ONLY. No other

type of tubing may be used. Use of other types of tubing 

will

 

void

the manufacturer’s warranty.

Piping Guide:

S

  Do not open service valves or remove protective caps from

tubing ends until all the connections are made.

S

  Bend tubing with bending tools to avoid kinks and flat spots.

S

  Keep the tubing free of dirt, sand, moisture, and other

contaminants

 

to avoid damaging the refrigerant system.

S

  Avoid sags in the suction line to prevent the formation of oil

 

traps.

Insulate each tube with minimum 3/8

in. (10 mm) wall thermal

pipe insulation.

 

Inserting the tubing into the insulation before

making

 

the connections saves time and improves installation quality.

1. The unit is equipped with multiple pairs of service valves.

Each pair is clearly marked (color and letter) to identify the

indoor unit circuits. In the outdoor unit wiring area, each

indoor unit interconnecting terminal block is marked (letter)

the same as the corresponding pair of service valves. The

indoor units must be piped and wired in matched sets (A to A;

B to B, etc.).

2. It is not required to use all of the available fan coil

connections if the application does not require them at the

current time. The system can be expanded at any time.

3. Conversion joints are supplied with the outdoor unit. They

are required for certain fan coil combinations. These joints

are to be connected to the outdoor unit as needed to match

the line set size.

4. Remove the service connection, if provided with the unit.

Oblique

DŽ

90

Roughness

Burr

A150767

Fig. 8

 - 

Cut the Pipe

5. Remove all the burrs from the cut cross section of the pipe

avoiding any burrs inside the tubes.

6. Remove the flare nuts attached to the indoor and outdoor

units.

7. Install the correct size flare nut onto the tubing and make a

flare connection. Refer to Table 11 for the flare nut spaces.

Table 11—Flare Nut Spacing

OUTER DIAM. (mm)

A (mm)

Max.

Min.

Ø1/4”(6.35)

0.05 

(1

.3

)

0.03

(

0.7

)

Ø3/8”(9.52)

0.06 

(1

.6

)

0.0

4(1

.0

)

Ø1/2”(12.7)

0.07 

(1

.8

)

0.0

4(1

.0

)

Ø5/8”(15.88)

0.09 

(

2.2

)

0.08

(

2.0

)

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"A"

A150768

Fig. 9

 - 

Flare Nut Spacing

8. Apply a small amount of refrigerant oil to the flare

connection on the tubing.

9. Align center of the pipes and/or service valve.

Indoor unit tubing

Flare nut

Piping

A150769

Fig. 10

 - 

Align Pipe Center

10. Connect both the liquid and gas piping to the indoor unit
11. Tighten the flare nut using a torque wrench as specified in

the Table 12.

12. Complete the installation.

Table 12—Tightening Torque

PIPE DIAMETER

INCH (mm)

TIGHTENING TORQUE

Ft-lb

N-m

Ø1/4” (6.35)

1

to

 

1

3

1

3.6 

to

 

1

7.6

Ø3/8” (9.52)

2

4

 

to

 3

1

32.5 

to

 

4

2.0

Ø1/2” (12.7)

37 

to

 

4

6

50.

1

 

to

 62.3

Ø5/8” (15.88)

50 

to

 60

67.7 

to

 8

1

.3

Summary of Contents for 38MGQ Series

Page 1: ...illustration purposes only Actual model may be slightly different TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 GENERAL 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 PIPING REQUIREMENTS 4 DIMENSIONS 6 CLEARA...

Page 2: ...ese words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal...

Page 3: ...unit helps with vibration prevention during operation 4 Drain Hose and Drain Joint 1 Fig 1 Parts List The following units are covered in these installation instructions Table 1 Unit Sizes SYSTEM TONS...

Page 4: ...Maximum Piping Length per system Ft m 98 30 147 45 196 60 245 75 Additional refrigerant charge between Standard Max piping length Oz ft g m 0 16 15 0 16 15 0 16 15 0 16 15 Gas Pipe Size in mm 3 8 2 9...

Page 5: ...door unit The field supplied 14 3 power communication wiring from the outdoor unit to the indoor unit consists of four 4 wires and provides the power for the indoor unit Two wires are high voltage AC...

Page 6: ...6 700 31 89 810 31 89 810 36 93 1369 Width in mm 33 27 845 37 20 945 37 20 945 53 9 938 Depth in mm 12 60 320 15 55 395 15 55 395 15 43 392 Weight Net lbs kg 114 63 52 154 76 70 2 169 75 77 255 50 115...

Page 7: ...7 DIMENSIONS OUTDOOR CONTINUED Suction Fig 3 Outdoor Dimensions Size 27...

Page 8: ...8 DIMENSIONS OUTDOOR CONTINUED Suction Fig 4 Outdoor Dimensions Size 36...

Page 9: ...9 DIMENSIONS OUTDOOR CONTINUED Suction Fig 5 Outdoor Dimensions Size 48...

Page 10: ...10 CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 6 Clearances Outdoor Table 10 Clearances Outdoor Values UNIT MINIMUM VALUE in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101...

Page 11: ...ng tools to avoid kinks and flat spots S Keep the tubing free of dirt sand moisture and other contaminants to avoid damaging the refrigerant system S Avoid sags in the suction line to prevent the form...

Page 12: ...firmly Loose wiring may cause terminal to overheat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected S No wire should be allowed to touch ref...

Page 13: ...13 CONNECTION DIAGRAMS Fig 12 Connection Diagram Size 18 Fig 13 Connection Diagram Size 27...

Page 14: ...Fig 15 Connection Diagram Size 48 Notes 1 Do not use thermostat wire for any connection between indoor and outdoor units 2 All connections between indoor and outdoor units must be as shown The connect...

Page 15: ...d Line Service Valve excluding the 18 000 BTU unit 1 Completely tighten the flare nuts A B C D E Fully open all circuits service valves connect the manifold gage charge hose to the charge port of the...

Page 16: ...nue operating for an additional 15 minutes 2 Close service valves and shut off vacuum pump 3 Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig 4 Close servic...

Page 17: ...LED STATUS IDU Error IDU Error E0 Outdoor EEPROM malfunction F4 E6 E2 Communication malfunction between indoor and outdoor units E1 E2 E3 Communication malfunction between IPM board and outdoor main b...

Page 18: ...ration S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 38MGQ 03SI Replaces...

Reviews: