background image

Refrigerant

Only quali

 ed personnel must perform a periodic tightness control, in 

accordance with the regulation (CE) 

Nº 517/2014.

-  The frequency of checks is no longer related to the load of refrigerant 

but to its global warming potential: 

Load kg x GWP =  t CO2e 

Carbon dioxide equivalency (t CO2e ) is a quantity that describes, for 

a given mixture and amount of greenhouse gas, the amount in tonnes 

of CO2 that would have the same global warming potential (GWP).

Please, consult data of carbon dioxide equivalency (t CO2e) provided 

in the technical characteristics tables of this manual.

-  Operators shall ensure that the unit is checked for leaks ad minima 

according to the following frequency:

•  t CO2e < 5  ............ not subjected

•  t CO2e 5 to 50  ...... every year

•  t CO2e 50 to 500 ... every 6 months

•  t CO2e > 500 ......... every 3 months

-  Where a leakage detection system has been installed the frequency 

of checks is halved.

Note: Never forget that the cooling systems contain liquids and vapours 

under pressure. The service pressure of R-410A is approximately 1.5 

higher than that of R-407C.

-  All necessary precautions must be taken during the partial opening 

of the cooling circuit. This opening entails the discharge of a certain 

amount of refrigerant to the atmosphere. It is essential to limit this 

quantity of lost refrigerant to a minimum by pumping and isolating 

the charge in some other part of the circuit.

- The refrigerant 

 uid at low temperature can cause in

 ammatory 

injuries similar to burns when contacting the skin or eyes. Always use 

safety goggles, gloves, etc. when opening ducts that may contain 

liquids. 

-  The refrigerant in excess must be stored in appropriate containers 

and the amount of refrigerant stored at the technical rooms must be 

limited. 

-  Refrigerant barrels and deposits must be handled with precaution 

and visible warning signs must be placed to attract attention over 

the risks of intoxication, 

 re and explosion linked to the refrigerant. 

-  At the end of its useful life, the refrigerant must be retrieved and 

recycled as per the current regulations.

Compressor

In the case of compressor replacement:

-  Disconnect the unit from power supply.

-  Completely empty the load of refrigerant using a speci

 c recovery 

unit for R-410A

-  Disconnect electrically the compresor.

-  Carefully unscrew the suction and discharge piping.

-  The compressor is 

 xed onto the platform with 4 screws Ø 8 mm. 

Unscrew the 

 xings.

-  Place the new compressor and check that it has a suf

 cient oil charge.

Warning: when tightening the compressor screws, please consult 

the maximum torque that can be applied.

If a torque wrench is not available, tighten them until noticing 

resistance, then tighten the screws by turning them 3/4 of a revolution.

-  Screw the suction and discharge piping.

-  Connect the compressor in accordance with the circuit diagram.

-  Make vacuum and next, reload the gas into the unit according to 

load data provided in the technical characteristics table and in the 

unit’s data plate.

Liquid sight glass

-  This sight glass, located on the liquid line, after the dehydrating 

 lter, enables controlling the refrigerant load and the presence of 

moisture in the circuit. The presence of bubbles in the indicator 

means that the refrigerant 

 uid load is insuf

 cient or that there are 

non-condensable products in the cooling circuit. The presence of 

moisture is characterised by the change in colour of the control paper 

located on the sight glass. 

-  In the 38HB/HF units the liquid sight glass is located on the support 

next to the electric panel.

Warning:

If the unit stops, certain indicators may appear in yellow; the change in 

colour is due to the sensitivity, which depends on the temperature of the 

 uid. These will change to green after a few hours of the unit operating.

If the indicators remain yellow, that will indicate the presence of 

excessive humidity in the circuit. This will require the presence of a 

specialist.

Compressor

Liquid sight glass

V-220005

Air coil

-  Check that the coil is free from dust and grease. 

-  Cleaning the accumulated dust on the coil can be performed with 

a vacuum cleaner perpendicular to the 

 ns or with a low-pressure 

water cleaner. Grease can be removed with water with degreaser. 

Do not put stress on the 

 ns as they could deform.

Use safety gloves for this task. Take care with the sharp 

parts of the coil. 

Split-system cooling units
and heat pumps

17

Summary of Contents for 38HB series

Page 1: ...LATION OPERATION AND MAINTENANCE INSTRUCTIONS 38HB HF Nominal cooling capacity 19 3 36 9 kW Nominal heating capacity 22 3 41 9 kW 50 Hz Split system units Translation of the original document 80127 07...

Page 2: ...re commissioning 8 Electrical connections 8 Condensate drain connection 9 Checks in the centrifugal fans 10 Air ducts connections 10 Cooling connections 11 9 Safety elements 12 10 Optional 12 Condensa...

Page 3: ...stallation 40HB HF series 40HB series Indoor unit cooling only with centrifugal fan and expansion valve horizontal construction designed for installation on premises connected to a network of ducts 40...

Page 4: ...15 9 15 3 20 1 25 1 Fan A 6 9 6 9 9 0 11 6 Control A 0 9 0 9 0 9 0 9 Total A 23 7 23 1 30 0 37 6 Dimensions Length mm 1 680 1 680 2 088 2 088 Width mm 915 915 1 198 1 198 Height mm 670 670 810 810 Wei...

Page 5: ...ncluded on the plates of characteristics or in the regulatory documentation provided with the product In case of a leak Toxicity According toASHRAE 34 R 410Abelongs to theA1 A1 group i e with high saf...

Page 6: ...oor or the structure supports the weight of the unit please consult the weight of the unit in the section Centre of gravity coordenates Both the outdoor unit 38HB HF and the indoor unit 40HB HF have...

Page 7: ...ned to an acoustic technician 38HB HF 80 90 120 160 dB A 79 1 81 5 79 2 83 9 38HB HF 80 90 120 160 dB A 65 0 68 4 68 5 69 7 40HB HF 80 90 120 160 dB A 65 9 64 6 65 2 64 2 C The sound pressure level of...

Page 8: ...Electrical connections Installation norms To perform the electric installation of the unit cable glands conductor section and their calculations protections etc refer to the information provided in t...

Page 9: ...0014 All the units both outdoor and indoor are equipped with a condensates drain pan with a bronze gas threaded M 3 4 drain junction Pan drain Outdoor unit 38HB HF Indoor unit 40HB HF If the unit is g...

Page 10: ...ct to a duct network In the event that the outlet fan of the indoor circuit is accessible from a particular point in the duct network the installer must install a protection mesh in the discharge as p...

Page 11: ...l avoid the dirt formation that may collapse some spots in the cooling circuit Apply isolator to the piping covering them and af x it with tape The material used must guarantee the air tightness at op...

Page 12: ...stat When connected to the compressor suction it will stop its operation when the pressure at that point goes down below the tare value caused by obstructions in the circuit excessive dirt in the lter...

Page 13: ...sh that the units include regularly with G4 rating mounted on the same frame The frame has access designed from the right side for maintenance To access the electrical heaters the screws that fasten t...

Page 14: ...for ducting In order to remove the electrical heaters the power supply cables must be disconnected from the terminal board and the hose taken out Hose Electrical heaters Safety thermistors Rail Then u...

Page 15: ...e support next to the electric panel Liquid sight glass Liquid line Gas line Main door switch Access to the electric panel Checks prior to commissioning It is advisable to make a complete sketch of th...

Page 16: ...these parameters whilst the unit is running allows controlling the installation performance and it is the best possible way to avoid breakdowns since the analysis of these data makes early detection o...

Page 17: ...mpressor replacement Disconnect the unit from power supply Completely empty the load of refrigerant using a speci c recovery unit for R 410A Disconnect electrically the compresor Carefully unscrew the...

Page 18: ...ust be discarded by using the appropriate procedure Jugs must be kept closed Avoid using oil from an already open jug kept in poor conditions Both the oil type as well as the volume needed for each mo...

Page 19: ...ow very high adjust ow f Repair Compressor does not start does not make noise humming a No power b The contacts of a control element are open c Timing of anti cycle short does not allow the starting...

Page 20: ...Order No 10127 07 2015 Supersedes order No New Manufactured for CARRIER in Spain The manufacturer reserves the right to change the speci cation without prior notice Printed in the European Union...

Reviews: