background image

9. S

AFETY

 

ELEMENTS

Clogged fi lter detector (optional)

Differential pressostat for indication, through an automatic reset alarm, 

of a level of dirtiness of the 

 lters greater than the established level. 

This pressostat is installed in the factory in the indoor unit. 

Control of air fl ow (optional)

A differential pressostat can be incorporated in order to measure the 

variation in air 

 ow. This pressostat allows the detection of fan belt 

breakages, since the fan relay only detects operating faults that have 

arisen in the motor. This safety device is included in units with electrical 

heaters. This pressostat is installed in the factory in the indoor unit. 

10. O

PTIONAL

Conde nsat ion pre ssure  c ont rol (38HB/HF)

This control is advisable for outdoor units 38HB/HF that work in cooling 

with an outdoor temperature below 15ºC. 

In units with centrifugal fan a check is performed per damper in the fan 

supply. A servomotor opens or closes the damper depending on the 

proportional signal 0-10V received from the electronic control system.

V-220004

Damper

Servomotor

The installation of some of these options brings in pressure 

drops at air level therefore this must be considered when 

selecting fans. 

The pressure drop graphs in the options, can be seen in the 

technical brochure.

High pressure pressostat

Connected to the compressor discharge, it will 

stop its operation when the pressure at that point 

reaches the setpoint. It disconnects at 42 bar and 

it is automatically reactivated.

Low pressure pressostat

When connected to the compressor suction, it 

will stop its operation when the pressure at that 

point goes down below the tare value (caused 

by obstructions in the circuit, excessive dirt in the 

 lters, fan stop or ice formation in the evaporator).

This pressostat disconnects at 2 bar and is automatically reactivated.

Safeties at the compressor

The scroll type compressor that these units as standard have the 

following safeties:

-  Non-return valve built into the compressor.

-  Temperature probe for the discharge from the compressor to protect 

the unit with discharge temperatures greater than 135ºC.

Defrost control

This safety device is intended to eliminate ice which could accumulate in 

the outdoor coil when the unit is working in the heating cycle. Defrosting 

is carried out by the control depending on the value measured by the 

sensor(s) on the outdoor coil(s) and the time set between defrosting 

operations.

Magnetothermals for line protection

They are located at the beginning of the power lines for the 

compressor(s) and motor fan(s) to protect them. 

Automatic switch in the control circuit

Magnetothermal switch that protects the operation circuit against 

continuous surges as well as against high currents of short duration 

(short circuits).

Main door switch

By using a mechanical device, it impedes access to the electric panel 

when the unit is with voltage.

Anti-fi re safety

With the optional return air probe, the electronic control can activate an 

anti-

 re safety device that detains the unit when the return air surpasses 

a temperature of 60°C (by default). It cannot return to operation until 

the temperature has dropped to below 40ºC.

Split-system cooling units
and heat pumps

12

Summary of Contents for 38HB series

Page 1: ...LATION OPERATION AND MAINTENANCE INSTRUCTIONS 38HB HF Nominal cooling capacity 19 3 36 9 kW Nominal heating capacity 22 3 41 9 kW 50 Hz Split system units Translation of the original document 80127 07...

Page 2: ...re commissioning 8 Electrical connections 8 Condensate drain connection 9 Checks in the centrifugal fans 10 Air ducts connections 10 Cooling connections 11 9 Safety elements 12 10 Optional 12 Condensa...

Page 3: ...stallation 40HB HF series 40HB series Indoor unit cooling only with centrifugal fan and expansion valve horizontal construction designed for installation on premises connected to a network of ducts 40...

Page 4: ...15 9 15 3 20 1 25 1 Fan A 6 9 6 9 9 0 11 6 Control A 0 9 0 9 0 9 0 9 Total A 23 7 23 1 30 0 37 6 Dimensions Length mm 1 680 1 680 2 088 2 088 Width mm 915 915 1 198 1 198 Height mm 670 670 810 810 Wei...

Page 5: ...ncluded on the plates of characteristics or in the regulatory documentation provided with the product In case of a leak Toxicity According toASHRAE 34 R 410Abelongs to theA1 A1 group i e with high saf...

Page 6: ...oor or the structure supports the weight of the unit please consult the weight of the unit in the section Centre of gravity coordenates Both the outdoor unit 38HB HF and the indoor unit 40HB HF have...

Page 7: ...ned to an acoustic technician 38HB HF 80 90 120 160 dB A 79 1 81 5 79 2 83 9 38HB HF 80 90 120 160 dB A 65 0 68 4 68 5 69 7 40HB HF 80 90 120 160 dB A 65 9 64 6 65 2 64 2 C The sound pressure level of...

Page 8: ...Electrical connections Installation norms To perform the electric installation of the unit cable glands conductor section and their calculations protections etc refer to the information provided in t...

Page 9: ...0014 All the units both outdoor and indoor are equipped with a condensates drain pan with a bronze gas threaded M 3 4 drain junction Pan drain Outdoor unit 38HB HF Indoor unit 40HB HF If the unit is g...

Page 10: ...ct to a duct network In the event that the outlet fan of the indoor circuit is accessible from a particular point in the duct network the installer must install a protection mesh in the discharge as p...

Page 11: ...l avoid the dirt formation that may collapse some spots in the cooling circuit Apply isolator to the piping covering them and af x it with tape The material used must guarantee the air tightness at op...

Page 12: ...stat When connected to the compressor suction it will stop its operation when the pressure at that point goes down below the tare value caused by obstructions in the circuit excessive dirt in the lter...

Page 13: ...sh that the units include regularly with G4 rating mounted on the same frame The frame has access designed from the right side for maintenance To access the electrical heaters the screws that fasten t...

Page 14: ...for ducting In order to remove the electrical heaters the power supply cables must be disconnected from the terminal board and the hose taken out Hose Electrical heaters Safety thermistors Rail Then u...

Page 15: ...e support next to the electric panel Liquid sight glass Liquid line Gas line Main door switch Access to the electric panel Checks prior to commissioning It is advisable to make a complete sketch of th...

Page 16: ...these parameters whilst the unit is running allows controlling the installation performance and it is the best possible way to avoid breakdowns since the analysis of these data makes early detection o...

Page 17: ...mpressor replacement Disconnect the unit from power supply Completely empty the load of refrigerant using a speci c recovery unit for R 410A Disconnect electrically the compresor Carefully unscrew the...

Page 18: ...ust be discarded by using the appropriate procedure Jugs must be kept closed Avoid using oil from an already open jug kept in poor conditions Both the oil type as well as the volume needed for each mo...

Page 19: ...ow very high adjust ow f Repair Compressor does not start does not make noise humming a No power b The contacts of a control element are open c Timing of anti cycle short does not allow the starting...

Page 20: ...Order No 10127 07 2015 Supersedes order No New Manufactured for CARRIER in Spain The manufacturer reserves the right to change the speci cation without prior notice Printed in the European Union...