39
6. Diagnosis for compressor synchronism (AP1 below is control board of the outdoor unit)
Main detection points:
S
Is the system pressure high?
S
Is the voltage too low?
Malfunction diagnosis process:
If the compressor wire COMP(UVW) is well
connected, the connection sequence
forwards to clockwise direction?
Check if the fan
terminal OFAN is
connected well
Replace
compressor
If the outdoor fan works
normally?
If the stop time of
compressor is more than
3min
Synchronism after
energize the unit
and start it
Connect
wire well
Synchronism
occurred during
operation
Replace
control board
AP1
If the radiating of unit is
well?
Remove
malfunction?
Improve the radiating
of unit (clean heat
exchanger and
increase ventilation)
Replace fan
capacitor C1
Replace
outdoor fan
Yes
No
No
No
Yes
Yes
No
Replace
control board
AP1
Remove
malfunction?
Replace
compressor
Yes
No
No
Yes
If the input voltage of unit
is normal?
Start to run until the
power resume normal
voltage
N
If the refrigerant is too
much?
Charge the
refrigerant with
service manual
Yes
Yes
No
Yes
End
End
No
Fig. 42 – Troubleshooting
Summary of Contents for 38GRQB09-3
Page 10: ...10 Outdoor unit Fig 11 Sizes 09 12...
Page 46: ...46 EXPLODED VIEW AND PARTS LIST Indoor Unit Fig 47 Indoor Unit...
Page 48: ...48 OUTDOOR UNIT Fig 48 Outdoor Unit...
Page 50: ...50 Fig 49...
Page 53: ...53 Shut off power hold both ends of horizontal...
Page 54: ...54...
Page 55: ...55...
Page 56: ...56 ziptie side cutters...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 73: ...73 6 7 8...
Page 74: ...74 9 Remove electric box 10 Remove evaporator...
Page 75: ...75...
Page 76: ...76 11 Remove swing blade...
Page 77: ...77 12 Remove cross flow blade and motor...
Page 78: ...78 13 Remove drive box...
Page 90: ...90 APPENDIX Appendix 1 Reference Sheet of Celsius and Fahrenheit...
Page 95: ...95 UNIT BREAKDOWNS a b c d e...
Page 96: ...96 f g h...
Page 97: ...97...
Page 98: ...98...
Page 99: ...99...