8. PFC (correction for power factor) malfunction (outdoor unit malfunction) (AP1 below is control board of the outdoor unit).
Main detection point:
S
Check if reactor (L) of outdoor unit and PFC capacity are damaged.
Malfunction diagnosis process:
Start
If the resistance
value is 0
Remove PFC capacity
and test resistance of
two terminals
Capacity is
short
circuit and
replace it
Y
Re-energize
the unit and
start it
Cut the terminal of reactor,
test the resistance
between two terminals of
reactor with ohmic meter
Replace the
reactor
Re-
energize
the unit and
start it
Check the
connection wire
of reactor (L) of
outdoor unit and
PFC capacity
Is there damage or a
short circuit?
Replace
connection
wire with circuit
diagram
Replace
control board
AP1
Yes
Yes
No
No
Y
No
N
N
No
No
No
If there is damaged
short circuit
Does the unit
normally?
Does the unit
operate?
Y
Y
Y
End
Yes
Yes
Yes
Yes
operate
normally?
Does the unit
operate?
normally?
Fig. 44 – Troubleshooting
Summary of Contents for 38GRQB09-3
Page 10: ...10 Outdoor unit Fig 11 Sizes 09 12...
Page 46: ...46 EXPLODED VIEW AND PARTS LIST Indoor Unit Fig 47 Indoor Unit...
Page 48: ...48 OUTDOOR UNIT Fig 48 Outdoor Unit...
Page 50: ...50 Fig 49...
Page 53: ...53 Shut off power hold both ends of horizontal...
Page 54: ...54...
Page 55: ...55...
Page 56: ...56 ziptie side cutters...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 73: ...73 6 7 8...
Page 74: ...74 9 Remove electric box 10 Remove evaporator...
Page 75: ...75...
Page 76: ...76 11 Remove swing blade...
Page 77: ...77 12 Remove cross flow blade and motor...
Page 78: ...78 13 Remove drive box...
Page 90: ...90 APPENDIX Appendix 1 Reference Sheet of Celsius and Fahrenheit...
Page 95: ...95 UNIT BREAKDOWNS a b c d e...
Page 96: ...96 f g h...
Page 97: ...97...
Page 98: ...98...
Page 99: ...99...