7

CAUTION

Indoor Unit Fixing

•  For detaching the indoor unit from the 

installation plate, pull the indoor unit 
toward you while pushing its bottom up at 
the speci

fi

 ed parts.

1

2

1

1.  Pass the pipe through the hole in the wall and hook the indoor unit on the 

installation plate at the upper hook.

2.  Swing the indoor unit to right and left to con

fi

 rm that it is 

fi

 rmly hooked up 

on the installation plate.

3.  While pressing the indoor unit onto the wall, hook it at the lower part on the 

installation plate. Pull the indoor unit toward you to con

fi

 rm that it is 

fi

 rmly 

hooked up on the installation plate.

Drainage

1.  Run the drain hose sloped downwards.

2.  Put water in the drain pan and make sure that the water is drained out of 

doors.

3.  When connecting extension drain hose, insulate the connecting part of 

extension drain hose with shield pipe.

 

NOTE

•  The hole should be made at a slight downward slant on the outdoor side.

Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.

This air conditioner has the structure designed 
to drain water collected from dew, which forms 
on the back of the indoor unit, to the drain pan. 
Therefore, do not store the power cord and other 
parts at a height above the drain guide.

CAUTION

OUTDOOR UNIT

OUTDOOR UNIT

Installation Place

•  A place which provides enough spaces around the outdoor unit as shown in 

the diagram

•  A place which can bear the weight of the outdoor unit and does not allow an 

increase in noise level and vibration

•  A place where the operation noise and discharged air do not disturb your 

neighbors

•  A place which is not exposed to a strong wind
•  A place free of a leakage of combustible gases
•  A place which does not block a passage
•  When the outdoor unit is to be installed in an elevated position, be sure to 

secure its feet.

•  An allowable length of the connecting pipe is up to 20 m.
•  There is no need to add refrigerant as long as the length of the connection 

piping is 15 m or less.

•  You will need to add 20g of refrigerant per meter of added connection piping 

for installations requiring connection piping to be between 16 m to 20 m.

•  An allowable height level is up to 10 m.
•  A place where the drain water does not cause any problems

CAUTION

1.  Install the outdoor unit in a location where there are no obstructions near 

its air intake or air outlet.

2.  When the outdoor unit is installed in a place that is always exposed to 

strong winds like on the coast or on a high story of a building, secure the 
normal fan operation using a duct or a wind shield.

3.  Especially in windy areas, install the unit to prevent the admission of wind.
4.  Installation in the following places may result in trouble. 

Do not install the unit in such places.

 

•  A place full of machine oil.

 

•  A saline-place such as the coast.

 

•  A place full of sul

fi

 de gas.

 

•  A place where high-frequency 

 

  waves are likely to be generated, 

 

  such as from audio equipment, 

 

  welders, and medical equipment.

•  Do not use the supplied drain nipple for draining water. Drain the water from 

all the drain holes directly.

•  To protect the outdoor unit from snow accumulation, install a holding frame, 

and attach a snow protection hood and plate.

*  Do not use a double-stacked design.

Precautions about Installation in Regions 

with Snowfall and Cold Temperatures

•  Bind the auxiliary pipes (two) and connecting cable with facing tape 

tightly. In case of leftward piping and rear-leftward piping, bind the 
auxiliary pipes (two) only with facing tape.

Indoor unit

Connecting cable

Auxiliary pipes

Installation plate

•  Carefully arrange pipes so that any pipe does not stick out of the rear 

plate of the indoor unit.

•  Carefully connect the auxiliary pipes and connecting pipes to one 

another and cut off the insulating tape wound on the connecting pipe 
to avoid double-taping at the joint; moreover, seal the joint with the 
vinyl tape, etc.

•  Since dewing results in a machine trouble, make sure to insulate both 

connecting pipes. (Use polyethylene foam as insulating material.)

•  When bending a pipe, carefully do it, not to crush it. 

The lower part of indoor unit may 

fl

 oat, 

due to the condition of piping and you 
cannot 

fi

 x it to the installation plate. In 

that case, use the 

%

 screws provided to 

fi

 x the unit and the installation plate. 

Information

Hook here.

Installation plate

Hook

Press

(unhook)

Push

Push

Do not rise the
drain hose.

Do not form the
drain hose into
a wavy shape.

50 mm
or more

Do not put the
drain hose end
into water.

Do not put the
drain hose end
in the drainage ditch.

Shield pipe

Drain hose

Extension drain hose

Inside the room

Wall

Drain
guide

Space for pipes

Snow protection plate

Snow protection hood

At least
50 cm

Snow accumulation line

Holding frame

Front

Anchor
bolts

Install at least 50 cm
above the snow
accumulation line.

Strong
wind

%

 

Screw

%

 

Screw

01_1115551229-EN.indd   7

01_1115551229-EN.indd   7

1/16/2558 BE   6:35 PM

1/16/2558 BE   6:35 PM

Summary of Contents for 38EYV050M

Page 1: ...r unit 42EQV050M 060M Outdoor unit 38EYV050M 060M 1115551229 AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL ENGLISH 01_1115551229 EN indd 1 01_1115551229 EN indd 1 1 16 2558 BE 6 35 PM 1 16 2558 BE 6...

Page 2: ...rainage 7 OUTDOOR UNIT 7 Installation Place 7 Precautions about Installation in Regions with Snowfall and Cold Temperatures 7 Refrigerant Piping Connection 8 Evacuating 8 Wiring Connection 8 Electrica...

Page 3: ...STALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE...

Page 4: ...be sure to stop the compressor unit before removing the refrigerant pipe If removing the refrigerant pipe while the compressor is operating with the service valve opened it may cause air suction and o...

Page 5: ...mote control holder Shield pipe Attach to the front panel Air filter Installation plate 50 mm or more 170 mm or more 170 mm or more 6 5 Filter Filter Hook Hook Remark Detail of accessory and installat...

Page 6: ...shall be installed as top of the indoor unit comes to at least 2 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION CAUTION Failure to firmly install the unit may...

Page 7: ...hem out The combination of using wire controller and batteries may cause of batteries explosion 3 Make hole for insert control wire by use screwdriver break the polyester sheet as shown on figure 7 4...

Page 8: ...pipe is laid exceeding 43 mm above the wall surface the indoor unit may unstably be set on the wall When bending the connecting pipe make sure to use a spring bender so as not to crush the pipe Bend t...

Page 9: ...o obstructions near its air intake or air outlet 2 When the outdoor unit is installed in a place that is always exposed to strong winds like on the coast or on a high story of a building secure the no...

Page 10: ...lves Packed valve at liquid side Service port Valve core Setting pin Packed valve at gas side Vacuum pump Vacuum pump adapter for counter flow prevention For R410A only Charge hose For R410A only Hand...

Page 11: ...in case of 2 air conditioners are installed near Remote Control B Setup 1 Press RESET button on the indoor unit to turn the air conditioner ON 2 Point the remote control at the indoor unit 3 Push and...

Page 12: ...O O O O O O X O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O X O 2 O O O X O O O O O O O O O O Z O O R410A O O O O O O O O X O O Z O O O O O O O X O O O O O O O O O O X...

Page 13: ...2 GR O O X O O O o o o o o o o o o O O O R410A HFC R410A 1 6 R22 0 o o o o o o o o o o o o o o o o 02_1115551229 GR indd 2 02_1115551229 GR indd 2 1 16 2558 BE 6 36 PM 1 16 2558 BE 6 36 PM...

Page 14: ...170 mm 170 mm 100 mm 100 mm 600 mm 600 mm O 6 5 A B C D A B C D 8 mm X 8 mm 10 mm 9 108 mm 28 mm 125 mm 2 5 m m 86 mm 102 mm 320 mm 600 mm 90 mm 600 mm 8 o o o o o o o o o o o o o 02_1115551229 GR ind...

Page 15: ...r of pipe hole 35 120 180 240 O 23 mm 65 mm o u it ut ne 40mm To unit ut ine 3 mm To un t o t l ne 40mm O e 23mm om he gh s de edge s he c n e o p pe ho e o n i t u o i e 120mm 0 2 5 1 0 1 2 0 O se 8...

Page 16: ...o o 2 3 1 2 3 7 4 8 5 9 0 25 N m 0 03 kgf m 6 7 3 1 16L 8 3 1 25L 9 3 1 25L 0 15 N m 0 02 kgf m 10 28 22 AWG 0 08 0 32 mm2 4 7 30 m 70 mm 5 mm 4 6 5 o o 0 12 N m 0 01 kgf m 7 8 9 28 22 AWG 0 08 0 32 m...

Page 17: ...o o o o o o o o o 43 mm o o o o o o 43 mm o o o o o o o o X o o o o o 7 30 mm o o O o o o o o o o o o o o o o o o R 30 mm X o o polisin o o o o o X o o o 3 1 16L o 3 1 25L 1 2 o 1 1 3 o PRESET TIMER...

Page 18: ...o o o o o o o I o o o o o o o o o o o o o o o o o o o o o o o o 20 m 15 20 16 20 o o 10 m o o o o o o o o 1 o o o o o I o o o o o o o 50 mm o o o o o o o o o o o 2 3 o o o E o o o o o o o o o o o o o...

Page 19: ...o 1 o 2 o o o o o o o o 7 A o mm RIDGID o 90 A O o o o o o o o o X o o o o o o o o o o R410A vo R410A vo o o R410A vo 101 kPa 76 cmHg O 5 O 1 o 2 o 3 o o o O 4 o o 5 o o o o o 7 o o o o o o o o o o o...

Page 20: ...o o o o o o o o o o o o o o o o o o TEST RUN COOL o o RESET 10 O o o o Auto Restart o Auto Restart o o o o o o o o o o o o 1 RESET 3 3 OPERATION 5 5 2 RESET 3 3 OPERATION o o o ON OFF O O o o o o o o...

Page 21: ...MEMO 02_1115551229 GR indd 10 02_1115551229 GR indd 10 1 16 2558 BE 6 37 PM 1 16 2558 BE 6 37 PM...

Page 22: ...MEMO 02_1115551229 GR indd 11 02_1115551229 GR indd 11 1 16 2558 BE 6 37 PM 1 16 2558 BE 6 37 PM...

Page 23: ...02_1115551229 GR indd 12 02_1115551229 GR indd 12 1 16 2558 BE 6 37 PM 1 16 2558 BE 6 37 PM...

Page 24: ...1115551229 02_1115551229 GR indd 13 02_1115551229 GR indd 13 1 16 2558 BE 6 37 PM 1 16 2558 BE 6 37 PM...

Reviews: