background image

Installation, Start-Up

and Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . 1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9

Step 1

Complete Pre-Installation Checks

. . . . 2

• UNPACK UNIT
• INSPECT SHIPMENT

Step 2

Select Location

. . . . . . . . . . . . . . . . . . . . . 2

Step 3

Mount Mounting Bracket on Wall

. . . . 4

Step 4

Connect Refrigerant Piping

. . . . . . . . . 5

Step 5

Connect Condensate Drain Line

. . . . . 7

Step 6

Make Electrical Connections

. . . . . . . . 7

Step 7

Make Connections to Outdoor Unit

. . 9

• COOLING-ONLY SYSTEMS

• HEAT PUMP SYSTEMS

Step 8

Install Fan Coil Unit Onto Mounting

Bracket

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-12

40QN Control System

. . . . . . . . . . . . . . . . . . . . . . . 10

After Extended Shutdowns

. . . . . . . . . . . . . . . . . . 10

Seasonal Changeovers

. . . . . . . . . . . . . . . . . . . . . . 10

To Turn The Unit On and Off

. . . . . . . . . . . . . . . . . 10

Adjusting Airflow

. . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Operating Mode Memory

. . . . . . . . . . . . . . . . . . . . 10

Automatic Operation (Auto) Mode

. . . . . . . . . . . . 11

Operating Fault Diagnosis

. . . . . . . . . . . . . . . . . . . 11

Microprocessor Control Operation

. . . . . . . . . . . 11

CLEANING AND MAINTENANCE

. . . . . . . . . . . . 12-14

Lubrication

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

To Install or Replace Remote Controller

Batteries

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

To Set the Current Time

. . . . . . . . . . . . . . . . . . . . . 13

To Remove and Clean or Replace Air Filters

. . 13

• TO REMOVE AIR FILTERS
• TO CLEAN OR REPLACE FILTERS

To Clean Indoor Unit Front Panel

. . . . . . . . . . . . 13

To Clean Indoor Coil

. . . . . . . . . . . . . . . . . . . . . . . . 13

To Clean Outdoor Coil (Outdoor Unit)

. . . . . . . . 14

To Clean Condensate Drains

. . . . . . . . . . . . . . . . . 14

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14,15

Diagnostic Codes

. . . . . . . . . . . . . . . . . . . . . . . . . . . 14

System Tests

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

• THERMISTOR TESTS
• COMPRESSOR FAILURE
• REVERSING VALVE FAILURE (38BK Only)

System Safeties and Interlocks

. . . . . . . . . . . . . . 15

• INDOOR FAN FAILURE
• COMPRESSOR SHORT-CYCLING PROTECTION
• INDOOR COIL FREEZE PROTECTION (Cooling or

Dehumidification Mode Only)

• INDOOR COIL HIGH-TEMPERATURE

PROTECTION (Heat Pump Systems Only)

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . 15-18

START-UP CHECKLIST

. . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installing and servicing air-conditioning equipment can be

hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should

install or service air-conditioning equipment.

Untrained personnel can perform basic maintenance, such

as cleaning and replacing filters. All other operations should
be performed by trained service personnel. When working
on air conditioning equipment, observe precautions in lit-

erature and on tags and labels attached to unit.

Follow all safety codes. Wear safety glasses and work gloves.

Use quenching cloth for brazing operations. Have fire ex-

tinguisher available. Read these instructions

thoroughly.

Con-

sult local building codes and National Electrical Code (NEC)
for special installation requirements.

Before installing or servicing system, always turn off
main power to system. There may be more than one dis-
connect switch. Turn off indoor fan coil power if ap-

plicable. Electrical shock can cause personal injury.

GENERAL

The new Carrier 40QNE heat pump high wall fan coil units

(Fig. 1) DO NOT have electric heaters. These new heat pump
fan coil units have been specifically designed to improve sys-
tem efficiency in both heating and cooling modes when matched
with a 38BK outdoor heat pump unit. If your application
requires heating, heat pump units must be used, both out-
doors and indoors. See Table 1 for recommended system

combinations.

Fig. 1 — 40QN High Wall Fan Coil Unit

40QNB/QNE

018,024

High Wall Fan Coil Units

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1 4
Tab

3e 2f

PC 111

Catalog No. 534-078

Printed in U.S.A.

Form 40QN-1SI

Pg 1

4-96

Replaces: New

Summary of Contents for 38BK-018

Page 1: ...S Installing and servicing air conditioning equipment can be hazardous due to system pressure and electrical compo nents Only trained and qualified service personnel should install or service air conditioning equipment Untrained personnel can perform basic maintenance such as cleaning and replacing filters All other operations should be performed by trained service personnel When working on air co...

Page 2: ...ting screws taped to the mounting bracket INSPECT SHIPMENT Upon receipt of shipment check unit Fig 1 for damage Forward claim papers directly to the transportation company Manufacturer is not responsible for damage incurred in transit Table 2 Application Ranges COOLING MODE Maximum Minimum Indoor Unit Outdoor Unit Indoor Unit Outdoor Unit 95 F DB 115 F DB 67 F DB 55 F DB 71 F WB 57 F WB 0 F DB HEA...

Page 3: ...cuRater device in the fan coil unit on 38HDC and BK applications A thermostatic expansion valve is used in the outdoor unit on 38HDS applications Insulate both refrigerant lines on 38HDS and BK applications 5 The 49 top and left side clearances are absolute minimums Clearances of 109 are recommended Fig 2 40QN Dimensional Drawing UNIT WEIGHT 40QN018 39 Lb 17 5 Kg 40QN024 43 Lb 19 5 Kg 3 ...

Page 4: ... 10 in away from the ceiling with the 8 screws provided Always be sure to insert screws into the top 2 holes indicated in Fig 6 Make sure the attached bracket will support a 200 lb vertical load For a masonry wall anchor shields can be used to attach bracket to the wall 4 Temporarily hang unit on bracket to check location and level A clearance of 49 is the absolute minimum A clearance of 109 is re...

Page 5: ...t be a 6 in vertical rise to the valve connections on the outdoor unit If more than the rec ommended length is buried refrigerant may migrate to the cooler buried section during extended periods of unit shutdown causing refrigerant slugging and possible com pressor damage at start up Use the following instructions to connect piping 1 Install insulation Insulateall refrigerant lines on heat pumps a...

Page 6: ... 39 43 REFRIGERANT R 22 with AccuRaterT Control or TXV FAN Rpm 1120 1470 Nominal Cfm High Speed 540 550 COIL Rows 2 3 Face Area sq ft 2 56 2 56 Fins in 15 9 18 1 Number of Circuits 2 3 CONNECTIONS MPT Suction in Flare 5 8 Liquid in Flare 3 8 Condensate Drain 5 8 LINE SIZES Suction in 5 8 Liquid in 3 8 Condensate Drain 5 8 TXV Thermostatic Expansion Valve 38HDS only Table 4 Required Piston Sizes fo...

Page 7: ...tch and unit NOTE Install branch circuit disconnect per NEC of ad equate size to handle unit starting current Locate disconnect within sight from and readily accessible from unit per Section 440 14 of NEC Some codes allow indoor unit to share disconnect with outdoor unit if disconnect can be locked check local code before installing in this manner To make electrical connections 1 Remove the screws...

Page 8: ...ocked Rotor Amps MCA Minimum Circuit Amps per NEC Section 430 24 NEC National Electrical Code Permissible limits of the voltage range at which unit will operate satisfactorily Fig 12 Drainage System Rear Piping Shown NOTE This shows item locations only Front cover of fan coil unit must be removed to access terminal boards Fig 13 Fan Coil Unit Wiring Preparation FAN COIL UNITS LEGEND CONN Connectio...

Page 9: ...R O and O and G and G Step 8 Install Fan Coil Unit Onto Mounting Bracket 1 Hook the fan coil unit onto the top of the mounting bracket See Fig 16 2 Snap the fan coil unit onto the mounting bracket as shown in Fig 16 IMPORTANT An audible snapping sound will be heard as the hook on the unit is secured into the hole on the mounting bracket Be sure unit is cor rectly mounted START UP Complete the foll...

Page 10: ...stem after it has been out of use for the winter season perform the following steps BEFORE starting the system 1 Inspect and clean the outdoor unit particularly the coil 2 Clean or replace the air filters in the indoor unit 3 Clean the indoor unit drain pan and drain pipe and re move any obstructions 4 Turn on indoor and outdoor unit disconnect switches to supply power to the system 12 hours befor...

Page 11: ... the following occurs 1 If the room temperature is above or equal to the selected temperature the unit will operate for 16 minutes and the compressor and outdoor fan will operate The indoor fan will operate as in the cooling mode After 16 minutes of operation or when the room reaches 2 F below set point the unit switches to normal dehumidification operation 2 If the room temperature is below the s...

Page 12: ...ency mode manually move the slide switch on the fan coil unit to the EMER position Fig 20 The unit is automatically operated in cooling or heating BK units only mode according to room tempera ture Emergency operation settings are as follows 1 Operation mode AUTO 2 Fan Speed AUTO 3 Cooling set point 77 F 4 Timer Mode Continuous NOTE The unit cannot be controlled by the remote con troller until the ...

Page 13: ... is flashing Note that a m and p m are also indicated as the times are scrolled through TA 3 Press again The flashing will stop and the current time will be reset to the new setting To Remove and Clean or Replace Air Filters Operating your system with dirty air filters may damage the indoor unit and can also cause reduced cooling per formance intermittent system operation frost build up on the ind...

Page 14: ...reen UNIT ON light on the front of the fan coil unit To access the LED indicator light remove the front cover of the unit by removing the 3 screws holding it in place If the LED indicator light continuously flashes on for one second then off for one second the control is functioning properly and no fault is present A fast flashing LED indi cates that a fault has been detected Table 7 lists the num...

Page 15: ...s less than or equal to 32 F for 10 minutes after the compressor has started then the compressor and outdoor fan are turned off The indoor fan continues to run at the user selected speed until the indoor coil reaches 44 F At that time the compressor and outdoor fan will restart INDOOR COIL HIGH TEMPERATURE PROTECTION Heat Pump Systems Only If indoor coil temperature is greater than or equal to 135...

Page 16: ...mistor RC Resistor Capacitor RCV Receiver RVS Reversing Valve Solenoid SC Start Capacitor SR Start Relay STM Step Motor TB Terminal Block TRAN Transformer U Unloader Terminal Marked Terminal Unmarked Splice Terminal Block Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring 1 If any of the original wire furnished must be replaced it must be replaced with type 90 C wi...

Page 17: ...ling Only System 38HDC Shown RELAY CHART COMPRESSOR K13 THERMISTOR EQUIVALENCE TEMPERATURE RESISTANCE F C V 95 35 6 500 72 22 11 400 32 0 32 500 ALL THERMISTORS IN THE 40QN SYSTEMS ARE IDENTICAL TO EACH OTHER 17 ...

Page 18: ...00 32 0 32 500 ALL THERMISTORS IN THE 40QN SYSTEMS ARE IDENTICAL TO EACH OTHER Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3e 2f PC 111 Catalog No 534 078 Printed in U S A Form 40QN 1SI Pg 18 4 96 Replaces New ...

Page 19: ...ORRECT SIZE FUSE OR HACR BREAKER BEEN PROVIDED ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY IS THE DISCONNECT SWITCH INSTALLED IN SIGHT FROM THE UNIT IS THE LOW VOLTAGE CABLE INDOOR TO OUTDOOR UNIT RUN AND CONNECTED PROPERLY HAS CONDENSATE DRAIN BEEN RUN AND SLOPED PROPERLY IS AIR FILTER S IN PLACE IS UNIT MOUNTED LEVEL IS COOLING PISTON INSTALLED THE CORRECT SIZE AND IN THE CORRECT DI...

Page 20: ... MEASURE AND RECORD THE AIR ENTERING OUTDOOR UNIT F AIR ENTERING INDOOR UNIT F DISCHARGE LINE TEMPERATURE F VAPOR LINE TEMPERATURE F MEASURE AND RECORD THE VAPOR LINE PRESSURE PSIG DISCHARGE PRESSURE PSIG CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and wi...