background image

 

 

 

PIPING CONNECTIONS 

Complete all installation and piping work required for indoor and 
outdoor units. If brazing is required pass nitrogen or other inert gas 
through piping to prevent formation of cooper oxide. Unit contains R-
22 charge, do not open Schreader valve at this time. Leak test field 
piping by pressure method.  
 
 

PIPING INSULATION 

No refrigerant control device is shipped with the unit except 024 
model. It is already installed in matching Fan coil units, check 
carefully the indoor unit. Insulate suction line adequately (Fig. 8) 
 

 

 
 
 

COMPLETE ELECTRICAL CONNECTIONS 
 
 
 

 

 

 
 

POWER 

– Unit is factory wired for voltage shown on name plate. 

Provide adequate fused disconnect switch within sign of unit, readily 
accessible, but out of reach children. 
 
Provide for locking switch open (OFF) is advisable to prevent power 
from being turned on w hile unit is being serviced. 
 
Route power wires through opening in unit side panel and connect in 
unit control box (fig. 9). Unit must be grounded. 

 

 

 
 
 

CONTROL CIRCUIT WIRING 

Refer to wiring diagram for field supplied wiring details. 
See Fig. 11 & 12. 

 

Note: - Operation of unit on improper line voltage constitutes 
            abuse and could affect Carrier Warranty. Do not install  
            unit in system where voltage may fluctuate above or below  
            permissible limits. 
 

START-UP 
PRELIMINARY CHECKS: 

1) 

Check that all internal wiring connections are tight and all 
barriers, covers and panels are in place. 

2) 

Field electrical power source must agree with unit name 
plate rating. 

3) 

All service valves must be opened. 

 

START SYTEM 

1. 

Check that field disconnect is closed. 

2. 

Set room thermostat to below room temperature, and unit 
compressor will start after 3 minutes delay o. 

3. 

Check back pressure when compressor runs. A dd charge to 
keep back pressure at approximately 448kPa (65 PSIG). 

 
 
 
 

REFRIGERANT CHARGING 
 
 

 

 
 
 
 
 
 

              I M P O R T A N T  

 
For accurate system performance, charge by superheat method 
as shown in table 5 and 6. 
 
To check and adjust charge, follow the following procedures:- 
 
1) 

Operate unit for a minimum of 15 minutes before checking 
charge. 

2) 

Measure suction pressure by attaching a gauge to suction 
line service port. 

3) 

Measure suction line temperature by attaching a service 
thermometer to unit suction line near suction valve. 
Insulate thermometer for accurate readings. 

4) 

Measure outdoor coil air inlet dry-bulb temperature with a 
second thermometer. 

5) 

Measure indoor coil air inlet wet-bulb temperature with a 
sling psychrometer. 

6) 

 Refer to table 5. Find air temperature entering outdoor coil 
& wet-bulb temperature entering indoor coil. At this 
intersection, note the superheat.   

7) 

Refer to table 6 . Find superheat temperature and suction 
pressure, note suction line temperature. 

 

 

FIG. 8 PIPING INSULATION 

                                   

CAUTION 

THE CONTROL VOLTAGE FROM THE FAN COIL UNIT 
MUST BE OF 230V. DO NOT CONNECT THE POWER 
SUPPLY TO THE

 

SIGNAL 

FIG. 9 POWER WIRES TO THE SIDE OF UNIT 

                                     

CAUTION 

TO PREVENT PERSONAL INJURY, WEAR SAFETY 
GLASSES AND GLOVES WHEN HANDLING 
REFRIGERANT. DO NOT OVERCHARGED SYSTEM. 
THIS CAN CAUSE COMPRESSOR FLOODING. 

NOTE: Model 240 need  
to insulate both Suction  

and liquid pipes 

5

 

Summary of Contents for 38ASB Series

Page 1: ... remove unit from the carton and take off protective covering If the unit has been damaged file claim with Transportation Company and notify Carrier immediately PROTECTION Protect unit from damage caused by job site debris Do not allow dust debris and water get into the unit These will damage unit s component and unit s performance will be affected 38ASB CCARS240 600 condensing units Fig 1 are shi...

Page 2: ...sed for 40KMC GKX 42GX AR 40LX Model used for SlimPack ASBFE600BA NEW MODEL NUMBER REMARKS 38ASB 3TR SERIES 38ASB240BA 38ASB360BA OLD MODEL NUMBER CCAR 5TR Single phase supply volatge CCARS024EA CCARS036EA CCARS060KA 2TR 38ASB036BA 38ASB060BA FIG 2 38ASB CCARS024 060 DIMENSIONAL DRAWING 2 ...

Page 3: ...ENSER COIL Rows Fins inch 2R 15 3 5R 15 Face Area m 2 0 379 CONNECTIONS Type Liquid mm inch Suction mm inch CONTROLS PRESSURES SWITCH High Cut Out psi SETTINGS Cut In psi Low Cut Out psi Cut In psi NOMINAL POWER SOURCE V Ph Hz ABSOLUTE MIN MAX VOLTAGE V 230V 3Ph 60Hz 19 05 3 4 15 88 5 8 Direct Drive 0 654 230V 1Ph 60Hz 230V 1Ph 60Hz 950 1 7 Flare 550 230V 3Ph 60Hz 230V 1Ph 60Hz Propeller 1 Permane...

Page 4: ... of refrigerant grade correct size and condition Suspend refrigerant tubes so they do not transmit vibration to structure Also when passing refrigerant tubes through walls seal opening so vibration is not transmitted to structure Leave some slack in refrigerant tubes between structure and unit to absorb vibration The longer the piping the lower the cooling capacity of the unit See table 3 TABLE 3 ...

Page 5: ...rce must agree with unit name plate rating 3 All service valves must be opened START SYTEM 1 Check that field disconnect is closed 2 Set room thermostat to below room temperature and unit compressor will start after 3 minutes delay o 3 Check back pressure when compressor runs Add charge to keep back pressure at approximately 448kPa 65 PSIG REFRIGERANT CHARGING IMPORTANT For accurate system perform...

Page 6: ...move dirt see Fig 10 Be sure to flush all dirt and debris from drain holes in base of unit Fan motor is water proof but it is more safe to cover or wrap motor shell with plastic sheet or plastic bag to prevent water from getting inside Clean coil semi annually or as required Fins are not continuous through coil sections Dirt and debris may pass between the row of fins and become trapped between th...

Page 7: ...PE740132 FIG 12 38ASB600DC WIRING DIAGRAM FIG 13 38ASB600DB WIRING DIAGRAM PE740133 NOTE FOR OTHER 38ASB WIRING DIAGRAM NOT SHOWN HERE PLEASE REQUEST COPIES FROM CCAC ENGINEERING DEPARTMENT 7 ...

Page 8: ... 16 1 17 8 19 4 20 6 22 2 23 3 25 15 5 3 9 5 6 6 7 8 3 10 11 7 13 3 15 16 7 18 3 19 4 21 1 22 2 23 9 18 3 3 3 5 8 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 1 22 8 21 1 3 9 5 6 7 2 8 9 10 6 11 7 13 3 15 16 7 18 3 20 21 7 23 9 3 3 5 6 7 8 3 10 11 7 13 3 15 6 17 2 18 9 20 6 26 7 2 8 4 4 6 7 8 3 10 11 7 13 9 15 6 17 2 19 4 29 4 4 4 6 1 8 3 10 6 12 2 14 4 16 7 18 3 32 2 2 8 5 7 2 8 9 11 1 13 3 15 17 2 ...

Page 9: ...FIG 14 SCHEMATIC SYSTEM WIRING DIAGRAM 38ASB240BA MATCHED WITH 42PGA026 38ASB240BA MATCHED WITH 42AR024 42GX024 38ASB360BA MATCHED WITH 42AR036 42GX040 9 ...

Page 10: ...38ASB240BA MATCHED WITH 40GKX KMC024 38ASB360BA MATCHED WITH 40GKX KMC036 FIG 15 SCHEMATIC SYSTEM WIRING DIAGRAM 38ASB360BA MATCHED WITH ASBFM360BA 10 ...

Page 11: ...FIG 16 SCHEMATIC SYSTEM WIRING DIAGRAM 38ASB360BA MATCHED WITH 40LX040 38ASB600DC MATCHED WITH 42AR 42GX060 11 ...

Page 12: ...38ASB600DC MATCHED WITH 40GKX KMC060 38ASB600DB MATCHED WITH 40LX060 12 ...

Page 13: ...38ASB600DC MATCHED WITH ASBFE600BA 13 ...

Page 14: ...ED OR CYLING COOLING OUTDOOR AIR RESTRICTED OR RECIRCULATING RESTRICTED DISCHARGE LINE OVERCHARGE OR NONCONDENSABLES IN SYSTEM LOW REFRIGERANT CHARGE LINE VOLTAGE TO HIGH OR LOW COMPRESSOR BEARINGS HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR MOTOR DEFECTIVE INCORRECT OUTDOORFANMOTOR CAPACITOR COMPRESSOR RUNS BUT INSUFFICIENT COOLING LOW SUCTION PRESSURE HIGH SUCTION LOW HEAD PRESSURE HIGH SUCTION LOW S...

Page 15: ...Tel No 63 2 850 1367 Fax No 63 2 809 9979 Website www carrier com ph Manufacturer reserve the right to discontinue or charge at any time specifications or designs without notice and without incurring obligations Form 38ASB CCARS024 060 1IOM Replaces NEW Concepcion Carrier Air conditioning Company Philippines 15 ...

Reviews: