Wiring Diagrams

Units Produced After January 1996

INDEX

UNIT

38AKS

ELECTRICAL

CHARACTERISTICS

(V-Ph-Hz)

SCHEMATIC

DIAGRAM

FIG. NO.

COMPONENT

ARRANGEMENT

FIG. NO.

LABEL DIAGRAM

(On Unit)

NO. 38AK

013-024

208/230-3-60

1

2

501206

380-3-60

1

2

501206

230-3-50

1

2

501206

346-3-50*

1

2

501206

400-3-50

1

2

501206

460-3-60

3

4

501207

575-3-60

3

4

501207

*38AKS024 only.
Remote Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fig. 5
Programmable Electronic Thermostat Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fig. 6
Accessory Transformer Relay Package

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fig. 7

Accessory Winter Start Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fig. 8
Motormaster® Control Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fig. 9-15

SAFETY CONSIDERATIONS

Installation, start-up, and servicing of this equipment can

be hazardous due to system pressures, electrical compo-
nents, and equipment location (roofs, elevated structures, etc.)

Only trained, qualified installers and service mechanics

should install, start up, and service this equipment.

When working on the equipment, observe precautions in

the literature, tags, stickers, and labels attached to the equip-
ment, and any other safety precautions that apply.

• Follow all safety codes.

• Wear safety glasses and work gloves.

• Use care in handling, rigging, and setting bulky equipment.

• Use care in handling electronic components.

ELECTRIC SHOCK HAZARD

Open all remote disconnects before servicing
this equipment.

OPERATING SEQUENCE

Cooling —

When the first stage (TC1) of the cooling ther-

mostat closes, the timer starts. After approximately
3 seconds, the timer activates the compressor and fan
motor no. 1. When the liquid pressure builds to approxi-
mately 260 psig (1793 kPa), fan motor no. 2 is energized.

On demand for additional cooling capacity, the second stage

(TC2) of the cooling thermostat closes, energizing a field-
supplied liquid line solenoid valve (LLSV), which opens.
This increases the suction pressure, causing the compressor
to operate at higher capacity.

When fan switch is set at AUTO, the indoor-air fan cycles

with the compressor. When the switch is set at CONT, the
indoor-air fan runs continuously.

At shutdown, the Time Guard® II timer prevents the com-

pressor from restarting for approximately 5 minutes.

In addition, a field-supplied solenoid valve (locate at fan

coil) wired in parallel with the compressor contactor coil,
shuts off the liquid line to prevent the refrigerant migration
back to the compressor during the off cycle. This valve is
recommended for all installations and is mandatory if piping
length is over 75 ft (22.9 m) or if liquid line diameter ex-
ceeds

5

8

in. (38AKS013, 014) or

7

8

in. (38AKS016, 024). If

two liquid line solenoid valves are used, add accessory relay-
transformer package 38AE900001 (60 Hz only).

38AKS013-024

Air-Cooled Condensing Units

50/60 Hz

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

3a 2a

PC 111

Catalog No. 563-820

Printed in U.S.A.

Form 38AKS-2W

Pg 1

8-96

Replaces: New

Summary of Contents for 38AKS013-024

Page 1: ...r mostat closes the timer starts After approximately 3 seconds the timer activates the compressor and fan motor no 1 When the liquid pressure builds to approxi mately 260 psig 1793 kPa fan motor no 2...

Page 2: ...l rating 24 vac 23 va maximum For 24 1 60 LLS sealed coil rating 24 vac 18 va maximum Minimum thermostat electrical rating is 120 va 5 amp at 24 vac Minimum fan switch electrical rating is 60 va 2 5 a...

Page 3: ...Fig 1 Power and Control Circuit Schematics 208 230 380 3 60 230 346 400 3 50 SCHEMATIC 3...

Page 4: ...Fig 2 Component Arrangement 208 230 380 3 60 230 346 400 3 50 COMPONENT ARRANGEMENT 4...

Page 5: ...Fig 3 Power and Control Circuit Schematics 460 575 3 60 SCHEMATIC 5...

Page 6: ...ion LLSV2 plus IFC va should not exceed 30 va 2 Do not exceed 5 va 24 vac per coil R1 Use accessory relay transformer package 38AE900001 if these va values must be exceeded Fig 5 Remote Thermostat Wir...

Page 7: ...LLSV2 plus IFC VA should not exceed 30 VA 2 Do not exceed 5 VA 24 VAC per coil 3 If the VA values in Notes 1 and 2 must be exceeded use accessory relay transformer pack age 38AE900001 60 Hz units onl...

Page 8: ...ommon R Accessory Relay Field Supplied HD Heat Device SVR Solenoid Valve Relay HT ANT Heat Anticipator TC Thermostat Cooling IFC Indoor Fan Contactor TH Thermostat Heating IFR Indoor Fan Relay Fig 7 A...

Page 9: ...t control before installing and us ing the low ambient kit Order Winter Start Control acces sory no 38AE900021 and install according to the instruc tions supplied with the kit See Fig 9 for wiring FAB...

Page 10: ...DIMENSIONS ft in BAFFLE LOCATIONS A Right Hand Side 2 511 16 Back 5 81 8 Left Hand Side 3 07 16 As viewed from access panel side Fig 10 Wind Baffle Details 10...

Page 11: ...with condensing unit MOUNT SENSOR ASSEMBLY The sensor assembly is fragile Handle with care 1 See Fig 12 to determine where to locate sensor on coil return bend As shown in Fig 13 fasten sensor to retu...

Page 12: ...he condensing temperature and then main tained until the set point is achieved If fan motor no 1 does not start verify the following con ditions and correct as necessary Condensing unit power is on Po...

Page 13: ...HOLES 156 154 4 mm DIAM NO 23 DRILL BOTTOM OF CONTROL ALL VOLTAGES EXCEPT 460V CUT ALONG SOLID BORDER LINES TO REMOVE TEMPLATE BOTTOM OF 460V CONTROL 5 1 2 140 MM 5 1 2 140 MM 4 1 2 114 mm TOP OF CON...

Page 14: ......

Page 15: ......

Page 16: ...facturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 111 Catalog No 563 820 Printed in U S...

Reviews: