INSTALL CONTROL POWER WIRING — Wire the Motor-
master® low-ambient control to the unit’s power circuit as
shown in Fig. 14 and 15; refer to the following sections for
various unit voltages.

Wire low-ambient control in series with fan motor.

Power wiring must comply with all local and national re-

quirements. All units except 460-v, 3-ph, 60 Hz use Motor-
master control, Carrier Part No. 32LT900301. The 460-v units
use Motormaster control, Carrier Part No. 32LT900611.

ALL UNITS EXCEPT 575-3-60 — For these units, without
special transformer, wire Motormaster control to condenser
fan motor circuit as shown in Fig. 14.

575-3-60 UNITS — The 575-v units require a special field-
installed transformer and fan motor. Wire special trans-
former (part no. HT01AH859) and Motormaster control to
special fan motor (part no. HC44VL610) as shown in Fig. 15.

Blue wire from CB1-13 to CAP1 must be reconnected from

CB1-13 to TRAN2-H2.

Blue wire from CAP1 to TRAN2-H2 must be recon-

nected from CAP1 to field-installed transformer.

VERIFY OPERATION — Turn on the unit power and set
the thermostat below the ambient room temperature. If the
unit is equipped with a Time Guard® II circuit, wait at least
5 minutes.

After the compressor starts, the fan speed is modulated

according to the condensing temperature and then main-
tained until the set point is achieved.

If fan motor no. 1 does not start, verify the following con-

ditions and correct as necessary:

• Condensing unit power is on.
• Power is present at fan motor relay contacts (or trans-

former output output when one is installed).

• Sensor wire connections inside the low-ambient control

are tight.

If the preceding conditions are met and fan motor no. 1

still does not start, perform corrective procedures or replace
components as follows:

• Jumper the power wires (BLK-to-BLK) in the Motor-

master control. If the motor does not run, check motor wir-
ing and run capacitor. Replace capacitor and motor if nec-
essary. If the motor runs, ensure the fan motor is wired in
series with the control. Refer to Fig. 14.

• If the fan motor runs when connected to the single-phase

voltage supply but does not run when connected in series
with the Motormaster control, AND the return bend where
the sensor is mounted is warm, short the sensor leads (BLU-
to-RED). If the motor runs, replace the sensor. If the mo-
tor does not run, replace the control and sensor assembly.

Fig. 12 — Location of Low-Ambient Kit Sensors

Fig. 13 — Sensor Installation

*Use control part no. 32LT900301 for all unit voltages except 460 V.

Use control part no. 32LT900611 for 460 V units.

Fig. 14 — Motormaster Control Power Wiring

for All Units except 575-V

Fig. 15 — Motormaster Control Power Wiring for 575-V

Units Using 208/230-V Motors

12

Summary of Contents for 38AKS013-024

Page 1: ...r mostat closes the timer starts After approximately 3 seconds the timer activates the compressor and fan motor no 1 When the liquid pressure builds to approxi mately 260 psig 1793 kPa fan motor no 2...

Page 2: ...l rating 24 vac 23 va maximum For 24 1 60 LLS sealed coil rating 24 vac 18 va maximum Minimum thermostat electrical rating is 120 va 5 amp at 24 vac Minimum fan switch electrical rating is 60 va 2 5 a...

Page 3: ...Fig 1 Power and Control Circuit Schematics 208 230 380 3 60 230 346 400 3 50 SCHEMATIC 3...

Page 4: ...Fig 2 Component Arrangement 208 230 380 3 60 230 346 400 3 50 COMPONENT ARRANGEMENT 4...

Page 5: ...Fig 3 Power and Control Circuit Schematics 460 575 3 60 SCHEMATIC 5...

Page 6: ...ion LLSV2 plus IFC va should not exceed 30 va 2 Do not exceed 5 va 24 vac per coil R1 Use accessory relay transformer package 38AE900001 if these va values must be exceeded Fig 5 Remote Thermostat Wir...

Page 7: ...LLSV2 plus IFC VA should not exceed 30 VA 2 Do not exceed 5 VA 24 VAC per coil 3 If the VA values in Notes 1 and 2 must be exceeded use accessory relay transformer pack age 38AE900001 60 Hz units onl...

Page 8: ...ommon R Accessory Relay Field Supplied HD Heat Device SVR Solenoid Valve Relay HT ANT Heat Anticipator TC Thermostat Cooling IFC Indoor Fan Contactor TH Thermostat Heating IFR Indoor Fan Relay Fig 7 A...

Page 9: ...t control before installing and us ing the low ambient kit Order Winter Start Control acces sory no 38AE900021 and install according to the instruc tions supplied with the kit See Fig 9 for wiring FAB...

Page 10: ...DIMENSIONS ft in BAFFLE LOCATIONS A Right Hand Side 2 511 16 Back 5 81 8 Left Hand Side 3 07 16 As viewed from access panel side Fig 10 Wind Baffle Details 10...

Page 11: ...with condensing unit MOUNT SENSOR ASSEMBLY The sensor assembly is fragile Handle with care 1 See Fig 12 to determine where to locate sensor on coil return bend As shown in Fig 13 fasten sensor to retu...

Page 12: ...he condensing temperature and then main tained until the set point is achieved If fan motor no 1 does not start verify the following con ditions and correct as necessary Condensing unit power is on Po...

Page 13: ...HOLES 156 154 4 mm DIAM NO 23 DRILL BOTTOM OF CONTROL ALL VOLTAGES EXCEPT 460V CUT ALONG SOLID BORDER LINES TO REMOVE TEMPLATE BOTTOM OF 460V CONTROL 5 1 2 140 MM 5 1 2 140 MM 4 1 2 114 mm TOP OF CON...

Page 14: ......

Page 15: ......

Page 16: ...facturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 111 Catalog No 563 820 Printed in U S...

Reviews: