background image

Installation —

After completing the pre-installation steps,

proceeds as follows:

MOUNT CONTROL ASSEMBLY
1. See Fig. 11 for the location of the access panel and Motor-

master® low-ambient control in the bottom of the unit.
Remove the access panel.

2. Using the template supplied in this document, drill pilot

holes for mounting the low-ambient control.

When drilling holes, be careful not to damage return coil
bends inside unit.

3. Fasten control to unit with four no. 10 sheet metal screws

and star lockwashers provided. Lockwashers are re-
quired to ensure electrical ground with condensing unit.

MOUNT SENSOR ASSEMBLY

The sensor assembly is fragile. Handle with care.

1. See Fig. 12 to determine where to locate sensor on coil

return bend. As shown in Fig. 13, fasten sensor to return
bend with the supplied screw, plate washers, and nut. See
Table 1 for sensor temperature vs resistance values.

2. Coil and secure excess wire inside the unit near the sen-

sor or next to the low ambient control; provide additional
protection against abrasion or movement of the wire if
necessary.

3. Reinstall the access panel.

Table 1 — Sensor (Thermistor) Temperature

vs Resistance

TEMPERATURE

NOMINAL RESISTANCE

(Ohms)

F

C

60

16

7750

70

21

5900

77

25

5000

80

27

4650

90

32

3650

100

38

2875

110

43

2275

120

49

1850

Fig. 11 — Location of Motormaster Low-Ambient Control

11

Summary of Contents for 38AKS013-024

Page 1: ...r mostat closes the timer starts After approximately 3 seconds the timer activates the compressor and fan motor no 1 When the liquid pressure builds to approxi mately 260 psig 1793 kPa fan motor no 2...

Page 2: ...l rating 24 vac 23 va maximum For 24 1 60 LLS sealed coil rating 24 vac 18 va maximum Minimum thermostat electrical rating is 120 va 5 amp at 24 vac Minimum fan switch electrical rating is 60 va 2 5 a...

Page 3: ...Fig 1 Power and Control Circuit Schematics 208 230 380 3 60 230 346 400 3 50 SCHEMATIC 3...

Page 4: ...Fig 2 Component Arrangement 208 230 380 3 60 230 346 400 3 50 COMPONENT ARRANGEMENT 4...

Page 5: ...Fig 3 Power and Control Circuit Schematics 460 575 3 60 SCHEMATIC 5...

Page 6: ...ion LLSV2 plus IFC va should not exceed 30 va 2 Do not exceed 5 va 24 vac per coil R1 Use accessory relay transformer package 38AE900001 if these va values must be exceeded Fig 5 Remote Thermostat Wir...

Page 7: ...LLSV2 plus IFC VA should not exceed 30 VA 2 Do not exceed 5 VA 24 VAC per coil 3 If the VA values in Notes 1 and 2 must be exceeded use accessory relay transformer pack age 38AE900001 60 Hz units onl...

Page 8: ...ommon R Accessory Relay Field Supplied HD Heat Device SVR Solenoid Valve Relay HT ANT Heat Anticipator TC Thermostat Cooling IFC Indoor Fan Contactor TH Thermostat Heating IFR Indoor Fan Relay Fig 7 A...

Page 9: ...t control before installing and us ing the low ambient kit Order Winter Start Control acces sory no 38AE900021 and install according to the instruc tions supplied with the kit See Fig 9 for wiring FAB...

Page 10: ...DIMENSIONS ft in BAFFLE LOCATIONS A Right Hand Side 2 511 16 Back 5 81 8 Left Hand Side 3 07 16 As viewed from access panel side Fig 10 Wind Baffle Details 10...

Page 11: ...with condensing unit MOUNT SENSOR ASSEMBLY The sensor assembly is fragile Handle with care 1 See Fig 12 to determine where to locate sensor on coil return bend As shown in Fig 13 fasten sensor to retu...

Page 12: ...he condensing temperature and then main tained until the set point is achieved If fan motor no 1 does not start verify the following con ditions and correct as necessary Condensing unit power is on Po...

Page 13: ...HOLES 156 154 4 mm DIAM NO 23 DRILL BOTTOM OF CONTROL ALL VOLTAGES EXCEPT 460V CUT ALONG SOLID BORDER LINES TO REMOVE TEMPLATE BOTTOM OF 460V CONTROL 5 1 2 140 MM 5 1 2 140 MM 4 1 2 114 mm TOP OF CON...

Page 14: ......

Page 15: ......

Page 16: ...facturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 111 Catalog No 563 820 Printed in U S...