background image

7

Carrier inlet areas are shown in Table 6. The design air

volume is shown in this table. It can be determined from this
table that the average design air velocity for those units is equal
to 2656 fpm at 1.0-in. wg.

Table 6 — Inlet Areas

.

*35L units only.
NOTE: For Carrier ComfortID™ terminals, all flow sizes are normal-
ized using a single Probe Multiplier (PMF) for all sizes equal to
2.273.

PNEUMATIC CONTROLS

All control packages are pressure independent and include

standard linear airflow sensors in both the hot and cold inlets
for variable air volume control (control sequence 1500 to 1507)
or an airflow sensor in one inlet and unit discharge for constant
volume control arrangements (control sequence 1508 to 1523).

Preparation for Balancing

1. Inspect all pneumatic connections to assure tight fit and

proper location.

2. Verify that the thermostat being used is compatible with

the control sequence provided (direct acting or reverse
acting).

3. Check main air pressure at the controller(s). The main air

pressure must be between 15 psi and 25 psi. (If dual or

switched-main air pressure is used, check the pressure at
both high and low settings.) The difference between
“high” pressure main and “low” pressure main should be
at least 4 psi, unless otherwise noted, and the “low” set-
ting difference should exceed 15 psi.

4. Check that the unit damper will fail to the proper position

when main air pressure is lost. Disconnect the pneumatic
actuator line from the velocity controller and observe the
VAV damper position. The damper should fail to either a
normally open position (indicator mark on shaft end is
horizontal) or a normally closed position (indicator mark
on shaft end is vertical).

5. Check that there is primary airflow in the inlet duct.
6. Connect a Magnehelic gage, inclined manometer or other

differential pressure measuring device to the balancing
taps provided in the velocity probe sensor lines. The
manometer should have a full scale reading of 0.0 to
1.0 in. wg. The high pressure signal is delivered from the
front sensor tap (away from the valve), and the low pres-
sure signal is delivered from the back line (near the
valve). The pressure differential between high and low
represents the amplified velocity pressure in the inlet
duct.

7. Read the differential pressure and enter the Flow Probe

Chart to determine the airflow in the terminal unit. This
chart is shown in Fig. 4A-4C and is also attached to the
side of each unit. For example, a differential pressure of
0.10 in. wg for a size 8 unit yields an airflow of 275 cfm.

Volume controller for units is shown in Fig. 5.

Balancing

Procedure

(Control

Sequences

1500-1523)

1. Damper action is factory set at NO (normally open), or

NC (normally closed). To reselect loosen damper selec-
tion switch screw and align pointer with damper pointer
and tighten screw. The spring range of the actuator is not
critical since the controller will output the necessary pres-
sure to the actuator to position the damper according to
set point. (See Fig. 5.)

2. Pipe the controller: Connect port “B” to the damper actu-

ator. Connect port “M” to the clean, dry main air. Connect
port “T” to the thermostat output. Connect port “H” to the
total pressure tap on the airflow sensor. Connect port “L”
to the static pressure tap on the airflow sensor.

The controller can be set up for cooling or heating applications
using either a direct acting (DA) or reverse acting (RA) ther-
mostat signal. The two flow adjustments are labeled “LO
STAT

P” and “HI STAT

P.”

35L,N UNIT SIZE

04*

05*

06

07*

08

09*

INLET

DIAMETER

4.0

5.0

6.0

7.0

8.0

9.0

CFM AT 1 IN. WG

232

362

502

710

927

1174

INLET AREA

(sq ft)

0.087

0.136

0.196

0.267

0.349

0.442

35L,N UNIT SIZE

10

12

14

16

22*

INLET DIAMETER

10.0

12.0

14.0

16.0

16 x 24

CFM AT 1 IN. WG

1449

2086

2840

3709

7250

INLET AREA

(sq ft)

0.545

0.785

1.069

1.396

2.640

10000

8000

6000

4000

2000

1000

800

600

400

200

100

80

60

40

20

10

0.01

.03

.05

0.1

0.3

0.5

1

710

522

362

232

2086

1449

1174

927

3709

2840

7250

FLOW PROBE PRESSURE DIFFERENTIAL IN. WG

CFM

CFM

A

T

ONE

INCH

SIGNAL

SIZE

4

SIZE

5

SIZE

6

SIZE

7

SIZE

8

SIZE

9

SIZE

10

SIZE

12

SIZE

14

SIZE

16

SIZE

22

NOTE: Size 22 available on 35L units only.

Fig. 4C — Dual Duct Inlet Flow Probe Chart

(35L only)

T

H

L

B

M

NO

NC

G

RESET START

LO STAT

P

RESET SPAN

HI STAT

P

D A M P E R

I N C R

I N C R

TO DAMPER
ACTUATOR
TO MAIN AIR
SUPPLY

DIFFERENTIAL PRESSURE (FLOW)
LIMIT ADJUSTMENT WHEN T’STAT
PRESSURE IS HIGH (HI STAT)
(FACTORY SET AT 0.65 IN. WG.)†
†- FIELD ADJUSTMENT REQUIRED

DIFFERENTIAL PRESSURE (FLOW)
LIMIT ADJUSTMENT WHEN T’STAT
PRESSURE IS LOW (LO STAT)
(FACTORY SET AT 0 IN. WG.)†

ALL ADJUSTMENTS CCW TO INCREASE
(1/8”-5/32” FLATBLADE SCREWDRIVER)

RESET SPAN ADJUSTMENT
(FACTORY SET AT 5 PSI)

DAMPER ACTION SELECTION
(FACTORY SET AT NORMALLY OPEN)
NOTE: SCREW MUST BE TIGHT AND ARROWS
IN PERFECT ALIGNMENT FOR DEVICE TO FUNCTION PROPERLY.

LOOSEN SCREW TO
CHANGE DAMPER ACTION
(SUPPLIED IN N.O. POSITION)

GAGE TAP. LEAVE CAP ON UNLESS
CONNECTING GAGE FOR RESET
START OR RESET SPAN ADJUSTMENT

PUSH ON NIPPLES
FOR 3/16” (5) I.D.
FR TUBING (5)

* TO STATIC PRESSURE

TO TOTAL PRESSURE

*(DIFFERENCE IS: DIFFERENTIAL
PRESSURE, OR DEVICE
VELOCITY PRESSURE)

RESET START POINT ADJUSTMENT
(FACTORY SET AT 8 PSI)

TO THERMOSTAT BRANCH SIGNAL
(RESET SIGNAL)

Fig. 5 — CSC-3011 Controller

Summary of Contents for 35L Series

Page 1: ...EMPERATURE SENSOR AND SET POINT ADJUSTMENT SLIDEBAR WIRING THE CCN NETWORK COMMUNICATION SERVICE JACK PRIMARY AIR TEMPERATURE SENSOR INSTALLATION INDOOR AIR QUALITY SENSOR INSTALLATION INDOOR AIR QUAL...

Page 2: ...llowing conditions 1 Unit casing is 22 gage 2 Unit insulation is 1 2 in thick 1 5 lb Tuf Skin Rx dual density fiberglass 3 Units rated with standard linear flow sensor Warranty All Carrier furnished i...

Page 3: ...controller DA NO cold inlet NO hot inlet 1503 Multi function controller DA NO cold inlet NC hot inlet 1504 Multi function controller RA NC cold inlet NC hot inlet 1505 Multi function controller RA NC...

Page 4: ...rop Ps of the desired configuration INLET SIZE in CFM MINIMUM AIRFLOW CFM MINIMUM CCN AIRFLOW CFM MINIMUM INLET STATIC PRESSURE Unit Pressure Drop in wg MINIMUM SYSTEM OPERATING PRESSURE in wg AT MAXI...

Page 5: ...ic Pressure drop Ps of the desired configuration Table 5 35N Dual Duct Full Blending Discharge Sensor Pickup CCN Carrier Comfort Network INLET SIZE Area CFM MINIMUM AIRFLOW CFM MINIMUM CCN AIRFLOW CFM...

Page 6: ...l terminals at system start up System calibration is accomplished by calculating a flow coefficient that adjusts the pressure fpm characteristics The flow coefficient is determined by dividing the flo...

Page 7: ...ields an airflow of 275 cfm Volume controller for units is shown in Fig 5 Balancing Procedure Control Sequences 1500 1523 1 Damper action is factory set at NO normally open or NC normally closed To re...

Page 8: ...t start point to the controller s internal reset start point of 0 psig RESET SPAN setting is factory set at 5 0 psig This is the required change in thermostat pressure that the controller will reset b...

Page 9: ...a 1 6 in hex key wrench turn the setscrews clockwise until cover is loose 3 Check voltages Verify 16 vdc between and terminals Applications for Dual Duct Minimum Air From Cold Duct Dual duct applicati...

Page 10: ...e found inside the control box SUPPLY AIR TEMPERATURE SAT SENSOR INSTAL LATION On terminals with heat the SAT sensor is provid ed The sensor is factory wired to the controlled and shipped in the contr...

Page 11: ...secure the sensor to the electrical box 6 Use 20 gage wire to connect the sensor to the controller This size is suitable for distances of up to 500 ft Use a three conductor shielded cable for the sen...

Page 12: ...nches Fig 14 Space Temperature Sensor and Wall Mounted Humidity Sensor Mounting 2 3 4 5 6 1 SW1 SEN BLK GND RED SPT RED WHT GND BLK CCN COM SENSOR WIRING Fig 15 Space Temperature Sensor Wiring 33ZCT55...

Page 13: ...supplied wire nuts to connect cable to sensor 5 At zone controller connect sensor wires to PAT and GND terminals INDOOR AIR QUALITY SENSOR INSTALLATION The indoor air quality IAQ sensor accessory mon...

Page 14: ...fty areas such as near heat ing or air conditioning ducts open windows fans or over heat sources such as baseboard heaters radiators or wall mounted light dimmers Sensors mounted in those areas will p...

Page 15: ...lation section for sensor wiring instructions COMMUNICATION BUS WIRE SPECIFICATIONS The Carrier Comfort Network CCN Communication Bus wiring is field supplied and field installed It consists of shield...

Page 16: ...all dampers to control to the minimum cooling cfm and verify that the static pressure is below the maximum safe operating limits when the damper is providing minimum cooling airflow 5 Set air source s...

Page 17: ...ow to the space A typical application is shown in Fig 24 Use package no 4160 with 35L N units COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH CONSTANT MINIMUM COLD DECK AIRFLOW CONTROL PACKAGE NO 4170 Du...

Page 18: ...air system The venti lation air is conditioned heated cooled dehumidified as required to provide a neutral temperature The ventilation air is connected to the hot deck inlet of the terminal The contr...

Page 19: ......

Page 20: ...tinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53350001 01 Printed in U S A Form 35L N 1SI Pg 20 3 06 Replaces 35L M N 1SI Book 3...

Reviews: