background image

10

Analog Control Troubleshooting —

The

follow-

ing troubleshooting guide is directed towards single duct cool-
ing applications, the same concepts can be applied to other
configurations.

CONTROLLER

1. Verify 24 vac at terminals “~” (phase) and “-” (ground).

Tolerance can be –15% to +20% (20.4 to 28.8 vac).

2. Verify 16 vdc at terminals “16 VDC” and “-”.

a. Tolerance is 15.0 to 17.0 vdc power supply to

thermostat.

b. If not correct, disconnect thermostat and recheck.

If still incorrect, replace CSP controller.

3. Check requested flow voltage on terminal “IN” and “-”.

a. Use charts on pages 6 and 7, Fig. 4A-4C to corre-

late into cubic feet per minute (cfm).

b. If reading is not what is desired, see the System

Calibration of the Linear Averaging Flow Probe
section to adjust thermostat.

4. Check actual flow voltage on terminal “OUT” and “-”

(for 0 to 10 vdc).
Use charts on pages 6 and 7, Fig. 4A-4C to correlate into
cfm.

5. Check box movement, damper rotation, etc.

a. Review requested flow and actual flow parameters

above to determine if unit should be satisfied
(within 50 fpm) or driving open or closed.

b. If damper is not moving, verify damper is not stuck

or at end of travel. Check rotation jumpers for
proper position.

c. Change requested flow to make unit drive opposite

direction. This can be accomplished by moving the
set point sliders or 1) and 2) below.

1.) To manually open the box, remove wiring from

terminal “IN” and jumper terminal “IN” to ter-
minal “16VDC”. This will tell unit to control at
3300 fpm/full airflow, and the green LED
should turn on (and the box should drive open).

2.) To manually close the box, remove wiring from

terminal “IN”, jumper and “IN” terminal to “-”
terminal. This will tell unit to control at zero
fpm/no airflow, and the red LED should be on
(and the box should drive closed).

NOTE: When using the same transformer for more than one
control, the phase and ground must be consistent with each
device.

ComfortID™ CONTROLS

Install

Sensors

and

Make

Field

Wiring

Connections

GENERAL — All field wiring must comply with National
Electrical Code (NEC) and local requirements. Refer to
Tables 8-11 for electrical and wiring specifications.

For information on how to test and balance CCN controls,

refer to the 33ZC Installation and Operation Instructions.

Wire the control as shown on the control package diagram

for the specific installation. Control wiring diagrams can be
found inside the control box.
SUPPLY-AIR TEMPERATURE (SAT) SENSOR INSTAL-
LATION — On terminals with heat, the SAT sensor is provid-
ed. The sensor is factory wired to the controlled and shipped in
the control box. The SAT must be field-installed in the duct
downstream from the air terminal. The SAT sensor part num-
ber is 33ZCSENSAT. See Table 8 for resistance information.

To install the sensor, proceed as follows:

1. Remove the plug from one of the

7

/

8

-in. openings in the

control box and pass the sensor probe through the hole.

2. Drill or punch a

1

/

2

-in. hole in the duct downstream of

the unit, at a location meeting the requirements shown in
Fig. 11.

3. Using 2 self-drilling screws (supplied), secure the sensor

probe to the duct.

The SAT sensor probe is 6 inches in length. The tip of the

probe must not touch the inside of the duct. Use field-supplied
bushings as spacers when mounting the probe in a duct that is
6 in. or less in diameter.

If the unit is a cooling only unit, the SAT sensor is not pro-

vided and is not required.

For units with hot and cold airstreams, locate SAT sensor

probe at least 2 ft downstream (see Fig. 11).

Perform the following steps if state or local code requires

the use of conduit, or if your installation requires a cable length
of more than 8 ft:

1. Disconnect the sensor cable from the ComfortID zone

controller, at the terminals labeled SAT and GND.

2. Mount the sensor to the duct (see steps 2 and 3 above).
3. Mount a field-supplied 4-in. x 4-in. x 20-in. extension

box over the duct sensor.

4. Connect a conduit (

1

/

2

-in. nominal) to the zone controller

enclosure and extension box.

5. Pass the sensor probe through the extension box opening

and into the conduit.

6. Reconnect the sensor leads to the zone controller labeled

SAT and GND.

Never jumper terminal 16 VDC to “-” as this would cause
a short, and possibly damage the power supply.

Disconnect electrical power before wiring inside the con-
troller. Electrical shock, personal injury, or damage to the
zone controller can result.

DO NOT run sensor or relay wires in the same conduit or
raceway with Class 1 service wiring.
DO NOT abrade or nick the outer jacket of cable.
DO NOT pull or draw cable with a force that may harm the
physical or electrical properties.
DO NOT bend a cable through a radius sharper than that
recommended by its manufacturer.
AVOID splices in any control wiring.

LEAVING

AIR

HEATED

AIR

COOL

AIR

2 FT. MIN.

SAT

ZC

Fig. 11 — Supply Air Temperature Probe

(Part No. 33ZCSENSAT) Locations

LEGEND

SAT —

Supply Air Temperature Sensor

ZC

Zone Controller

Summary of Contents for 35L Series

Page 1: ...EMPERATURE SENSOR AND SET POINT ADJUSTMENT SLIDEBAR WIRING THE CCN NETWORK COMMUNICATION SERVICE JACK PRIMARY AIR TEMPERATURE SENSOR INSTALLATION INDOOR AIR QUALITY SENSOR INSTALLATION INDOOR AIR QUAL...

Page 2: ...llowing conditions 1 Unit casing is 22 gage 2 Unit insulation is 1 2 in thick 1 5 lb Tuf Skin Rx dual density fiberglass 3 Units rated with standard linear flow sensor Warranty All Carrier furnished i...

Page 3: ...controller DA NO cold inlet NO hot inlet 1503 Multi function controller DA NO cold inlet NC hot inlet 1504 Multi function controller RA NC cold inlet NC hot inlet 1505 Multi function controller RA NC...

Page 4: ...rop Ps of the desired configuration INLET SIZE in CFM MINIMUM AIRFLOW CFM MINIMUM CCN AIRFLOW CFM MINIMUM INLET STATIC PRESSURE Unit Pressure Drop in wg MINIMUM SYSTEM OPERATING PRESSURE in wg AT MAXI...

Page 5: ...ic Pressure drop Ps of the desired configuration Table 5 35N Dual Duct Full Blending Discharge Sensor Pickup CCN Carrier Comfort Network INLET SIZE Area CFM MINIMUM AIRFLOW CFM MINIMUM CCN AIRFLOW CFM...

Page 6: ...l terminals at system start up System calibration is accomplished by calculating a flow coefficient that adjusts the pressure fpm characteristics The flow coefficient is determined by dividing the flo...

Page 7: ...ields an airflow of 275 cfm Volume controller for units is shown in Fig 5 Balancing Procedure Control Sequences 1500 1523 1 Damper action is factory set at NO normally open or NC normally closed To re...

Page 8: ...t start point to the controller s internal reset start point of 0 psig RESET SPAN setting is factory set at 5 0 psig This is the required change in thermostat pressure that the controller will reset b...

Page 9: ...a 1 6 in hex key wrench turn the setscrews clockwise until cover is loose 3 Check voltages Verify 16 vdc between and terminals Applications for Dual Duct Minimum Air From Cold Duct Dual duct applicati...

Page 10: ...e found inside the control box SUPPLY AIR TEMPERATURE SAT SENSOR INSTAL LATION On terminals with heat the SAT sensor is provid ed The sensor is factory wired to the controlled and shipped in the contr...

Page 11: ...secure the sensor to the electrical box 6 Use 20 gage wire to connect the sensor to the controller This size is suitable for distances of up to 500 ft Use a three conductor shielded cable for the sen...

Page 12: ...nches Fig 14 Space Temperature Sensor and Wall Mounted Humidity Sensor Mounting 2 3 4 5 6 1 SW1 SEN BLK GND RED SPT RED WHT GND BLK CCN COM SENSOR WIRING Fig 15 Space Temperature Sensor Wiring 33ZCT55...

Page 13: ...supplied wire nuts to connect cable to sensor 5 At zone controller connect sensor wires to PAT and GND terminals INDOOR AIR QUALITY SENSOR INSTALLATION The indoor air quality IAQ sensor accessory mon...

Page 14: ...fty areas such as near heat ing or air conditioning ducts open windows fans or over heat sources such as baseboard heaters radiators or wall mounted light dimmers Sensors mounted in those areas will p...

Page 15: ...lation section for sensor wiring instructions COMMUNICATION BUS WIRE SPECIFICATIONS The Carrier Comfort Network CCN Communication Bus wiring is field supplied and field installed It consists of shield...

Page 16: ...all dampers to control to the minimum cooling cfm and verify that the static pressure is below the maximum safe operating limits when the damper is providing minimum cooling airflow 5 Set air source s...

Page 17: ...ow to the space A typical application is shown in Fig 24 Use package no 4160 with 35L N units COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH CONSTANT MINIMUM COLD DECK AIRFLOW CONTROL PACKAGE NO 4170 Du...

Page 18: ...air system The venti lation air is conditioned heated cooled dehumidified as required to provide a neutral temperature The ventilation air is connected to the hot deck inlet of the terminal The contr...

Page 19: ......

Page 20: ...tinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53350001 01 Printed in U S A Form 35L N 1SI Pg 20 3 06 Replaces 35L M N 1SI Book 3...

Reviews: