background image

13

3. Connect the sensor cable as follows:

a. Connect one wire from the cable (RED) to the SPT

terminal on the controller. Connect the other end of
the wire to the left terminal on the SEN terminal
block of the sensor.

b. Connect another wire from the cable (BLACK) to

the ground terminal on the controller. Connect the
other end of the wire to the remaining open termi-
nal on the SEN terminal block.

c. For T56 sensors, connect the remaining wire

(WHITE/CLR) to the T56 terminal on the control-
ler. Connect the other end of the wire to the right
most terminal on the SET terminal block.

d. In the control box, connect the cable shield to

J1-3, equipment ground.

e. Install a jumper between the two center T56 termi-

nals (right SEN and left SET).

WIRING THE CCN NETWORK COMMUNICATION
SERVICE JACK — To wire the service jack, perform the
following:

1. Strip back the jacket from the CCN communication ca-

ble(s) for at least 3 inches. Strip

1

/

4

in. of insulation from

each conductor. Remove the shield and separate the drain
wire from the cable. Twist together all the shield drain
wires and fasten them together using an closed end crimp
lug or a wire nut. Tape off any exposed bare wire to pre-
vent shorting.

2. Connect the CCN + signal wire(s) (RED) to Terminal 5.
3. Connect the CCN – signal wire(s) (BLACK) to Terminal 2.
4. Connect the CCN GND signal wire(s) (WHITE/CLR) to

Terminal 4.

PRIMARY AIR TEMPERATURE SENSOR INSTALLA-
TION — A primary air temperature (PAT) sensor is used on a
zone controller which is functioning as a Linkage Coordinator
for a non-CCN (Carrier Comfort Network®)/Linkage compati-
ble air source. The part number is 33ZCSENPAT. See Fig. 17.
The sensor is also available as field-supplied accessory.

When used on a zone controller, try to select a zone control-

ler which will allow installation of the PAT sensor in the main
trunk, as close to the air source as possible. See Fig. 18.

To mount the PAT sensor, remove sensor cover.

1. Drill a

1

/

2

-in. hole in supply duct.

2. Using field-supplied drill tap screw, secure sensor to duct.
3. Connect sensor to zone controller using field-supplied

2-conductor cable. Refer to Table 9.

4. Use field-supplied wire nuts to connect cable to sensor.
5. At zone controller, connect sensor wires to PAT and GND

terminals.

INDOOR-AIR QUALITY SENSOR INSTALLATION —
The indoor-air quality (IAQ) sensor accessory monitors carbon
dioxide levels. This information is used to increase the airflow
to the zone and may also modify the position of the outdoor-air
dampers to admit more outdoor air as required to provide the
desired ventilation rate. The wall sensor is used to monitor the
conditioned space. The sensor uses infrared technology to
measure the levels of CO

2

present in the air. The wall sensor is

available with or without an LCD readout to display the CO

2

level in ppm and is also available in a combination model
which senses both temperature and CO

2

level.

The CO

2

sensors are factory set for a range of 0 to

2000 ppm and a linear voltage output of 0 to 10 vdc. Refer to
the instructions supplied with the CO

2

sensor for electrical re-

quirements and terminal locations. The sensor requires a sepa-
rate field-supplied 24 vac 25 va transformer to provide power
to the sensor. The transformer may be mounted in the control
box if space is provided (except electric heat units).

For factory configuration changes to some models of the

sensor, the User Interface Program (UIP) or Sensor Calibration
Service Kit is required.

To accurately monitor the quality of the air in the condi-

tioned air space, locate the sensor near the return air grille so it
senses the concentration of CO

2

leaving the space. The sensor

should be mounted in a location to avoid direct breath contact.

Do not mount the space sensor in drafty areas such as near

supply diffusers, open window, fans, or over heat sources. Al-
low at least 3 ft between the sensor and any corner. Avoid
mounting the sensor where it is influenced by the supply air;
the sensor gives inaccurate readings if the supply air is blown
directly onto the sensor.

To mount the sensor, refer to the installation instructions

shipped with the accessory kit.
INDOOR AIR QUALITY SENSOR WIRING — To wire the
sensor after it is mounted in the conditioned air space, see
Fig. 19-21 and the instructions shipped with the sensor. Use

Fig. 17 — Primary Air Temperature Sensor

(Part Number 33ZCSENPAT)

Fig. 18 — Primary Air Temperature

Sensor Installation

(Air-Handling Unit Discharge Locations)

Summary of Contents for 35L Series

Page 1: ...EMPERATURE SENSOR AND SET POINT ADJUSTMENT SLIDEBAR WIRING THE CCN NETWORK COMMUNICATION SERVICE JACK PRIMARY AIR TEMPERATURE SENSOR INSTALLATION INDOOR AIR QUALITY SENSOR INSTALLATION INDOOR AIR QUAL...

Page 2: ...llowing conditions 1 Unit casing is 22 gage 2 Unit insulation is 1 2 in thick 1 5 lb Tuf Skin Rx dual density fiberglass 3 Units rated with standard linear flow sensor Warranty All Carrier furnished i...

Page 3: ...controller DA NO cold inlet NO hot inlet 1503 Multi function controller DA NO cold inlet NC hot inlet 1504 Multi function controller RA NC cold inlet NC hot inlet 1505 Multi function controller RA NC...

Page 4: ...rop Ps of the desired configuration INLET SIZE in CFM MINIMUM AIRFLOW CFM MINIMUM CCN AIRFLOW CFM MINIMUM INLET STATIC PRESSURE Unit Pressure Drop in wg MINIMUM SYSTEM OPERATING PRESSURE in wg AT MAXI...

Page 5: ...ic Pressure drop Ps of the desired configuration Table 5 35N Dual Duct Full Blending Discharge Sensor Pickup CCN Carrier Comfort Network INLET SIZE Area CFM MINIMUM AIRFLOW CFM MINIMUM CCN AIRFLOW CFM...

Page 6: ...l terminals at system start up System calibration is accomplished by calculating a flow coefficient that adjusts the pressure fpm characteristics The flow coefficient is determined by dividing the flo...

Page 7: ...ields an airflow of 275 cfm Volume controller for units is shown in Fig 5 Balancing Procedure Control Sequences 1500 1523 1 Damper action is factory set at NO normally open or NC normally closed To re...

Page 8: ...t start point to the controller s internal reset start point of 0 psig RESET SPAN setting is factory set at 5 0 psig This is the required change in thermostat pressure that the controller will reset b...

Page 9: ...a 1 6 in hex key wrench turn the setscrews clockwise until cover is loose 3 Check voltages Verify 16 vdc between and terminals Applications for Dual Duct Minimum Air From Cold Duct Dual duct applicati...

Page 10: ...e found inside the control box SUPPLY AIR TEMPERATURE SAT SENSOR INSTAL LATION On terminals with heat the SAT sensor is provid ed The sensor is factory wired to the controlled and shipped in the contr...

Page 11: ...secure the sensor to the electrical box 6 Use 20 gage wire to connect the sensor to the controller This size is suitable for distances of up to 500 ft Use a three conductor shielded cable for the sen...

Page 12: ...nches Fig 14 Space Temperature Sensor and Wall Mounted Humidity Sensor Mounting 2 3 4 5 6 1 SW1 SEN BLK GND RED SPT RED WHT GND BLK CCN COM SENSOR WIRING Fig 15 Space Temperature Sensor Wiring 33ZCT55...

Page 13: ...supplied wire nuts to connect cable to sensor 5 At zone controller connect sensor wires to PAT and GND terminals INDOOR AIR QUALITY SENSOR INSTALLATION The indoor air quality IAQ sensor accessory mon...

Page 14: ...fty areas such as near heat ing or air conditioning ducts open windows fans or over heat sources such as baseboard heaters radiators or wall mounted light dimmers Sensors mounted in those areas will p...

Page 15: ...lation section for sensor wiring instructions COMMUNICATION BUS WIRE SPECIFICATIONS The Carrier Comfort Network CCN Communication Bus wiring is field supplied and field installed It consists of shield...

Page 16: ...all dampers to control to the minimum cooling cfm and verify that the static pressure is below the maximum safe operating limits when the damper is providing minimum cooling airflow 5 Set air source s...

Page 17: ...ow to the space A typical application is shown in Fig 24 Use package no 4160 with 35L N units COMFORTID VARIABLE AIR VOLUME DUAL DUCT WITH CONSTANT MINIMUM COLD DECK AIRFLOW CONTROL PACKAGE NO 4170 Du...

Page 18: ...air system The venti lation air is conditioned heated cooled dehumidified as required to provide a neutral temperature The ventilation air is connected to the hot deck inlet of the terminal The contr...

Page 19: ......

Page 20: ...tinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53350001 01 Printed in U S A Form 35L N 1SI Pg 20 3 06 Replaces 35L M N 1SI Book 3...

Reviews: