Table 1 — TEMP System Thermostat Categories and Options (cont)
OPTION
DESCRIPTION
DEFAULT
MINIMUM
MAXIMUM
5.10
Fan Status Switch
OFF
OFF
ON
5.11
Humidity Sensor/Filter Status (0 — No Sensor, 1 — Indoor Humidity
Sensor, 2 — Filter Status Switch)
0
0
2
5.12
Humidity Sensor Calibration
Indoor Humidity
0
100
CATEGORY 6.0 SUPPLEMENTAL HEAT
No configuration needed.
CATEGORY 7.0 DIAGNOSTICS/METERING
7.1
Error Code Display
OFF
OFF
ON
7.2
Communication Check
OFF
OFF
ON
7.3
Alternate Information
OFF
OFF
ON
7.4
Comfort Trend Demand (1/10° F)
0
0
25.5
7.5
Comfort Trend Time Limit (Minute)
2
2
255
7.6
HVAC Usage Meter
OFF
OFF
ON
7.7
Override Usage Meter
OFF
OFF
ON
7.8
HVAC Override Usage Meter
OFF
OFF
ON
7.9
Heating Mode Error Set Point (F)
0
0
140
7.10
Cooling Mode Error Set point (F)
140
0
140
7.11
Unit Reset
OFF
OFF
ON
CATEGORY 8.0 START-UP
8.1
Device Element Address
0
0
239
8.2
Security Level (1 — All Programming Allowed, 2 — Programming of
Occupancy Schedules and Set Points Only, 3 — Programming of
Set Points Only, 4 — No Programming Allowed)
1
1
4
8.3
Device Bus Number
0
0
239
CATEGORY 9.0 BROADCAST/DAYLIGHT SAVINGS TIME
9.1
Broadcast Acknowledger
OFF
OFF
ON
9.2
Global Schedule Broadcast
OFF
OFF
ON
9.3
Network Time Request
OFF
OFF
ON
9.4
Receive Network Time
ON
OFF
ON
9.5
Network Time Broadcast
OFF
OFF
ON
9.6
Daylight Savings Time Start Month
4
1
12
9.7
Daylight Savings Time Start Week
1
1
5
9.8
Daylight Savings Time Start Day
7
1
7
9.9
Daylight Savings Time Added Minutes
60
0
90
9.10
Daylight Savings Time Stop Month
10
1
12
9.11
Daylight Savings Time Stop Week
5
1
5
9.12
Daylight Savings Time Stop Day
7
1
7
9.13
Daylight Savings Time Subtracted Minutes
60
0
90
CATEGORY 10.0 HOLIDAY SCHEDULES
10.1-10.18
Holiday Schedule 1-18
Holiday Start Month
Start Day
Duration (Days)
0
0
0
0
0
0
12
31
99
CATEGORY 11.0 ALARM
11.1
Equipment Priority
7
0
7
11.2
Communication Failure Retry Time (Minutes)
10
1
240
11.3
Re-Alarm Time (Minutes)
30
1
255
CATEGORY 12.0 OPTIMAL START
12.1
Optimal Start Time Limit (Hrs)
4
0
4
CATEGORY 13.0 LOADSHED
13.1
Demand Limit Group Number
0
0
16
CATEGORY 14.0 INDOOR-AIR QUALITY (IAQ)
14.1
System Indoor Air Quality Sensor
OFF
OFF
ON
14.2
Indoor-Air Quality Economizer Delay (Minutes)
10
5
30
14.3
Indoor-Air Quality Maximum Space Temperature Reset (F)
2
0
10
14.4
Indoor-Air Quality Humidity Lockout Set Point
0
0
100
14.5
Indoor-Air Quality Low Temperature Lockout (F) (OAT)
45
0
110
14.6
Indoor-Air Quality High Temperature Lockout (F) (OAT)
80
0
110
14.7
Indoor-Air Quality Alarm Delay (Minutes)
0
0
240