firing rate as shown on rating plate by clocking the gas meter.

S

Over firing/high BTU input: Set manifold pressure and verify
firing rate as shown on rating plate by clocking the gas meter.

S

Low temperature rise: Set unit for correct temperature rise range
as shown on unit rating plate.

S

Contaminated combustion air: Remove contaminates or provide
ample fresh air for combustion.

S

Excessive amounts of outside ventilation air: Return air
temperature cannot be below 60 degrees F for extended periods
of time.

S

Incorrect venting or termination: Recirculation of products of

combustion into the combustion air pipe can damage the
furnace. Verify proper venting and vent termination per
installation instructions. For additional information, and a
complete sequence of furnace operation, refer to furnace
Installation, Start-Up and Operating Instructions.

16. After System Check-out is complete, set thermostat below

room temperature.

17. Verify that burner shuts down and blower completes

selected off delay time.

18. Verify furnace operates properly and set thermostat to

desired room temperature.

19. Re-install outer door.