1 - INTRODUCTION

Prior to the initial start-up of the 30RQS/30RQSY units, the 
people involved should be thoroughly familiar with these 
instructions and the specific project data for the installation site.

The 30RQS/30RQSY heat pumps are designed to provide a 
very high level of safety and reliability making installation, 
start-up, operation and maintenance easier and more secure. 
They will provide safe and reliable service when operated 
within their application range.

They are designed for an operating life of 15 years by 
assuming a 75% utilisation factor; that is approximately 
100,000 operating hours.

The procedures in this manual are arranged in the sequence 
required for machine installation, start-up, operation and 
maintenance.
Be sure you understand and follow the procedures and safety 
precautions contained in the instructions supplied with the 
machine, as well as those listed in this guide, such as: 
protective clothing such as gloves, safety glasses, safety shoes 
and appropriate tools, and suitable qualifications (electrical, 
air conditioning, local legislation).

To find out, if these products comply with European directives 
(machine safety, low voltage, electromagnetic compatibility, 
equipment under pressure, etc.) check the declarations of 
conformity for these products.

1.1 -  Specific aspects for 30RQSY units with variable 

available pressure 

30RQSY units are designed for indoor installation in a plant 
room. For this type of installation cold or hot air leaving the 
air-cooled air heat exchangers is discharged by the fans to 
the outside of the building, using a duct system.

The suction air return can be outside or inside the room (see 
chapter 3.2 - “Duct connection”).

The installation of a duct system at the air heat exchanger 
discharge line and in certain cases at the heat exchanger air 
suction side causes a pressure drop due to the resistance 
caused by the air flow.

Therefore more powerful fan motors than those used for the 
30RQS units are installed in the units of this range. For each 
installation of a unit installed inside a plant room the duct 
pressure drops differ, depending on the duct length, duct 
section and direction changes.

30RQSY units equipped with fans with available pressure 
are designed to operate with air discharge ducts with maximum 
pressure drops of 160 Pa.

To compensate for these pressure drops 30RQSY units are 
equipped with variable-speed fans with a maximum speed of 
19 r/s to ensure an optimised air flow rate.

In the cooling mode, the full-load or part-load speed is 
controlled by a patented algorithm that permanently 
optimises the condensing temperature to ensure the best unit 
energy efficiency (EER) whatever the operating conditions 

and pressure drops of the system ductwork.

In the heating mode, the full-load or part-load speed of each 
circuit is fixed and at the configured maximum (range 
configurable from 12 r/s to 19 r/s) based on the constraints 
and characteristics of the installation site. The maximum 
configured speed applies to both the heating and cooling 
mode.

If required and for reasons that may apply at the installation 
site of the 30RQSY units a maximum fan speed can be set. 
To do this consult the 30RB/RQ Touch Pilot Junior control 
manual.

1.2 - Check equipment received

• 

Inspect the unit for damage or missing parts. If damage 
is detected, or if shipment is incomplete, immediately 
file a claim with the shipping company.

• 

Confirm  that  the  unit  received  is  the  one  ordered. 
Compare the name plate data with the order.

• 

The name plate is attached to the unit in two locations: 

 

on the outside on one of the unit sides

 

-  on the control box door on the inside.

• 

The  unit  name  plate  must  include  the  following 
information:

 

Model number - size

 

CE marking

 

Serial number 

 

Year  of  manufacture  and  pressure  and  leak 
tightness test date

 

Refrigerant used

 

Refrigerant charge per circuit

 

PS:  Min./max.  allowable  pressure  (high  and  low 
pressure side)

 

TS: Min./max. allowable temperature (high and low 
pressure side)

 

Pressure switch cut-out pressure

 

Unit leak test pressure

 

Voltage, frequency, number of phases

 

Maximum current drawn

 

Maximum power input

 

Unit net weight

• 

Confirm that all options ordered for on-site installation 
have been delivered, and are complete and undamaged.

The unit must be checked periodically, if necessary removing 
the insulation (thermal, acoustic), during its whole operating 
life to ensure that no shocks (handling accessories, tools, 
etc.) have damaged it. If necessary, the damaged parts must 
be repaired or replaced. See also chapter “Maintenance”.

1.3 - Installation safety considerations

After the unit has been received, and before it is started up, it 
must be inspected for damage. Check that the refrigerant 
circuits are intact, especially that no components or pipes have 
shifted or been damaged (e.g. following a shock). If in doubt, 
carry out a leak tightness check. If damage is detected upon 
receipt, immediately file a claim with the shipping company.

Summary of Contents for 30RQS039

Page 1: ...I O N S Reversible Air to Water Heat Pumps 30RQS 30RQSY 039 160 A Original instructions Nominal cooling capacity 40 160 kW 50 Hz Touch Pilot Junior For the operation of the control please refer to th...

Page 2: ...without filter frame 16 4 6 30RQSY 050 078 option 23B units with and without hydronic module with filter frame 17 4 7 30RQSY 080 120 units with and without hydronic module 18 4 8 30RQSY 140 160 units...

Page 3: ...ressors 43 15 2 Lubricant 43 15 3 Air evaporator condenser 43 15 4 Fans 43 15 5 Electronic expansion valve EXV 43 15 6 Moisture indicator 43 15 7 Filter drier 43 15 8 Water evaporator condenser 44 15...

Page 4: ...are equipped with variable speed fans with a maximum speed of 19 r s to ensure an optimised air flow rate In the cooling mode the full load or part load speed is controlled by a patented algorithm th...

Page 5: ...nd national usage monitoring regulations in the European Uniontheprotectiondevicesforthesemachinesareclassified as follows Safety accessory Damage limitation accessory in case of an external fire Refr...

Page 6: ...OPERATING CHECKS Important information regarding the refrigerant used Thisproductcontainsfluorinatedgreenhousegascoveredbythe Kyoto protocol Fluid type R410A GlobalWarming Potential GWP 2088 Relief v...

Page 7: ...ify and and record the set points of pressure switchesandreliefdevices valvesandpossiblerupture discs Be ready to switch off the main disconnect switch of thepowersupplyifthepressureswitchdoesnottrigg...

Page 8: ...itionanysafetydeviceswhen corrosion or build up of foreign material rust dirt scale etc is found within the valve body or mechanism If necessary replace the device Do not install relief valves in seri...

Page 9: ...tening measures have been taken if the unit has to operate as a heat pump in temperatures below 0 C it must be raised at least 300 mm from the ground Thisisnecessarytoavoidicebuild up on the unit chas...

Page 10: ...air heat exchanger is on two unit sides It is therefore necessary to install two additional brackets to allow connection of the heat exchanger suction duct These parts are inside the machine and fixe...

Page 11: ...ducts The fan protection grilles can be removed to increase the available pressure At the beginning of each duct provide an access hatch with minimum dimensions of 700 x 700 mm to allow motor replace...

Page 12: ...location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side clearan...

Page 13: ...entre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side clearance between the units should be increased from 1000 to 2000 mm C The hei...

Page 14: ...gs B Provide a gutter around the unit to collect the condensate water or install the accessory condensate collection pan 30RQSY 039 to 078 C The unit must be installed level less than 2 mm per metre d...

Page 15: ...pplied with the unit or available onrequest whendesigninganinstallation Forthelocationoffixingpoints weight distributionandcoordinatesofthecentreofgravityrefertothecertifieddimensional drawings B Prov...

Page 16: ...ith the unit or available on request when designing an installation For the location of fixing points weight distributionandcoordinatesofthecentreofgravityrefertothecertifieddimensional drawings B Pro...

Page 17: ...awings B Provide a gutter around the unit to collect the condensate water or install the accessory condensate collection pan 30RQSY 039 to 080 C The unit must be installed level less than 2 mm per met...

Page 18: ...mended clearances for maintenance Air outlet do not obstruct Power cable entry NOTES A Non certified drawings Refer to the certified dimensional drawings supplied with the unit or available on request...

Page 19: ...ecommended clearances for maintenance Air outlet do not obstruct Power cable entry NOTES A Non certified drawings Refer to the certified dimensional drawings supplied with the unit or available on req...

Page 20: ...fixing points weight distributionandcoordinatesofthecentreofgravityrefertothecertifieddimensional drawings B The unit must be installed level less than 2 mm per metre deviation in both axes Overall d...

Page 21: ...location of fixing points weight distributionandcoordinatesofthecentreofgravityrefertothecertifieddimensional drawings B The unit must be installed level less than 2 mm per metre deviation in both axe...

Page 22: ...lets and outlets 4 13 30RQS RQSY 140 160 units with desuperheater Position of the desuperheater inlets and outlets Unit water inlet and outlet Water inlet and outlet unit with option 49 4 11 30QBS RQS...

Page 23: ...Maximum total air flow l s 3692 3690 3910 5285 5284 5282 7770 7380 7376 7818 10568 10568 Maximum rotation speed r s 12 12 12 16 16 16 12 12 12 12 16 16 Water heat exchanger Direct expansion plate hea...

Page 24: ...draw A 26 29 33 36 42 53 53 55 62 77 85 106 Maximum unit current draw Un A 35 45 47 53 67 73 74 81 99 108 134 146 Maximum unit current draw Un 10 A 38 49 51 58 75 80 80 89 110 118 150 159 Customer sid...

Page 25: ...with rotating shroud Quantity 1 1 1 1 1 1 2 2 2 2 2 2 Maximum total air flow l s 3692 3690 3910 5278 4982 5267 7770 7380 7376 7818 9964 10534 Maximum speed r s 16 16 16 18 18 18 16 16 16 16 18 18 Wat...

Page 26: ...ximum unit current draw Un A 37 47 49 55 67 73 79 86 104 113 135 147 Maximum unit current draw Un 10 A 41 52 54 61 75 80 85 94 116 123 150 160 Customer side unit power reserve kW Customer reserve at t...

Page 27: ...ear of manufacture This information varies depending on the manufacturer and model at the time of incorporation Please refer to the motor name plates 4 Manufacturer s name and trademark commercial reg...

Page 28: ...ecifically designed I Altitudes above sea level m 1000 II Ambient air temperature C 55 IV Maximum air temperature C Please refer to the operating conditions given in this manual or in the specific con...

Page 29: ...power supply status and then prevent evaporator from frosting when heaters and boards are off NOTES Generally the recommendations of IEC 60364 are accepted as compliance with the requirements of the...

Page 30: ...en into account 250 litres Bad Good Bad Good 10 6 2 Maximum water loop volume Units with hydronic module incorporate an expansion tank that limits the water loop volume The table below gives the maxim...

Page 31: ...35 305 PVC Cu 070 1 x 95 1 x 95 1 x 35 220 XLPE Cu 1 x 50 350 PVC Cu 078 1 x 95 1 x 95 1 x 35 220 XLPE Cu 1 x 70 380 PVC Cu 080 1 x 95 1 x 95 1 x 35 220 XLPE Cu 1 x 70 380 PVC Cu 090 1 x 95 1 x 95 1 x...

Page 32: ...ce dure must be chemically neutral in relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier ATTENTION Use of units in a...

Page 33: ...your area you must do the following when switching the unit off in winter Addethyleneglycolorpropyleneglycolwithanadequate concentration to protect the installation up to a temperature of 10 K below t...

Page 34: ...rleavingpressureinformation seeregulationmanual 11 Check valve If dual pump 12 Plate heat exchanger 13 Heater or tracer for frost protection Option 14 Flow sensor for water heat exchange 15 Buffer tan...

Page 35: ...ic module sizes 039 078 Dual pump shown Hydronic module sizes 080 160 Dual pump shown Hydronic module sizes 039 080 Dual pump and buffer tank shown Hydronic module sizes 090 160 Dual pump and buffer t...

Page 36: ...for cleaning the hydronic circuit Open the valve completely item 22 Start up the system pump Read the pressure drop of the plate heat exchanger as thedifferencebetweentheunitinletandoutletpressures i...

Page 37: ...s measured an decreased flow rate if a higher value than the set point is measured This flow rate variation is realised observing the minimum and maximum admissible unit flow rates as well as the mini...

Page 38: ...t is measured the flow rate is increased If a lower delta T value than the set point is measured the flow rate is decreased This flow rate variation is realised observing the minimum and maximum admis...

Page 39: ...low rate l s Water flow rate l s Water flow rate l s Water flow rate l s Legend 1 30RQS 30RQSY 039 2 30RQS 30RQSY 045 3 30RQS 30RQSY 050 4 30RQS 30RQSY 060 5 30RQS 30RQSY 070 6 30RQS 30RQSY 078 Legend...

Page 40: ...0RQSY 039 2 30RQS 30RQSY 045 3 30RQS 30RQSY 050 4 30RQS 30RQSY 060 5 30RQS 30RQSY 070 6 30RQS 30RQSY 078 Legend 1 30RQS 30RQSY 080 2 30RQS 30RQSY 090 3 30RQS 30RQSY 100 4 30RQS 30RQSY 120 5 30RQS 30RQ...

Page 41: ...3 Operation of two units in master slave mode The control of a master slave assembly is in the entering water and does not require any additional sensors standard configuration It can also be located...

Page 42: ...or air temperature This requires only a 400 V 3 ph 50 Hz power supply source as well as a connection to the unit via a communication bus For the required configuration of the stages consult the 30RB R...

Page 43: ...s moisture in the circuit The presence of bubbles in the sight glass indicates an insufficient charge or non condensables in the system The presence of moisture changes the colour of the indicator pap...

Page 44: ...utral in relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier SCS NOTES Monitoring during operation Follow the regulat...

Page 45: ...Easy and fast installation plug play 30RQS RQSY 039 160 HP variable speed single pump hydronic mod 116V Single high pressure water pump with variable speed drive VSD water filter electronic water flow...

Page 46: ...l configuration for the desuperheater option is factory assembled 18 1 Physical data 30RQS 30RQSY units with partial heat reclaim using desuperheaters option 49 30RQS RQSY partial heat reclaim mode 03...

Page 47: ...er 4 Air condenser coils 5 Expansion valve EXV 6 Damage limitation option in case of a fire relief valve 7 Electric heater to protect the desuperheater against frost not supplied 8 Desuperheater insul...

Page 48: ...temperature and to find the position of the connection block on the board refer to the 30RB RQTouch Pilot Junior control manual Other parameters directly affecting the effective capacity reclaimed at...

Page 49: ...r the pump every 40 000 hours for applications with water every 15 000 hours for applications with glycol concentrations above 30 To facilitate maintenance operations it is recommended to installshut...

Page 50: ...s with a low pressure jet and a bio degradable cleaner Checktheunitoperatingparametersandcomparethem with previous values Carry out an oil contamination test Replace the oil if necessary Check and if...

Page 51: ...et metal plates 4 2 H M6 screw Stauff clamps 10 Earth screw Compressor 2 8 BPHE Brazed plate heat exchanger 20 6 Air heat exchanger We recommend that finned coils are inspected regularly to check the...

Page 52: ...e pressure Saturat temp Relative pressure 20 297 4 807 28 1687 52 3088 19 312 5 835 29 1734 53 3161 18 328 6 864 30 1781 54 3234 17 345 7 894 31 1830 55 3310 16 361 8 924 32 1880 56 3386 15 379 9 956...