Installations and user manual 

SL/SLS-DC1

SL/SLS-R1

Original instructions

.

... 2

GB  

.

... 52

NO 

.

... 83

FR  

.

... 27

SE 

Summary of Contents for SL/SLS-DC1

Page 1: ...Installations and user manual SL SLS DC1 SL SLS R1 Original instructions 2 GB 52 NO 83 FR 27 SE ...

Page 2: ... Generic danger Signals to the personnel that the operation described could cause physical injury if not performed according to the safety rules Danger of high voltage Signals to the personnel that the operation described could cause electrocution if not performed according to the safety rules Danger due to heat Signals to the personnel that the operation described could cause burns if not perform...

Page 3: ...nting air temperature probe 15 Wiring diagram 16 Installation of control for remote operation B10642 model R1 Mounting and connecting the fan control for remote adjustment B10642 17 Mounting 17 LED signals 17 Diagram for B10642 connections with 0 10 V DC thermostats signals 18 B10642 connection with 0 10 V thermostats 18 Troubleshooting Troubleshooting 19 Table of anomalies and remedies 19 User in...

Page 4: ... change of air This instruction leaflet is an integral part of the appliance and consequently must be kept carefully and must ALWAYS accompany the appliance even when it is passed to a new owner or user or transferred onto another system All repair or maintenance interventions must be performed by the technical service department or by professionally qualified personnel as foreseen in this booklet...

Page 5: ...um water inlet temperature C 80 80 80 80 80 Minimum inlet water temperature C 4 4 4 4 4 Hydraulic fixtures Eurokonus 3 4 Eurokonus 3 4 Eurokonus 3 4 Eurokonus 3 4 Eurokonus 3 4 Power supply V ph Hz 230 1 50 230 1 50 230 1 50 230 1 50 230 1 50 Maximum current absorbed A 0 11 0 16 0 18 0 26 0 28 Maximum power absorbed W 11 9 17 6 19 8 26 5 29 7 Weight SL kg 17 20 23 26 29 Weight SLS kg 12 14 16 19 2...

Page 6: ...U M SL SLS 200 SL SLS 400 SL SLS 600 SL SLS 800 SL SLS 1000 A mm 735 935 1135 1335 1535 659 579 A 129 129 459 379 A SL SLS GB 6 2 pipes Dimensions Overall dimensions ...

Page 7: ...w is not directed towards persons The following descriptions of the various mounting phase and the relative designs refer to a version of the machine with fixtures on the left The operations for the mounting of machines with fixtures on the right are exactly the same Only the images are to be considered as a mirror image To ensure that the installation is performed correctly and that the appliance...

Page 8: ...g of the feet Using the paper template trace the position of the two fixing brackets on the wall Use a suitable drill to make the holes with and insert the toggle bolts 2 for each bracket fix the two brackets Do not over tighten the screws so that the brackets can be adjusted with a spirit level Fully tighten the four screws to block the two brackets Check the stability by manually moving the brac...

Page 9: ... check the inclination of the exhaust pipe Any counterslope of the discharge line can cause water leakage In the case in which the cooler convector is installed in a horizontal position to guarantee the safety of the cleaning filter replacement operations it is obligatory that the two clamps in the supplied bag together with the instruction manual and the accessories are mounted by the installer I...

Page 10: ...ne If possible make the condensation liquid flow directly in a gutter or a rainwater discharge When discharging directly into the main drains it is advisable to make a siphon to prevent bad smells returning up the pipe towards the room The curve of the siphon must be lower than the condensation collection bowl If the condensation needs to be discharged into a container it must be open to the atmos...

Page 11: ...me collection bowl insulate the bowl condensation discharge pipe along all of its length Venting of the battery When starting up the system make sure that the hydraulic unit lockshield is open If there is no electric power and the thermo valve has already been powered use the special cap to press the valve stopper to open it Open all the system interception devices manual or automatic Start the fi...

Page 12: ...r is switched off The unit must be connected to the mains through a multipolar switch with minimum contact opening of at least 3mm or with a dewice that allows the complete disconnection from the device under the overvoltage conditions category III Electrical connections Mounting of valve kits The convector must be mounted with Frico valve kits for SL SLS see separate manuals For SL valve kit V206...

Page 13: ...fix the earth wire to the cooler convector ref M structure using the supplied screws the minimum force of about 2N must be used when screwing up connect the rapid connector on the motor MOTOR to that on the board ref I For the other versions remove the jumper and connect the two terminals from the grid safety microswitch connect the water probe to the H2 connector on the machine The water temperat...

Page 14: ... enabled only in cooling the continuous ventilation at the minimum speed even after the set point has been reached to ensure a more regular functioning of the temperature probe and to prevent air stratification Setting the cursor on OFF the function is cycled 2 minutes ON 10 minutes OFF When the contact connected to the CP ref A input is closed all the users connected will be switched off If the c...

Page 15: ...B 15 To position the temperature probe ref A pass the probe through the hole on the shoulder ref B insert the probe in the lower hole ref C fix the probe in the special hook ref D Mounting air temperature probe ...

Page 16: ...rical power supply connection BO boiler go ahead output free contact max 1A CH chiller go ahead output free contact max 1A CP presence sensor input if closed the fan coil goes into stand by HRS RS water probe 2kΩ only for ECA644 versions RS RS version wiring only for ECA644 If after powering the equipment the board detects the probe the start up will take place under normal conditions with minimum...

Page 17: ...er radiator structure using the supplied screws the minimum force of about 2N must be used when screwing up the 2 terminals of the GRID clamp ref I feature a jumper that ensures the operation of the SLI and RSI versions without microswitch For the other versions remove the jumper and connect the two terminals from the grid safety microswitch connect the rapid connector on the motor MOTOR to that o...

Page 18: ...The speed ramp provides a linear adjustment from the minimum value 400rpm to the maximum value 1400rpm for voltage values 1 1V 10 V DC The motor is off with values below 1 V DC The Y1 valve is enabled by voltage 1 V DC and turns off when the same falls below 0 9 V DC L N 230V 50 Hz electric power supply 10V device pilot input 0 10 V Y1 hot water solenoid valve 230V 50Hz 1A powered output Y2 output...

Page 19: ...he micro switch that stops the ventilation when the filter grill is opened does not close correctly Check that by closing the grill the micro switch contact is activated The electrical connections are not correct Check the electrical connections The appliance leaks water during the heating function Leaks in the hydraulic connections of the system Check the leak and fully tighten the connections Le...

Page 20: ...t keys The display also offers information on the statuses and on any active alarms through 8 specific symbols Automatic operation Silent operation Maximum ventilation speed Night function Heating on Cooling on Supervision on Flashing with CP presence contact closed Alarm indication light on Temp allows to increase set temperature Temp allows to decrease set temperature Heating Cooling allows swit...

Page 21: ...ol is very precise set it to the desired value and wait for it to run the adjustment based on the actually detected room temperature To activate the device key Operation Display Press the ON stand by key From off to on Select one of the 4 operation modes by pressing the relative key key Operation Display Press the Heating Cooling key for about 2 seconds to switch between heating and cooling operat...

Page 22: ...ed by the relative symbol appearing on the display key Operation Display Hold the Night function key The function activation will be signalled by the relative symbol on the display key Operation Display Hold the Max Operation key The function activation will be signalled by the relative symbol on the display key Operation Display Press both keys and at the same time for 3 seconds to activate the l...

Page 23: ...s proceed as follows Disable the device Set the main system switch to Off The anti freeze function is not active Long term shut down Error signals In some cases the detected values might not represent the real temperature due to the fact that the temperature probe is located in the lower section of the device Use this function to adjust the measured value shown on the display within a range of 10 ...

Page 24: ...t use abrasive sponges or abrasive or corrosive detergents to avoid damaging the painted surfaces When necessary clean the outer surfaces of the cooler convector with a soft cloth damp cloth extract the front grill by lifting it slightly and turn it until it comes right out of its seat extract the filter pulling it horizontally outwards Extraction of filter cells in the versions with aspiration gr...

Page 25: ... appliance is fitted with a safety switch that prevents the operation of the cooler with the mobile panel missing or out of position After finishing the cleaning of the filter check that the panel is mounted correctly Cleaning filtering seats filter lower edge The filter housing Insert your hands under the end of mobile panel Press the plastic lug Lift and extract the mobile panel Extract the filt...

Page 26: ...erations tabs slots Always keep the filters clean when far possible keep the doors and windows closed in the room being conditioned limit where possible the effect of direct sun rays in the rooms being conditioned use curtains shutters etc For the versions with a mobile panel rest it in its position parallel to the front panel and press until it is blocked Energy saving tips ...

Page 27: ...LS800 945 137 149 75 7 88 2 33 9 223 7 243 1014 45 214 5 SLS1000 1145 137 149 75 7 88 2 33 9 223 7 243 1214 45 214 5 SL200 345 319 8 149 79 7 240 8 42 5 230 447 414 45 214 5 SL400 545 319 8 149 79 7 240 8 42 5 230 447 614 45 214 5 SL600 745 319 8 149 79 7 240 8 42 5 230 447 814 45 214 5 SL800 945 319 8 149 79 7 240 8 42 5 230 447 1014 45 214 5 SL1000 1145 319 8 149 79 7 240 8 42 5 230 447 1214 45 ...

Page 28: ...e Frico AB Tel 46 31 336 86 00 Industrivägen 41 SE 433 61 Sävedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico se 2021 06 15 HH SÄ CH ...