13
4.2 - 30RQS 080-160, units with and without hydronic module
For units with fans with variable available pressure (30RQSY) please refer to the pages that follow.
NOTES:
A Non-certified drawings.
Refer to the certified dimensional drawings supplied with the unit or available on
request, when designing an installation.
For the location of fixing points, weight distribution and coordinates of the centre
of gravity refer to the certified dimensional drawings.
B In multiple-unit installations (maximum four units), the side clearance between
the units should be increased from 1000 to 2000 mm.
C The height of the solid surface must not exceed 2 m.
Legend:
All dimensions are given in mm
Control box
Water inlet
Water outlet
Required clearances for air flow
Recommended clearances for maintenance
Air outlet, do not obstruct
Power cable entry
Multiple unit installation
Solid wall
Solid wall
-A-
1
1
1
2136
1321
1000
1000
1000
1000
300
2
2
NOTE: If the walls are higher than 2 m, contact the factory