40
17 - SpECIfIC DETaIlS fOR UNITS WITH a faN
WITH avaIlaBlE STaTIC pRESSURE (30RQSY)
Selection based on the pressure drop
The cooling and heating capacities are given for an
available pressure of 160 Pa and for a unit without filter.
To calculate the performances at other pressure drops
please use the correction factors below.
Cooling mode
30RQSY 039-050/30RQSY 080-120
Duct pressure
drop
fan speed, r/s
power input
coefficient
Cooling capacity
coefficient
0
12.00
0.943
1.019
50
13.33
0.962
1.012
100
14.66
0.980
1.006
130
15.46
0.990
1.003
160
16.26
1.000
1.000
200
17.31
1.012
0.998
240
18.36
1.023
0.996
30RQSY 060-078/30RQSY 140-160
Duct pressure
drop
fan speed, r/s
power input
coefficient
Cooling capacity
coefficient
0
15.83
0.929
1.018
50
16.81
0.944
1.016
100
17.78
0.964
1.014
130
18.36
0.978
1.011
160
18.36
1.000
1.000
180
18.36
1.019
0.991
Heating mode
30RQSY 039-050/30RQSY 080-120
Duct pressure
drop
fan speed, r/s
power input
coefficient
Heating capacity
coefficient
0
18.36
0.990
1.016
50
18.36
0.990
1.012
100
18.36
0.990
1.009
130
18.36
1.000
1.005
160
18.36
1.000
1.000
200
18.36
1.000
0.994
240
18.36
1.010
0.981
30RQSY 060-078/30RQSY 140-160
Duct pressure
drop
fan speed, r/s
power input
coefficient
Heating capacity
coefficient
0
18.36
1.000
1.026
50
18.36
1.000
1.020
100
18.36
1.000
1.011
130
18.36
1.000
1.007
160
18.36
1.000
1.000
180
18.36
1.001
0.993
Note:
Pressure drop, clean filter = 6 Pa
Pressure drop, dirty filter = 12 Pa
This option permits the production of free hot water using
heat reclaim by desuperheating the compressor discharge
gases. The option is available for the whole 30RQS/30RQSY
range.
18 – paRTIal HEaT REClaIM USING DESUpER-HEaTERS (OpTION 49)
A plate heat exchanger is installed in series with the air
condenser coils on the compressor discharge line of each
circuit.
The control configuration for the desuperheater option is
factory assembled.
18.1 - physical data, 30RQS/30RQSY units with partial heat reclaim using desuperheaters (option 49)
30RQS/RQSY partial heat reclaim mode
039
045
050
060
070
078
080
090
100
120
140
160
Operating weight 30RQS units with RTpf coils*
Standard unit without hydronic module
kg
515
522
548
561
562
569
762
909
917
973
1088
1106
Standard unit with hydronic module option
Single high-pressure pump
kg
544
552
578
591
591
599
792
941
949
1009
1127
1145
Dual high-pressure pump
kg
570
578
603
617
617
625
818
986
994
1057
1164
1155
Operating weight 30RQSY units with RTpf coils*
Standard unit without hydronic module
kg
530
537
568
582
582
589
776
944
953
1008
1118
1135
Standard unit with hydronic module option
Single high-pressure pump
kg
560
567
597
611
612
619
806
975
985
1044
1157
1174
Dual high-pressure pump
kg
586
593
623
637
638
645
832
1020
1030
1092
1194
1211
Refrigerant charge, units with RTpf coils
R410A
Circuit A
kg
12,5
13,5
16,5
17,5
18
16,5
21,5
27,5
28,5
33
19
18,5
Circuit B
kg
-
-
-
-
-
-
-
-
-
-
19
18,5
Condensers
Grooved copper tubes. aluminium fins
Desuperheaters on circuits a and B
Plate heat exchangers
Water volume
l
0,549 0,549 0,549 0,732 0,732 0,732 0,732 0,976 0,976 0,976 0,732 0,732
Water volume
l
-
-
-
-
-
-
-
-
-
-
0,732 0,732
Max. water-side operating pressure without hydronic
module
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Water connections
Cylindrical, male gas thread
Connections
in
1
1
1
1
1
1
1
1
1
1
1
1
Outside diameter
mm
42
42
42
42
42
42
42
42
42
42
42
42
* Weights shown are a guideline only.