49
Options
No. Description
Advantages
Use
DX Free-cooling system on
two circuits
118A Patented Carrier free-cooling system with cooling
micro-pump on both refrigerant circuits. Operation without
glycol, no extra free-cooling coil. See DX Free-cooling
option chapter
Energy savings for applications with cooling demand
throughout the entire year
30RBM/30RBP
220-520
DX Free-cooling system on
one circuit
118B Patented Carrier free-cooling system with cooling
micro-pump on one refrigerant circuit. Operation without
glycol, no extra free-cooling coil. See DX Free-cooling
option chapter
Energy savings for applications with reduced demand for
cooling in winter (e.g. offices with a computer room,
meeting rooms etc.)
30RBM/30RBP
160-520 Except
size 360/400 on
30RBP
Lon gateway
148D Two-directional communication board complying with Lon
Talk protocol
Connects the unit by communication bus to a building
management system
30RBM/30RBP
160-520
Bacnet over IP
149
Two-directional high-speed communication using BACnet
protocol over Ethernet network (IP)
Easy and high-speed connection by Ethernet line to a
building management system. Allows access to multiple
unit parameters
30RBM/30RBP
160-520
Modbus over IP and RS485 149B
Bi-directional high-speed communication using Modbus
protocol over Ethernet network (IP)
Easy and high-speed connection by ethernet line to a
building management system. Allows access to multiple
unit parameters
30RBM/30RBP
160-520
Energy Management
Module
156
EMM Control board with additional inputs/outputs. See
Energy Management Module option chapter
Extended remote control capabilities (Set-point reset, ice
storage end, demand limits, boiler on/off command...)
30RBM/30RBP
160-520
Input contact for Refrigerant
leak detection
159
0-10 V signal to report any refrigerant leakage in the unit
directly on the controlller (the leak detector itself must be
supplied by the customer)
Immediate customer notification of refrigerant losses to the
atmosphere, allowing timely corrective actions
30RBM/RBP
160-520
Compliance with Russian
regulations
199 EAC certification
Conformance with Russian regulations
30RBM/30RBP
160-520
Power factor correction
231 Capacitors for automatic correction of power factor (cos
phi) value to 0.95.
Reduction of the apparent electrical power input,
compliance with minimum power factor limit set by
electricity providers
30RBM/30RBP
160-520
Enviro-Shield anti-corrosion
protection
262
Coating by conversion process which modifies the surface
of the aluminium producing a coating that is integral to the
coil. Complete immersion in a bath to ensure 100%
coverage. No heat transfer variation, salt spray resistance
test for 4000 hours (ASTM B117)
Improved corrosion resistance, recommended for use in
moderately corrosive environments
30RBM/30RBP
160-520
Super Enviro-Shield
anti-corrosion protection
263
Extremely durable and flexible epoxy polymer coating
applied on micro channel heat exchangers by electro
coating process, final UV protective topcoat. Minimal heat
transfer variation, tested 6000 hours constant neutral salt
spray per ASTM B117, superior impact resistance per
ASTM D2794
Improved corrosion resistance, recommended for use in
extremely corrosive environments
30RBM/30RBP
160-520
Welded evaporator
connection kit
266 Victaulic piping connections with welded joints
Easy installation
30RBM/30RBP
160-520
Shell and tubes heat
exchanger
280 Brazed plate heat exchanger replaced by shell & tube heat
exchanger
Extension of the water flow rate range, improved resistance
to fouling
30RBM/RBP
160-260
230V electrical plug
284 230 VAC power supply source provided with plug socket
and transformer (180 VA, 0.8 A)
Permits connection of a laptop or an electrical device
during unit commissioning or servicing
30RBM/30RBP
160-520
Expansion vessel
293
6-bar expansion vessel integrated into the hydraulic
module (requires option 116)
Easy and fast installation (plug & play), & Protection of
closed water systems from excessive pressure
30RBM/30RBP
160-520
Screwed water connection
sleeve kit for DSH
303 DSH connections with screw connection sleeves
Easy installation. Allows unit connection to a screw
connector
30RBM/30RBP
160-520
Welded water connection
kit for DSH
304
DSH inlet/outlet welded connection sleeves
Easy installation
30RBM/30RBP
160-520
Set point adjustment by
4-20mA signal
311 Connections to allow a 4-20mA signal input
Easy energy managment, allow to adjust set point by a
4-20mA external signal
30RBM/30RBP
160-520
Free Cooling dry cooler
management
313
Control and connections to a free-cooling drycooler 09PE
or 09VE fitted with optional FC control box
Easy system management, control capabilities extended to
a drycooler used in free cooling mode
30RBM/30RBP
160-520