5.3 - Electrical data 30RBM 160-520
30RBM
160
180
200
220
260
300
330
360
400
430
470
520
Power circuit
Nominal voltage
V-ph-Hz
400 - 3 -50
Voltage range
V
360 - 440
Control circuit supply
24 V via internal transformer
Nominal unit current draw
(1)
Circuit A&B
A
100
110
124
133
161
180
201
221
242
261
282
322
Max. operating input power
(2)
Circuit A&B
kW
80
88
99
107
129
145
161
177
194
210
226
258
Cosine Phi unit at maximum power
(2)
0,88
0,87
0,87
0,88
0,88
0,88
0,88
0,88
0,88
0,88
0,88
0,88
Maximum unit current draw (Un-10%)
(3)
Circuit A&B
A
144
158
176
192
230
259
288
317
345
374
403
460
Circuit A&B - Standard unit
A
133
146
163
177
212
239
266
292
319
345
372
425
Circuit A&B - Unit + option 231
A
100
110
125
133
163
181
204
222
244
262
285
326
Maximum start-up current, standard unit (Un)
(5)
Circuit A&B
A
307
356
374
352
423
450
476
503
529
556
583
636
Maximum start-up current, unit with soft starter (Un)
(5)
Circuit A&B
A
261
283
300
305
349
376
403
429
456
482
509
562
(1) Conditions equivalent to the standardised Eurovent conditions (water type heat exchanger water input/output temperature = 12°C/7°C, outdoor air temperature = 35°C).
(2) Power input, compr fans, at the unit operating limits (saturated suction temperature 15°C, saturated condensation temperature 68.3°C) and nominal voltage of 400 V (data given on the unit's
nameplate).
(3) Maximum unit operating current at maximum unit input power and 360 V.
(4) Maximum unit operating current at maximum unit input power and 400 V (values given on the unit's nameplate).
(5) Maximum instantaneous starting current at the operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of the largest compressor).
Fan motor electrical data at Eurovent equivalent conditions and motor ambient air temperature of 50°C at 400 V: current 3.8 A, starting current 20 A, input power: 1.75 kW.
5.4 - Electrical data 30RBP 160-520
30RBP
160
180
200
220
260
300
330
360
400
430
470
520
Power circuit
Nominal voltage
V-ph-Hz
400 - 3 -50
Voltage range
V
360 - 440
Control circuit supply
24 V via internal transformer
Nominal unit current draw
(1)
Circuit A&B
A
97
107
121
130
158
176
197
216
237
255
276
316
Max. operating input power
(2)
Circuit A&B
kW
81
88
99
108
129
145
162
178
194
210
226
259
Cosine Phi unit at maximum power
(2)
0,88
0,88
0,88
0,88
0,88
0,88
0,88
0,88
0,88
0,88
0,88
0,88
Maximum unit current draw (Un-10%)
(3)
Circuit A&B
A
142
154
173
189
227
255
284
312
340
369
397
454
Maximum unit current draw (Un)
(4)
Circuit A&B - Standard unit
A
131
142
160
174
209
235
262
287
314
340
366
419
Circuit A&B - Unit + option 231
A
98
108
123
131
161
178
201
219
241
259
281
321
Maximum start-up current, standard unit (Un)
(5)
Circuit A&B
A
305
353
371
349
420
446
472
498
525
550
577
629
Maximum start-up current, unit with soft starter (Un)
(5)
Circuit A&B
A
259
279
297
302
346
372
399
424
451
477
503
556
(1) Conditions equivalent to the standardised Eurovent conditions (water type heat exchanger water input/output temperature = 12°C/7°C, outdoor air temperature = 35°C).
(2) Power input, compr fans, at the unit operating limits (saturated suction temperature 15°C, saturated condensation temperature 68.3°C) and nominal voltage of 400 V (data given on the unit's
nameplate).
(3) Maximum unit operating current at maximum unit input power and 360 V.
(4) Maximum unit operating current at maximum unit input power and 400 V (values given on the unit's nameplate).
(5) Maximum instantaneous starting current at the operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of the largest compressor).
Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50°C at 400 V: Current 3.0 A; Start-up current 20 A; Power input:
1.75 kW.
5.5 - Short circuit stability current
Short-circuit withstand current (TN system
(1)
)
30RBM/30RBP
160
180
200
220
260
300
330
360
400
430
470
520
Short time (1s) assigned current Icw / Peak current Ipk
Circuits A & B
kA/kA
8/30
8/30
8/30
8/30
8/30
8/30
8/30
15/65
15/65
15/65
15/65
20/80
With fuses upstream – maximum fuse values assigned (gL/gG)
Circuits A & B
A
200
200
200
200
250
250
250
315
400
400
400
630
With fuses upstream – assigned conditional short-circuit current Icc/Icf
Circuits A & B
kA
50
50
50
50
50
50
50
50
50
50
50
50
(1) Type of system earthing
IT system:
the short-circuit holding current values given above for the TN system are not valid for IT; modifications are required.