Installation 

Manual

Summary of Contents for 30AWH-025QI

Page 1: ...5QO Inverter Hybrid Boiler Original instruction Installation Manual Please read carefully before installation to ensure that installation is performed correctly This manual can be downloaded from the...

Page 2: ...compressors in outdoor unit and a hydro unit are self controlled inaccordance with ambient temperature and flow temperature Intelligent energy saving operation In case of malfunction the self diagnosi...

Page 3: ...ance of brazed plate heat exchanger Control of water quality Other precautions and disposal of waste electronics 2 12 14 15 16 18 23 24 25 29 32 34 35 37 41 42 45 46 48 49 Operating Method ThingsYou M...

Page 4: ...hing that must be paid attention to is specified in the symbol using a picture or phrase Caution Failure to observe this notice may cause injury or damage to property Caution Failure to observe this n...

Page 5: ...to25 istheoptimalplaceforinstallation Installation Electrical work should be performed by a qualified technician in accordance with the instructions specified in this installation guide In addition a...

Page 6: ...ion an outdoor unit that has fallen down may not be repairable Do not install the product in a place that is exposed to direct sunlight or moisture Do not install the product near any fire sources or...

Page 7: ...evel when installing it Imbalance may cause vibration and leakage Mandatory Leveling off Leveling off Install the product in a place that can withstand the load of the product may cause vibration and...

Page 8: ...h the air outlet of the indoor outdoor unit faces the wind Do not install the outdoor units too close each other in parallel Warning Installation Prohibited Prohibited Partial insulation of the piping...

Page 9: ...Mandatory Warning Installation Caution Use a dedicated power supply Mandatory Mandatory Power supply to the product should be a dedicated circuit at a correct voltage Supplying power to the outdoor u...

Page 10: ...n the other hand the product may adversely affect medical equipment or broadcasting equipment as it generates disturbance noises Mandatory Take appropriate action to prevent children from touching the...

Page 11: ...bolts for transportation as materials for piping connection Clean the pipes before starting the plumbing work Make sure the sizes of the hot water suppy and return piping are identical If the room to...

Page 12: ...put anticorrosive agent to prevent the corrosion of domestic hot water tank and pipes Make sure the domestic hot water tank is grounded Use a professional service provider when disposing of the boile...

Page 13: ...pecified in the Article 41 of the Industrial Safety and Health Act After installing the boiler shake and fill the anticorrosive agent into the boiler before filling water Rinse the anticorrosive agent...

Page 14: ...ir inlet Electrical part casing cover Air outlet Refrigerant pipe connection gas pipe 15 8 liquid pipe 9 5 Communication cable Power cable Water outlet pipe 25A Refrigerant pipe connection gas pipe 15...

Page 15: ...when installing an expansion tank and insulation should be provided to prevent freezing and bursting Freeze and burst protection When the flow temperature goes below 6 the circulation pump heating pu...

Page 16: ...ure is very low We recommend that you use an auxiliary heating source if the room temperature is insufficient in the winter season Defrost operation If the heat exchanger of outdoor unit becomes frost...

Page 17: ...s restored Has an Er sign on the room temperature display or sign on the domestic hot water tank display been displayed for more than 1 hour Contact the authorized service center Is the voltage too lo...

Page 18: ...10m 1 liquid pipe 2 Refrigerant connection pipe OD 15 8mm X 10m 1 gas pipe 3 Insulator for refrigerant pipes ID 14 X T7 X 5m 2 4 Insulator for refrigerant pipes ID 14 X T7 X 5m 2 5 Indoor outdoor unit...

Page 19: ...nk Local sourcing 1 14 Expansion tank Local sourcing 1 15 Ball top Procured in the market 1 16 Ball valve Use pressure 10Kg diameter 25A material bronze 6 17 Ball valve for cleaning a brazed plate hea...

Page 20: ...ources A location in which it is easy to connect to the pipe of outdoor unit and perform water piping and electrical work Electric wiring should be carried out by a qualified experienced service techn...

Page 21: ...is exposed to hot air or direct sunlight Do not install it in a location with a saline atmosphere or where it will be exposed to sulphate gas Do not place any obstacle in front of the inlet or outlet...

Page 22: ...When the outdoor temperature is below 0 drainage may be unavailable if the drain hose freezes 3 4 Recommended places An area with no head wind An area with no direct sunlight An area in which the win...

Page 23: ...oninwhichwaterworksareavailable Installthedomestichotwatertankinalocationinwhichitiseasytoperformrepairandmaintenanceactivities Installthedomestichotwatertankinaplacewithnomoistureandthatisequippedwit...

Page 24: ...ated place A place that is not directly exposed to hot wind from a heating device X Poorly ventilated place X A place near a window or door subject to the influence of drafts from the gap X A place su...

Page 25: ...damages to the product Warning Transport the product with care A product with a weight of over 20kg should be carried by at least 2 people The plastic packing bag should be torn into pieces when disp...

Page 26: ...cessing of pipe 1 2 Install the oil trap and liquid loop at the correct position depending on the installation location of the indoor outdoor unit The maximum allowable length of piping is 30m Bend a...

Page 27: ...LPM and the recommended flow ranges from 35 to 40LPM The maximum allowable pressure is less than 0 98 bar Install a ball valve at each side of a pump to facilitate the cleaning and repair of the pump...

Page 28: ...r Service ballvalve 15A Strainer Ball valve 25A Domestic hot water pump output less than 80W Air vent Check valve 25A Drain valve Expansiontank Water supply valve DHW tank temperature sensor Remote co...

Page 29: ...e water pipe should be at least the same size as the connection pipe of the product When connecting a water pipe with a socket apply fastening torque as specified in the table below Applying more torq...

Page 30: ...ture sensor into the cap hole of the sensor holder Lock the sensor holder cap Connect the sensor cable to the terminal of domestic hot water tank temperature sensor in the indoor unit Domestic Hot Wat...

Page 31: ...th the ground s surface Be sure the end of the pipe is pointed downward toward the floor when you remove the burrs after machining a pipe Pay extra attention when performing piping work on a rainy day...

Page 32: ...about the installation and characteristics of R410A product please see the service guide of Carrier inverter air conditioning system Attention There should be no moisture or dust 1 There should be no...

Page 33: ...orr you should replace the oil if oil is mixed with dust or moisture coming from outside during the vacuum operation it takes longer or may be impossible to achieve the desired vacuum state 9 1 1 2 2...

Page 34: ...t to expose the inside of the copper pipe to the atmosphere for a period exceeding the specified time Gradient Wrinkle Crack Uneven thickness There should be no burr at the end part of the flare and t...

Page 35: ...according to the specified lengths of connection pipes First fasten the fitting by hand and then fasten it further using a wrench at a specified torque Fastening of connections Insufficient fastening...

Page 36: ...ot provided Caution Remove the cap from the 3 way valve Generate a vacuum using the vacuum pump connected to the shut off valve gas on the suction side Maintain the shutdown state until the vacuum pre...

Page 37: ...f refrigerant per 1m of extra pipe length Example 5m No additional refrigerant charging is required 25m 25m 5m x 40g 800g of additional refrigerant charging is required If the amount of refrigerant is...

Page 38: ...ng power supply cable perform wiring work between the hydro unit and the outdoor unit Connect the electric wire firmly to the terminal in accordance with the wiring diagram When connecting to the powe...

Page 39: ...cable together using a cable tie or other fixing devices As the power of the outdoor unit is supplied from the indoor unit connect to R S T N of the terminal block No 1 in the indoor unit Combining t...

Page 40: ...ring will cause malfunctions of the controller however polarity does not matter when connecting each load When connecting the wired remote controller connect to the A1 B1 and terminals correctly Incor...

Page 41: ...e power supply refer to the wiring diagram between outdoor unit and indoor unit on page 36 Caution Perform grounding work first before connecting wires Specifications of main power cable of Indoor uni...

Page 42: ...ram between the outdoor unit and indoor unit on the page 36 Caution Perform grounding work first before connecting wires Cable specifications between Outdoor Unit and Indoor Unit Note 1 Use power cabl...

Page 43: ...rence to the table below DIP S W Specifications SW1 1 2 3 4 ON New market Automatic control on Heater control on Not used OFF Replacement market Automatic control off Heater control off Not used Detai...

Page 44: ...ts Check the temperature of supply water Installationofwater pipingsystem Verificationof abnormalitiesinthe waterpipingsystem Carryoutdesignofthesystemincludingheatingload waterflowandinstallationloca...

Page 45: ...ating mode of the boiler to the user turning the product on and off functions of the remote controller Verify and check whether air has completely vented whether supply water flows seamlessly whether...

Page 46: ...on The system automatically enters stop mode after 3 hours of test operation Automatically selects and performs the heating operation according to the outdoor temperature Operation other than Tact swi...

Page 47: ...of Hydro Unit for more than 30 seconds in stop status of the system and then the outdoor unit will start the recovery operation right after releasing from TACT switch Recovery operation can be termin...

Page 48: ...osed properly when performing cleaning Connect a pipe to service valve for cleaning and fill cleaning agent with a temperature of 50 to 60 into the brazed plate heat exchanger and circulate it for 4 t...

Page 49: ...Insufficient water flow may cause freezing and bursting in the brazed plate heat exchanger Make sure that the strainer is not clogged or filled with air and determine whether the water flow is suffic...

Page 50: ...n Scale Basic item pH 25 7 0 8 0 7 0 8 0 O O Electrical conductivity 25 mS m 30 30 O O Chloride ion mg Cl 50 50 O Sulfate ion mg S O 50 50 O Acid consumption pH 4 8 mg CaCO 50 50 O Total hardness mg C...

Page 51: ...to any unrepairable used product Failures caused by nonconformance to the precautions for installation is not covered by the warranty and will incur service fees Grounding of the product is mandatory...