background image

5

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
Installation of filter drier in liquid line is  required.

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the

recommended deep vacuum method of 500 microns. The alternate

triple evacuation method may be used (see triple evacuation

procedure in service manual).  Always break a vacuum with dry

nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of

pulling a vacuum of 500 microns and a vacuum gage capable of

accurately measuring this vacuum depth. The deep vacuum method

is the most positive way of assuring a system is free of air and

liquid water. A tight dry system will hold a vacuum of 1000

microns after approximately 7 minutes.  (See Fig. 8.)

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET

TIGHT

DRY SYSTEM

2000

MICRONS

2500

3000

3500

4000

4500

5000

A95424

A95424

Fig. 8 –

 

Deep Vacuum Graph

Final Tubing Check

IMPORTANT

: Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, makings sure wire ties on feeder tubes are
secure and tight.
Be sure field wiring complies with local and national fire, safety,

and electrical codes, and voltage to system is within limits shown

on unit rating plate. Contact local power company for correction of

improper voltage. See unit rating plate for recommended circuit

protection device.

NOTE

:  Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do  not
install unit in system where voltage may fluctuate above or below
permissible limits.

Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
Do not supply power to unit with compressor terminal box

cover removed.

NOTE

:  Use copper wire only between disconnect switch and unit.

NOTE

:  Install branch circuit disconnect of adequate size per NEC

to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440–14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires

from disconnect through power wiring hole provided and into unit

control box.

Connect Ground and Power Wires

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault should

occur. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing electrical

codes.

Connect ground wire to ground connection in control box for

safety. Connect power wiring to contactor as shown in Fig. 9.

DISCONNECT

PER N.E.C. AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

BLUE

3 PHASE ONLY

A94025

Fig. 9 –

 

Line Connections

A00010

Fig. 10 –

 

3–Phase Monitor Control

(Applies to 3–Phase Units Only)

Summary of Contents for 25HBC5

Page 1: ...h a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testin...

Page 2: ...Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm abo...

Page 3: ...ng diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamin...

Page 4: ...lve and joint Wrap service valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tu...

Page 5: ...nd voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Ope...

Page 6: ...R C RVS COOLING C W2 HP THERMOSTAT TYPICAL FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE LEGEND 24 V FACTORY WIRING 24 V FIEL...

Page 7: ...its R Y and R G Circuit R Y energizes contactor starting outdoor fan motor and compressor Circuit R G energizes indoor blower relay starting blower motor on high speed Should temperature continue to f...

Page 8: ...f the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_...

Page 9: ...rect Do not use chart to adjust refrigerant charge Table 5 Additional Subcooling Required Model 25H 4 Subcooling Delta from Rating Plate Value Outdoor Unit Tonnage Indoor Unit Additional Subcooling Re...

Page 10: ...CN B F 005L FPMAN 018 FFMANP030 FB4CNP030L FFMANP036 FB4CNP048L FV4CNB006L 3 FPMAN 024 FFMANP031 FB4CNP036L FFMANP037 FV4CN B F 003L FX4DN B F 049L FPMBN 018 FPMAN 024 FFMANP030 FPMAN 036 FV4CN B F 00...

Page 11: ...ditions or refrigerant slugging may occur Charge must be weighed in Note Superheat F is at low side service port Allow a tolerance of 3 F Note Indoor dry bulb between 70 F and 80 F Table 9 Required Su...

Page 12: ...0 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compati...

Reviews: