Carrier 25HBC5 Installation Instructions Manual Download Page 7

7

Start–Up

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when

handling refrigerant and observe the following:

S

 Front seating service valves are equipped with Schrader valves.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent refrigerant to

the atmosphere. Recover during system repair or final unit

disposal.

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in personal injury,

equipment damage or improper operation.

S

 Do not overcharge system with refrigerant.

S

 Do not operate unit in a vacuum or at negative pressure.

S

 Do not disable low pressure switch in scroll compressor

applications.

S

 Compressor dome temperatures may be hot.

Follow these steps to properly start up system:

1. After system is evacuated, fully  open liquid and vapor ser-

vice valves.

2. Unit is shipped with valve stem(s) front seated (closed) and

caps installed. Replace stem caps after system is opened to

refrigerant flow (back seated). Replace caps finger–tight and

tighten with wrench an additional 1/12 turn.

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set

point is below indoor ambient temperature.

5. Set room thermostat to HEAT or COOL and fan control to

ON or AUTO mode, as desired. Operate unit for 15

minutes. Check system refrigerant charge.

Sequence of Operation

Turn on power to indoor and outdoor units. Transformer is

energized.

Cooling

On a call for cooling, thermostat makes circuits R–O and R–Y, and

R–G. Circuit R–O energizes reversing valve, switching it to

cooling position. Circuit R–Y energizes contactor, starting outdoor

fan motor and compressor circuit. R–G energizes indoor unit

blower relay, starting indoor blower motor on high speed.

When thermostat is satisfied, its contacts open, de–energizing

contactor and blower relay. Compressor and motors should stop.

NOTE

:  If indoor  unit is equipped with a time–delay relay circuit,

the indoor blower will run an additional 90 seconds to increase
system efficiency.

Heating

On a call for heating, thermostat makes circuits R–Y and R–G.

Circuit R–Y energizes contactor, starting outdoor fan motor and

compressor. Circuit R–G energizes indoor blower relay, starting

blower motor on high speed.
Should temperature continue to fall, R–W2 is made through

second–stage room thermostat. Circuit R–W2 energizes a relay,

bringing on first bank of supplemental electric heat and providing

electrical potential to second heater relay (if used). If outdoor

temperature falls below setting of outdoor thermostat (field

installed option), contacts close to complete circuit and bring on

second bank of supplemental electric heat.
When thermostat is satisfied, its contacts open, de–energizing

contactor and relay. All heaters and motors should stop.

Defrost

The defrost control is a time/temperature control which includes a

field selectable (quick–connects located at board edge) time period

between defrost cycles (30, 60, or 90 minutes), factory set to either

60 or 90 minutes.
The electronic defrost timer sequence is enabled when the T1 input

on the board is energized. The timer starts only when the defrost

thermostat is closed and the contactor is energized.
Defrost mode is identical to cooling mode except that outdoor fan

motor stops and second–stage heat is turned on to continue

warming conditioned spaces.
To initiate defrost, the defrost thermostat must be closed. This can

be accomplished as follows:

1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control

board  (see Fig. 12). Tape lead to prevent grounding.

3. Restart unit in heating mode, allowing frost to accumulate

on outdoor coil.

4. After a few minutes in heating mode, liquid line temperat-

ure should drop below closing point of defrost thermostat

(approximately 30

°

F/–1.11

°

C).

5. Short between speedup terminals with a flat–blade screw-

driver. This reduces the timing sequence to 1/25th of origin-

al time. (See Table 4.)

6. When you hear reversing valve change position, remove

screwdriver immediately; otherwise, control will terminate

normal 10–minute defrost cycle in approximately 2

seconds.

NOTE

:  Length of defrost cycle is dependent upon length of time

it takes to remove screwdriver from test pins after reversing valve
has shifted.

7. Unit will remain in defrost for remainder of defrost cycle

time or until defrost thermostat reopens at approximately

65

°

F (18.33

°

C) coil temperature of liquid line.

8. Turn off power to outdoor unit and reconnect fan motor

lead to OF2 on control board.

Summary of Contents for 25HBC5

Page 1: ...h a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testin...

Page 2: ...Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm abo...

Page 3: ...ng diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamin...

Page 4: ...lve and joint Wrap service valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tu...

Page 5: ...nd voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Ope...

Page 6: ...R C RVS COOLING C W2 HP THERMOSTAT TYPICAL FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE LEGEND 24 V FACTORY WIRING 24 V FIEL...

Page 7: ...its R Y and R G Circuit R Y energizes contactor starting outdoor fan motor and compressor Circuit R G energizes indoor blower relay starting blower motor on high speed Should temperature continue to f...

Page 8: ...f the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_...

Page 9: ...rect Do not use chart to adjust refrigerant charge Table 5 Additional Subcooling Required Model 25H 4 Subcooling Delta from Rating Plate Value Outdoor Unit Tonnage Indoor Unit Additional Subcooling Re...

Page 10: ...CN B F 005L FPMAN 018 FFMANP030 FB4CNP030L FFMANP036 FB4CNP048L FV4CNB006L 3 FPMAN 024 FFMANP031 FB4CNP036L FFMANP037 FV4CN B F 003L FX4DN B F 049L FPMBN 018 FPMAN 024 FFMANP030 FPMAN 036 FV4CN B F 00...

Page 11: ...ditions or refrigerant slugging may occur Charge must be weighed in Note Superheat F is at low side service port Allow a tolerance of 3 F Note Indoor dry bulb between 70 F and 80 F Table 9 Required Su...

Page 12: ...0 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compati...

Reviews: