Table 8 – Superheat Charging (Heat Pump Only)

OUTDOOR TEMP (°F)

EVAPORATOR ENTERING AIR TEMPERATURE (°F WB)

50

52

54

56

58

60

62

64

67

68

70

72

74

76

55

11

11

12

12

12

13

17

20

24

24

25

25

25

25

60

6

6

7

7

7

7

12

16

21

22

23

23

23

23

65

3

7

12

18

19

21

21

22

22

70

7

14

16

18

20

20

20

75

3

11

13

16

18

18

19

82

*6

8

12

15

16

17

85

4

7

11

14

15

16

90

4

8

12

14

15

95

6

10

12

14

100

4

8

11

12

105

3

6

9

11

110

5

7

10

115

3

6

8

*Optimum performance point, 82°F outdoor ambient and (80°F dry bulb),( 67°F wet bulb) indoor conditions. (DOE B Test Conditions)
Where a dash (––) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.

Note

: Superheat °F is at low–side service port, Allow a tolerance of ± 3°F

Note

: Indoor dry bulb between 70°F and 80°F

Table 9 – Required Suction–Line Temperature

SUPERHEAT TEMP (°F)

SUCTION PRESSURE AT SERVICE PORT (PSIG)

107.8

112.2

116.8

121.2

126

130.8

138.8

140.8

145.8

0

35

37

39

41

43

45

47

49

51

2

37

39

41

43

45

47

49

51

53

4

39

41

43

45

47

49

51

53

55

6

41

43

45

47

49

51

53

55

57

8

43

45

47

49

51

53

55

57

59

10

45

47

49

51

53

55

57

59

61

12

47

49

51

53

55

57

59

61

63

14

49

51

53

55

57

59

61

63

65

16

51

53

55

57

59

61

63

65

67

18

53

55

57

59

61

63

65

67

69

20

55

57

59

61

63

65

67

69

71

22

57

59

61

63

65

67

69

71

73

24

59

61

63

65

67

69

71

73

75

26

61

63

65

67

69

71

73

75

77

28

63

65

67

69

71

73

75

77

79

30

65

67

69

71

73

75

77

79

81

Summary of Contents for 25HBC5

Page 1: ...h a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testin...

Page 2: ...Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service end of unit and 48 in 1219 2 mm abo...

Page 3: ...ng diameters There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamin...

Page 4: ...lve and joint Wrap service valves with a heat sinking material such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tu...

Page 5: ...nd voltage to system is within limits shown on unit rating plate Contact local power company for correction of improper voltage See unit rating plate for recommended circuit protection device NOTE Ope...

Page 6: ...R C RVS COOLING C W2 HP THERMOSTAT TYPICAL FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O IF AVAILABLE LEGEND 24 V FACTORY WIRING 24 V FIEL...

Page 7: ...its R Y and R G Circuit R Y energizes contactor starting outdoor fan motor and compressor Circuit R G energizes indoor blower relay starting blower motor on high speed Should temperature continue to f...

Page 8: ...f the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_...

Page 9: ...rect Do not use chart to adjust refrigerant charge Table 5 Additional Subcooling Required Model 25H 4 Subcooling Delta from Rating Plate Value Outdoor Unit Tonnage Indoor Unit Additional Subcooling Re...

Page 10: ...CN B F 005L FPMAN 018 FFMANP030 FB4CNP030L FFMANP036 FB4CNP048L FV4CNB006L 3 FPMAN 024 FFMANP031 FB4CNP036L FFMANP037 FV4CN B F 003L FX4DN B F 049L FPMBN 018 FPMAN 024 FFMANP030 FPMAN 036 FV4CN B F 00...

Page 11: ...ditions or refrigerant slugging may occur Charge must be weighed in Note Superheat F is at low side service port Allow a tolerance of 3 F Note Indoor dry bulb between 70 F and 80 F Table 9 Required Su...

Page 12: ...0 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compati...

Reviews: