The furnace starts up in either low- or high-gas heat. If furnace
starts up in low-gas heat, control CPU determines low-gas
heat on time (from 0 to 16 minutes) which is permitted before
switching to high-gas heat.
If power is interrupted, stored history is erased, and control
CPU selects low-gas heat for up to 16 minutes and then
switches to high-gas heat as long as thermostat continues to
"call for heat." Subsequent selection is based on stored history
of thermostat cycle times.
When the wall thermostat "calls for heat," R-W1 circuit
closes. The furnace control performs a self-check, verifies
low-heat and high-heat pressure switch contacts LPS and HPS
are open, and starts inducer motor IDM in low speed or high
speed as appropriate.
a. Inducer prepurge period—As inducer motor IDM comes up

to low speed or high speed, the low-heat pressure switch
contacts LPS (or LPS and HPS) close to begin a 15-sec
prepurge period.

b. Ignitor warm-up—At the end of prepurge period, hot

surface ignitor HSI is energized for a 17-sec ignitor
warm-up period.

c. Trial-for-ignition sequence—When ignitor warm-up period

is completed, main gas valve relay contacts MGVR-1 and
-2 close to energize low-heat gas valve solenoid GV, gas
valve opens, and 24-v power is supplied for a field-installed
humidifier at terminals HUM and C

OM

. Low-heat gas valve

solenoid GV permits gas flow to the burners where it is
ignited. After 5 sec, ignitor HSI is de-energized, and a 2-sec
flame-proving period begins.
If furnace control CPU selects high-gas-heat operation,
high-heat gas valve solenoid GV is also energized after
normally closed high-heat pressure switch relay HPSR
closes and after inducer motor IDM goes to high speed and
provides sufficient pressure to close high-heat pressure
switch HPS. HPSR is open while furnace is powered in
standby mode. If high-heat pressure switch HPS fails to
close and low-heat pressure switch LPS closes, furnace
operates at low-heat gas flow rate until high-heat pressure
switch closes.

d. Flame-proving—When burner flame is proved at flame-

proving sensor electrode FSE, control CPU begins blower
on delay period and continues to hold gas valve GV open.
If burner flame is not proved within 2 sec, control CPU
closes gas valve GV, and control CPU repeats ignition
sequence for up to 3 more trials-for-ignition before going
to ignition lockout. LOCKOUT IS RESET AUTOMATI-
CALLY after 3 hr, or by momentarily interrupting 115-v
power to furnace, or by interrupting 24-v power at SEC1 or
SEC2 to control CPU (not at W/W1, G, R, etc.). Opening
thermostat R-W circuit will not reset ignition lockout.
If flame is proved when flame should not be present,
control CPU locks out of gas heating mode and operates
inducer motor IDM on high speed until flame is no longer
proved.

e. Blower on delay—If burner flame is proven, 45 sec after

gas valve GV is opened blower motor BLWM is energized
on appropriate heating speed, low-gas-heat or high-gas-
heat speed. Simultaneously, EAC terminals EAC-1 and
EAC-2 are energized with 115v and remain energized as
long as blower motor BLWM is energized.

f. Switching from low- to high-gas heat—If furnace control

CPU switches from low-gas heat to high-gas heat, control
CPU switches inducer motor IDM speed from low to high.
The high-heat pressure switch relay HPSR closes. When

inducer motor IDM provides sufficient pressure to close
high-heat pressure switch HPS, high-heat gas valve sole-
noid GV is energized. Blower motor BLWM switches
speed for high-gas heat 5 sec after control CPU switches
from low-gas heat to high-gas heat.

g. Switching from high- to low-gas heat—Control CPU will

not switch from high-gas heat to low-gas heat while
thermostat R-W circuit is closed when a single-stage
thermostat is used.

h. Blower off delay—When thermostat is satisfied, R-W

circuit is opened, de-energizing gas valve GV, stopping gas
flow to burners, and de-energizing humidifier terminals
HUM and C

OM

. Inducer motor IDM remains energized for

a 5-sec post-purge period. Blower motor BLWM and EAC
terminals EAC-1 and EAC-2 remain energized for 90, 135,
180, or 225 sec (depending on selection at blower off delay
switches SW-3 and SW-4). Furnace control CPU is factory
set for a 135-sec blower off delay.

2. Non-Adaptive Heating Mode—Two-Stage Thermostat and

2-Stage Heating
(See Fig. 16 for thermostat connections.)

NOTE:

The low-heat-only switch SW-2 ON selects low-heat-

only operation mode in response to closing thermostat R-W/W1
circuit. When high-heat-only switch SW-1 is off, closing thermo-
stat R to W1-and-W2 circuits is required for high-gas-heat
operation. When high-heat-only switch SW-1 is on, it always
causes high-gas-heat operation when R-W/W1 circuit is closed,
regardless of setting of low-heat-only switch SW-2 and regardless
of whether R-W2 circuit is closed or open.

The start-up and shutdown functions and delays described in
item 1 above apply to 2-stage heating mode as well, except for
switching from low- to high-gas heat and vice versa.
a. When wall thermostat "calls for heat," R-W/W1 circuit

closes for low-gas heat or R to W1-and-W2 circuits close
for high-gas heat. The furnace control performs a self-
check, verifies low-heat and high-heat pressure switch
contacts LPS and HPS are open, and starts inducer motor
IDM in low speed or high speed as appropriate.

b. Switching from low- to high-gas heat—If thermostat

R-W/W1 circuit for low-gas heat is closed and R-W2
circuit for high-gas heat closes, control CPU switches
inducer motor IDM speed from low to high. The high-heat
pressure switch relay HPSR closes. When inducer motor
IDM provides sufficient pressure to close high-heat pres-
sure switch HPS, high-heat gas valve solenoid GV is
energized. Blower motor BLWM switches speed for high-
gas heat 5 sec after R-W2 circuit closes.

c. Switching from high- to low-gas heat—If thermostat R-W2

circuit for high-gas heat opens and R-W/W1 circuit for
low-gas heat remains closed, control CPU switches inducer
motor IDM speed from high to low. The high-heat pressure
switch relay HPSR opens to de-energize high-heat gas
valve solenoid GV. When inducer motor IDM reduces
pressure sufficiently, high-heat pressure switch HPS opens.
The low-heat gas valve solenoid GV remains energized as
long as low-heat pressure switch LPS remains closed.
Blower motor BLWM switches speed for low-gas heat 5
sec after R-W2 circuit opens.

3. Cooling Mode

a. Single-Speed Cooling Outdoor Unit

(See Fig. 15 for thermostat connections.)

14

Summary of Contents for 2-STAGE 58TMA

Page 1: ... working on heating equipment observe precautions in the literature on tags and on labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States refer to the National Fuel Gas Code NFGC NFPA No 54 1996 ANSI Z223 1 1996 In Canada refer to the current edition of the National Standard of Canada CAN CGA B149 1 and 2 M95 Natural Gas...

Page 2: ...s before touching ungrounded objects 7 An ESD service kit available from commercial sources may also be used to prevent ESD damage INTRODUCTION The model 58TMA Series 111 Furnace is available in sizes 65 000 through 123 000 Btuh input capacities The design of the downflow horizontal gas fired furnace is A G A C G A certified for natural and propane gases and for installation on noncombustible floo...

Page 3: ...ous return air temperature of 60 F db or intermittent operation down to 55 F such as when used with a night setback thermostat Return air temperature must not exceed 85 F db To aid in installation troubleshooting and service a status code label is located on blower component door This label explains how to use the LED status indicated on furnace control which is viewed through the sight glass on d...

Page 4: ...s When installed parallel with furnace dampers or other means used to control the flow of air must prevent chilled air from entering furnace If dampers are manually operated they must be equipped with means to prevent operation of either unit unless damper is in full heat or full cooling position HAZARDOUS LOCATIONS When furnace is installed in a residential garage it must be installed so that bur...

Page 5: ...ugh 2 hori zontal ducts the openings and ducts MUST have at least 1 sq in of free area per 2000 Btuh of total input for all equipment within the confined space See Fig 4 and Table 2 c If combustion air is taken from outdoors through a single opening or duct horizontal or vertical commencing within 12 in of the top of the confined space opening and duct MUST have at least 1 sq in of free area per 3...

Page 6: ... Area of Opening and Duct Sq In Round Pipe In Dia 63 000 100 15 8 5 31 5 7 21 0 6 84 000 100 21 0 6 42 0 8 28 0 6 105 000 105 26 3 6 52 5 9 35 0 7 123 000 123 30 8 7 61 5 9 41 0 8 Table 3 Opening Dimensions In FURNACE CASING WIDTH APPLICATION PLENUM OPENING FLOOR OPENING A B C D 14 3 16 Non Combustible Flooring 12 11 16 19 13 3 8 19 5 8 Combustible Flooring Using KGASB Subbase 11 13 16 19 13 7 16 ...

Page 7: ... horizontal crawlspace installation is very similar to attic installation refer to Step 4 The installation of a sheet metal shield in front of louvered control panel is covered in Step 4 For a crawlspace installation this same sheet metal shield must be installed above louvered control panel Extend sheet metal shield over furnace top far enough to cover gas pipe entry hole Step 6 Filter Arrangemen...

Page 8: ...f furnace must be supported when furnace is used in horizontal position 3 8 IN HEX NUT WASHER 4 REQD PER ROD A PREFERRED ROD LOCATION B ALTERNATE ROD LOCATION A B A B B A A B Fig 8 Typical Attic Installation A97516 30 IN MIN WORK AREA 6 MIN TYPE B VENT GAS ENTRY 24 24 SHEET METAL SEDIMENT TRAP MANUAL SHUTOFF GAS VALVE LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP A...

Page 9: ...be installed by connecting a tee to riser leading from furnace Connect capped nipple into lower end of tee The capped nipple should extend below level of gas controls See Fig 13 Piping should be pressure tested in accordance with local and national plumbing and gas codes before furnace has been attached If test pressure exceeds 0 5 psig 14 in wc the gas supply pipe must be disconnected from furnac...

Page 10: ... use ONLY a 3 amp fuse The control will flash code 24 when fuse needs replacement ACCESSORIES 1 Electronic air cleaner EAC A terminal block EAC 1 hot and EAC 2 neutral is provided for EAC connection See Fig 14 The terminals are energized with 115v 1 amp maximum during blower motor operation 2 Humidifier HUM Screw terminals HUM 1 and COM are provided for 24 v humidifier connection The terminals are...

Page 11: ...satisfactorily Time delay fuse is recommended Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop Fig 15 Heating and Cooling Application Wiring Diagram With 1 Stage Thermostat and Condensing Unit A97443 115 V FUSED DISCONNECT SWITCH WHEN REQUIRED JUNCTION BOX CONTROL BOX 24 V TERMINAL BLOCK TWO WIRE HEATING ONLY FIVE WIRE 1 STAGE THER...

Page 12: ... response to call for heat See Fig 17 When high heat only switch SW 1 is on it always causes high gas heat operation when R W W1 circuit is closed regardless of the setting of low heat only switch SW 2 This furnace can operate as a 2 stage furnace with a single stage thermostat because furnace control CPU includes a programmed adaptive sequence of controlled operation which selects low gas heat or...

Page 13: ...witches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RED LS FRS2 RED RED FRS1 WHEN USED ALS1 DSS ORN LGPS YEL NOTE 8 LPS NOTE 8 WHEN USED RED YEL ORN WHEN USED NOTE 6 ALS2 ORN SWITCH 1 2 HEAT SET UP SWITCH NORM HI HT LO HT ON OFF OFF ON BLOWER OFF DELAY SEC SWITCH 3 4 9...

Page 14: ...If furnace control CPU switches from low gas heat to high gas heat control CPU switches inducer motor IDM speed from low to high The high heat pressure switch relay HPSR closes When inducer motor IDM provides sufficient pressure to close high heat pressure switch HPS high heat gas valve sole noid GV is energized Blower motor BLWM switches speed for high gas heat 5 sec after control CPU switches fr...

Page 15: ...perating for an additional 90 sec if no other function requires blower motor BLWM operation 5 Heat Pump NOTE An accessory interface kit is required with single speed heat pumps See interface kit Installation Instructions for single speed heat pump thermostat and interface connections No inter face kit is needed for 2 speed heat pumps See 2 speed heat pump Installation Instructions for thermostat c...

Page 16: ...ve that furnace goes off Set thermostat above room temperature and observe that furnace restarts ADJUSTMENTS 1 Set gas input rate Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft In the U S A input rating for altitudes above 2000 ft must be reduced by 4 percent for each 1000 ft above sea level In Canada input rating must be derated by 10 percent for altitudes ...

Page 17: ...ed in low heat operation g Jumper R to W W1 h Let furnace run for 3 minutes in low heat operation i Measure time in sec for gas meter to complete 1 revolu tion Note reading j Refer to Table 10 for cubic ft of gas per hr k Multiply gas rate cu ft hr by heating value Btu cu ft l Move setup switch SW 2 to OFF position and jumper R and W2 thermostat connections See Fig 17 This keeps furnace locked in ...

Page 18: ...3 3 5 1 4 43 3 6 1 5 43 3 7 1 5 42 3 2 1 3 42 3 3 1 3 2001 825 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 43 3 7 1 5 to 850 44 3 6 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 3000 875 44 3 4 1 4 44 3 5 1 4 44 3 6 1 5 44 3 7 1 5 44 3 8 1 6 or 900 44 3 2 1 3 44 3 3 1 4 44 3 4 1 4 44 3 5 1 4 44 3 6 1 5 Canada 925 46 3 8 1 6 45 3 8 1 6 44 3 2 1 3 44 3 3 1 4 44 3 4 1 4 Altitudes 950 46 3 6 1 5 46 ...

Page 19: ... 5 750 45 3 7 1 5 44 3 2 1 3 44 3 3 1 4 44 3 4 1 4 44 3 5 1 4 775 46 3 6 1 5 46 3 8 1 6 45 3 7 1 5 44 3 2 1 3 44 3 3 1 4 5001 800 46 3 4 1 4 46 3 5 1 5 46 3 7 1 5 46 3 8 1 6 45 3 7 1 5 825 47 3 7 1 5 47 3 8 1 6 46 3 4 1 4 46 3 6 1 5 46 3 7 1 5 to 850 47 3 4 1 4 47 3 6 1 5 47 3 7 1 5 47 3 8 1 6 46 3 5 1 4 875 48 3 7 1 5 48 3 8 1 6 47 3 5 1 4 47 3 6 1 5 47 3 7 1 5 6000 900 48 3 5 1 4 48 3 6 1 5 48 3...

Page 20: ...ld Pressure High Low U S A Only 600 45 3 7 1 5 44 3 2 1 3 44 3 3 1 4 44 3 4 1 4 44 3 5 1 4 625 46 3 6 1 5 46 3 7 1 5 46 3 8 1 6 45 3 8 1 6 44 3 2 1 3 8001 650 47 3 8 1 6 46 3 4 1 4 46 3 5 1 5 46 3 7 1 5 46 3 8 1 6 675 47 3 5 1 4 47 3 6 1 5 47 3 7 1 5 47 3 8 1 6 46 3 5 1 4 to 700 48 3 7 1 5 48 3 8 1 6 47 3 5 1 4 47 3 6 1 5 47 3 7 1 5 725 48 3 4 1 4 48 3 6 1 5 48 3 7 1 5 48 3 8 1 6 47 3 4 1 4 9000 7...

Page 21: ...used applies only to furnaces with 5 speed blower motors Follow this same procedure for proper selection of cool and low gas heat speed selection 6 Set thermostat heat anticipator a When using a nonelectronic thermostat the thermostat heat anticipation must be set to match amp draw of electrical Table 11 Gas Rate Cu Ft Hr SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF ...

Page 22: ...tart up allow furnace to operate for 2 minutes then block flue outlet 100 percent Furnace should cycle off within 2 minutes d Remove blockage and reconnect vent connector to furnace flue collar e Wait 5 minutes and then reset draft safeguard switch 3 Check flow sensing pressure switches This control proves operation of draft inducer blower a Turn off 115 v power to furnace b Remove gas control doo...

Page 23: ... 1 and SW 2 and blower off delay SW 3 and SW 4 Refer to Tables 6 and 7 3 Verify manual reset switches have continuity 4 Ensure blower and gas control access doors are properly installed 5 Cycle test furnace with room thermostat 6 Check operation of accessories per manufacturer s instruc tions 7 Review User s Manual with owner 8 Leave literature packet near furnace 23 ...

Page 24: ...ceTraining plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 644 5544 Packaged Service Training Classroom Service Training Copyright 1997 CARRIER Corp 7310 W Morris St Indianapolis IN 46231 58tma6si Manufacturer reserves the right ...

Reviews: