COLD WEATHER KIT
For cold climates, optional cold weather kit (part
number 0F6148) is recommended. The kit includes:
• Battery Warmer
• 4” Junction Box with hardware
• 6 qt. pack 5W-30 synthetic oil (engine)
COOLANT HEATER KIT
The optional Coolant Heater Kit (part number
0G3065) is available to be used in cunjuntion with
the Optional Cold Weather Kit. This kit includes:
• 1500 watt, 120 volt Engine Block Heater
• Heater Mounting Bracket
• All fittings, hoses and hardware to mount and
plumb heater
RECONFIGURING THE FUEL SYSTEM
NOTE:
All models are configured to run on natural gas
from the factory.
Before the generator can be operated using a LP fuel
source, the fuel system, wire harness, and ignition
control module must be reconfigured. The steps to
reconfigure the generator from a natural gas (NG) to
a liquidified petroleum (LP) fuel source are as fol-
lows:
FUEL SYSTEM
1. Turn the main gas supply off and disconnect the
battery. The battery may be reconnected after the
wire harness has been reconfigured.
2. Remove the carburetor fuel hose from the outlet
port of the demand regulator (see Figure 6.2).
3. Disconnect the power wires from the fuel sole-
noid located on top of the regulator assembly by
removing the screw on the front of the connector
and pulling the connector forward, away from the
solenoid body.
4. Loosen the spring clamp on the small fuel enrich-
ment line and remove the hose from the hose
barb.
5. Remove the black pipe assembly from the out-
let port of the demand regulator. The solenoid
assembly may need to be removed before per-
forming this operation (Figure 6.2).
6. Remove the NG fuel jet (loosen counter clock-
wise) from the outlet port.
7. Remove the LP fuel jet (loosen counter clockwise)
from the jet keeper port on the side of the regula-
tor housing. Install this jet into the outlet port in
the regulator casting.
NOTE:
The jet sizes are stamped on the individual jets.
The larger jet size is used for running on NG.
Figure 6.1 — Interconnections
6-2
Standby Generator Sets
Specifications
GenSpec046 Rev.
B 08/08
NEUTRAL
N1
N2
23
194
186
178
To Generator Control Panel
Utility In
Load
Out
Gen
Transfer Switch
4- # 14 GA
WIRES TO
GENERATOR
CONNECTION
BOX
TO GENERATOR
CONNECTION BOX
This is a generic representation of the components contained in the transfer switch and connection box.
Refer to the wiring and schematic diagrams for generator specifi c connections.
Summary of Contents for 2.4L
Page 28: ......
Page 30: ......
Page 32: ......
Page 34: ......
Page 36: ......
Page 38: ......
Page 39: ......
Page 41: ......
Page 42: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......