![Carrier 19EF Series Start Up & Operation Manual Download Page 24](http://html1.mh-extra.com/html/carrier/19ef-series/19ef-series_start-up-and-operation-manual_2562257024.webp)
PIC System Functions
NOTE: Throughout this manual, words printed in capital let-
ters and italics are values that may be viewed on the LID.
See Table 2 for examples of LID screens. Point names are
listed in the Description column. An overview of LID op-
eration and menus is given in Fig. 10-16.
CAPACITY CONTROL — The PIC controls the machine
capacity by modulating the inlet guide vanes in response to
chilled water temperature changes away from the CON-
TROL POINT. The CONTROL POINT may be changed by
a CCN network device, or is determined by the PIC adding
any active chilled water reset to the chilled water SET POINT.
The PIC uses the PROPORTIONAL INC (Increase) BAND,
PROPORTIONAL DEC (Decrease) BAND, and the PRO-
PORTIONAL ECW (Entering Chilled Water) GAIN to de-
termine how fast or slow to respond. CONTROL POINT
may be viewed/overridden on the Status table, Status01
selection.
ENTERING CHILLED WATER CONTROL — If this op-
tion is enabled, the PIC uses ENTERING CHILLED WATER
temperature to modulate the vanes instead of LEAVING
CHILLED WATER temperature. ENTERING CHILLED WA-
TER control option may be viewed/modified on the Equip-
ment Configuration table, Config table.
DEADBAND — This is the tolerance on the chilled water/
brine temperature CONTROL POINT. If the water tempera-
ture goes outside of the DEADBAND, the PIC opens or closes
the guide vanes in response until it is within tolerance. The
PIC may be configured with a 0.5 to 2 F (0.3 to 1.1 C) dead-
band. DEADBAND may be viewed or modified on the Equip-
ment Service1 table.
For example, a 1° F (0.6° C) deadband setting controls
the water temperature within ±0.5° F (0.3° C) of the control
point. This may cause frequent guide vane movement if the
chilled water load fluctuates frequently. A value of 1° F
(0.6° C) is the default setting.
PROPORTIONAL BANDS AND GAIN — Proportional band
is the rate at which the guide vane position is corrected in
proportion to how far the chilled water/brine temperature is
from the control point. Proportional gain determines how
quickly the guide vanes react to how quickly the tempera-
ture is moving from CONTROL POINT.
The proportional band can be viewed/modified on the LID.
There are two response modes, one for temperature re-
sponse above the control point, the other for response below
the control point.
The first type is called PROPORTIONAL INC BAND, and
it can slow or quicken vane response to chilled water/brine
temperature above DEADBAND. It can be adjusted from a
setting of 2 to 10; the default setting is 6.5. PROPOR-
TIONAL DEC BAND can slow or quicken vane response to
chilled water temperature below deadband plus control point.
It can be adjusted on the LID from a setting of 2 to 10, and
the default setting is 6.0. Increasing either of these settings
will cause the vanes to respond slower than a lower setting.
The PROPORTIONAL ECW GAIN can be adjusted at the LID
display from a setting of 1.0 to 3.0, with a default setting of
2.0. Increase this setting to increase guide vane response to
a change in entering chilled water temperature. The propor-
tional bands and gain may be viewed/modified on the Equip-
ment Service3 table.
DEMAND LIMITING — The PIC will respond to the AC-
TIVE DEMAND LIMIT set point by limiting the opening of
the guide vanes. It will compare the set point to either COM-
PRESSOR MOTOR LOAD or COMPRESSOR MOTOR CUR-
RENT (percentage), depending on how the control is con-
figured for the DEMAND LIMIT SOURCE which is accessed
on the SERVICE1 table. The default setting is current
limiting.
MACHINE TIMERS — The PIC maintains 2 runtime clocks,
known as COMPRESSOR ONTIME and SERVICE ON-
TIME. COMPRESSOR ONTIME indicates the total lifetime
compressor run hours. This timer can register up to
500,000 hours before the clock turns back to zero. The SERV-
ICE ONTIME is a resettable timer that can be used to indi-
cate the hours since the last service visit or any other reason.
The time can be changed through the LID to whatever value
is desired. This timer can register up to 32,767 hours before
it rolls over to zero.
The chiller also maintains a start-to-start timer and a stop-
to-start timer. These timers limit how soon the machine can
be started. See the Start-Up/Shutdown/Recycle Sequence sec-
tion, page 34, for operational information.
OCCUPANCY SCHEDULE — This schedule determines when
the chiller is either occupied or unoccupied.
Each schedule consists of from one to 8 occupied/unoccupied
time periods, set by the operator. These time periods can be
enabled to be in effect, or not in effect, on each day of the
week and for holidays. The day begins with 0000 hours and
ends with 2400 hours. The machine is in OCCUPIED mode
unless an unoccupied time period is in effect.
The machine will shut down when the schedule goes to
UNOCCUPIED. These schedules can be set up to follow the
building schedule or to be 100% OCCUPIED if the operator
wishes. The schedules also can be bypassed by forcing the
Start/Stop command on the PIC Status screen to start. The
schedules also can be overridden to keep the unit in an OC-
CUPIED mode for up to 4 hours, on a one-time basis.
Figure 15 shows a schedule for a typical office building
time schedule, with a 3-hour, off-peak cool down period from
midnight to 3 a.m., following a weekend shutdown. Ex-
ample: Holiday periods are unoccupied 24 hours per day.
The building operates Monday through Friday, 7:00 a.m. to
6:00 p.m., with a Saturday schedule of 6:00 a.m. to
1:00 p.m., and includes the Monday midnight to 3:00 a.m.
weekend cool-down schedule.
NOTE: This schedule is for illustration only, and is not in-
tended to be a recommended schedule for chiller operation.
The Local Time Schedule is still the Occupancy Schedule
01. The Ice Build Time Schedule is Schedule 02 and the CCN
Default Time Schedule is Schedule 03. The CCN schedule
number is defined on the Config table in the Equipment Con-
figuration table on page 19. The schedule number can change
to any value from 03 to 99. If this schedule number is changed
on the Config table, the operator must use the Attach to Net-
work Device table to upload the new number into the Sched-
ule screen. See Fig. 14.
Safety Controls —
The PIC monitors all safety control
inputs, and if required, shuts down the machine or limits the
guide vanes to protect the machine from possible damage
from any of the following conditions:
• high bearing temperature
• high motor winding temperature
• high discharge temperature
• low oil pressure
24
Summary of Contents for 19EF Series
Page 10: ...Fig 5 19EF Controls and Sensor Locations cont 10...
Page 13: ...Fig 12 19EF Menu Structure 13...
Page 14: ...Fig 13 19EF Service Menu Structure 14...
Page 38: ...Fig 24 19EF Leak Test Procedures 38...
Page 69: ...Fig 36 Electronic PIC Controls Wiring Schematic 69...
Page 70: ...Fig 36 Electronic PIC Controls Wiring Schematic cont 70...
Page 71: ...Fig 37 Machine Power Panel Starter Assembly and Motor Wiring Schematic 71...