Table 2 — LID Screens (cont)
EXAMPLE 8 — SERVICE2 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE2.
6. Press SELECT .
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
OPTIONS BOARD 1
20 mA POWER CONFIGURATION
External = 0, Internal = 1
RESET 20 mA Power Source
DISABLE/ENABLE
res
20 ma
DISABLE
DEMAND 20 mA Power Source
DISABLE/ENABLE
dem
20 ma
DISABLE
SPARE ALERT ENABLE
Disable = 0, Low = 1, High = 2
Temp = Alert Threshold
CHWS Temp Enable
0-2
chws
en
0
CHWS Temp Alert
–40-245 (–40-118)
DEG F (DEG C)
chws
al
245 (118)
CHWR Temp Enable
0-2
chwr
en
0
CHWR Temp Alert
–40-245 (–40-118)
DEG F (DEG C)
chwr
al
245 (118)
Reset Temp Enable
0-2
rres
en
0
Reset Temp Alert
–40-245 (–40-118)
DEG F (DEG C)
rres
al
245 (118)
Spare Temp 1 Enable
0-2
spr1
en
0
Spare Temp 1 Alert
–40-245 (–40-118)
DEG F (DEG C)
spr1
al
245 (118)
Spare Temp 2 Enable
0-2
spr2
en
0
Spare Temp 2 Alert
–40-245 (–40-118)
DEG F (DEG C)
spr2
al
245 (118)
Spare Temp 3 Enable
0-2
spr3
en
0
Spare Temp 3 Alert
–40-245 (–40-118)
DEG F (DEG C)
spr3
al
245 (118)
OPTIONS BOARD 2
20 mA POWER CONFIGURATION
External = 0, Internal = 1
SPARE 1 20 mA Power Source
DISABLE/ENABLE
sp1
20 ma
DISABLE
SPARE 2 20 mA Power Source
DISABLE/ENABLE
sp2
20 ma
DISABLE
SPARE ALERT ENABLE
Disable = 0, Low = 1, High = 2
Temp = Alert Threshold
Spare Temp 4 Enable
0-2
spr4
en
0
Spare Temp 4 Alert
–40-245 (–40-118)
DEG F (DEG C)
spr4
al
245 (118)
Spare Temp 5 Enable
0-2
spr5
en
0
Spare Temp 5 Alert
–40-245 (–40-118)
DEG F (DEG C)
spr5
al
245 (118)
Spare Temp 6 Enable
0-2
spr6
en
0
Spare Temp 6 Alert
–40-245 (–40-118)
DEG F (DEG C)
spr6
al
245 (118)
Spare Temp 7 Enable
0-2
spr7
en
0
Spare Temp 7 Alert
–40-245 (–40-118)
DEG F (DEG C)
spr7
al
245 (118)
Spare Temp 8 Enable
0-2
spr8
en
0
Spare Temp 8 Alert
–40-245 (–0-118)
DEG F (DEG C)
spr8
al
245 (118)
Spare Temp 9 Enable
0-2
spr9
en
0
Spare Temp 9 Alert
–40-245 (–40-118)
DEG F (DEG C)
spr9
al
245 (118)
NOTE: This screen provides the means to generate alert messages based on exceeding the ‘‘Temp Alert’’ threshold for each point listed. If the
‘‘Enable’’ is set to 1, a value above the ‘‘Temp Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 2, a value below the ‘‘Temp
Alert’’ threshold shall generate an alert message. If the ‘‘Enable’’ is set to 0, alert generation is disabled.
EXAMPLE 9 — SERVICE3 DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE3.
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
Proportional Inc Band
2-10
gv
inc
6.5
Proportional Dec Band
2-10
gv
de
6.0
Proportional ECW Gain
1-3
gv
ecw
2.0
Guide Vane Travel Limit
30-100
%
gv
lim
50
21
Summary of Contents for 19EF Series
Page 10: ...Fig 5 19EF Controls and Sensor Locations cont 10...
Page 13: ...Fig 12 19EF Menu Structure 13...
Page 14: ...Fig 13 19EF Service Menu Structure 14...
Page 38: ...Fig 24 19EF Leak Test Procedures 38...
Page 69: ...Fig 36 Electronic PIC Controls Wiring Schematic 69...
Page 70: ...Fig 36 Electronic PIC Controls Wiring Schematic cont 70...
Page 71: ...Fig 37 Machine Power Panel Starter Assembly and Motor Wiring Schematic 71...