background image

1. Correct nozzle size has been selected for desired input rate.

2. Blower wheel support is removed.

3. Electrical wiring is completed according to Fig. 3 or 4.

4. Blower access door is secured in place.

5. Valve on oil supply line is open.

6. RESET BUTTON on primary control is pushed down.

7. Flame observation door is closed.

8. Thermostat is set for heating mode and set above room

temperature.

If all of the above items have been performed, set main electrical
switch to ON position and burner should start. When burner starts,
proceed to Combustion Check section.

Step 2-Combustion Check

In order to obtain optimum performance from oil burner, the
following setup procedures must be followed:

1. A test kit to measure smoke, stack draft, over-fire draft, oil

pump pressure, CO

2

, and stack temperatures MUST be used in

order to obtain proper air band setting. Although all of the
above measurements are required for optimum setup and
efficiency data, the most important readings that must be taken
are smoke number, over-fire draft, stack draft, and pump
pressure.

2. The proper smoke number has been established by engineer-

ing tests to be between 0 and 1. This degree of smoke emission
is commonly referred to as a “trace” of smoke. It is recom-
mended to use a Bacharach true spot smoke test set or
equivalent.

3. In order to ensure proper draft through furnace, a barometric

draft regulator (supplied with furnace) must be installed. In
order for this device to function properly, barometric damper
must be mounted with hinge pins horizontal and face of
damper vertical. (See instructions included with damper.) The
draft regulator should be adjusted after furnace has been firing
for at least 5 minutes, and set between -0.025 and -0.035 in.
wc. (See Table 9.)

4. The over-fire draft, which is taken through observation door

(located in center line above burner in front panel of furnace),
is a measurement necessary to determine if there is a blockage
between oil burner and flue outlet.
There should be a total pressure drop of between 0.020 and
0.05 in. wc through furnace as shown in Table 9. The over-fire
draft must be set within the range shown in Table 9. A reading
outside the range shown in Table 9 (for e0.1 in. wc)
would indicate that furnace is in an extremely high-pressure
condition in primary section. This condition may be caused by
any of the following problems:

a. Excessive combustion air due to air shutter being too wide

open.

b. A lack of flue draft (chimney effect) or some other

blockage, such as soot, in secondary section of heat
exchanger.

c. Use of an oversized nozzle input.

d. Pump pressure over the values listed in Table 10.

5. The CO

2

and stack temperature instruments enable you to

obtain data required to determine thermal efficiency of fur-
nace.

6. An oil filter should be installed as close to burner as possible

with ALL oil burners and is essential on lower firing rate
burners. We recommend the use of a low pressure drop oil
filter such as the General Filter, Inc. model #1A-25A or
equivalent.

7. The oil pressure regulator is factory set to give oil pressure of

130 psig for the model having 105,000 BTUH input and 130
psig for the model having 119,000 BTUH input. The firing
rate noted on nameplate may be obtained using the nozzles
and pump pressures 
indicated in Table 10.

8. On a new installation, air entrapped in oil line leading from

tank to nozzle must be thoroughly purged in order to prevent
excessive after drip. The oil pump is provided with a special
fitting which allows purging of any air between tank and oil
pump. The proper procedure for performing this operation is
as follows:

a. Place a piece of clear plastic 1/4-in. diameter tubing over

purge fitting on oil pump.

b. Start oil burner, then open purge fitting and allow burner to

run until purge tube is completely free of air bubbles.

c. Tighten purge fitting. Allow oil to run to nozzle and fire

burner.

d. If purging takes longer than 15 sec and no flame has been

established, burner stops. Push reset button on front of
primary control to restart burner.

e. For detailed information on operation of primary control,

refer to instructions included with furnace.

After all the setup procedures mentioned above have been com-
pleted, the burner should be allowed to operate and an inspection
mirror should be used to observe the flame pattern at tip of nozzle.
Any irregularities such as burning to 1 side or pulsating flame
patterns should be corrected by changing nozzle.

Step 3-Fan Adjustment Check

This furnace is equipped with a 4-speed direct-drive motor to
deliver a temperature rise within range specified on rating plate,
between return and supply plenums, at external duct static pressure
noted on rating plate.

When operating furnace in heating mode, static pressure and
temperature rise (supply-air temperature minus return-air
temperature) must be within those limits specified on rating
label. Failure to follow this warning could lead to severe
furnace damage.

Adjust fan speed ACCORDING TO OIL INPUT SELECTED so
that temperature rise is within rise range specified on rating plate.
(See Table 11.) Consult wiring diagram for speed changes on
direct-drive motor.

To adjust fan off time, set DIP switches on control board to obtain
desired timing. (See Fig. 5.)

Table 9-Furnace Draft Conditions (In. WC)

FURNACE

INPUT

(BTUH)

FLUE

DRAFT

MINIMUM

OVER-FIRE

DRAFT

MAXIMUM

TOTAL RESTRICTION

THROUGH

HEAT EXCHANGER

70,000

-0.025

0.010

0.020 to 0.035

91,000

-0.025

0.020

0.030 to 0.045

105,000

-0.025

0.025

0.035 to 0.050

119,000

-0.025

0.025

0.035 to 0.050

140,000

-0.025

0.025

0.035 to 0.050

154,000

-0.025

0.025

0.035 to 0.050

7

Summary of Contents for 1-58CLA

Page 1: ...OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT For use with grade 1 or 2 Fuel Oil Do not use Gasoline Crankcase Oil or any Oil containing Gasoline Failure to follow this warning could lead to sooting fire explosion and or severe bodily harm Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit Failure to follow this caution will re...

Page 2: ...ult in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation INTRODUCTION The model 58CLA Furnaces are available in 2 sizes Each size unit can be fired at 3 different rates by a simple nozzle change Unit 105 12 covers input ranges from 91 000 to 105 000 Btuh unit 120 20 covers input ranges from...

Page 3: ...amper is in full cool or heat position INSTALLATION Step 1 Air for Combustion and Ventilation Installation of this furnace in an area where it will receive contaminated combustion air must be avoided Such contami nation would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetra chloride cleaning solvents hydrochloric acid water soften ing chemicals and simi...

Page 4: ...hould be located about 6 in from top and bottom of enclosure at front of furnace See Table 3 NOTE In calculating free area consideration shall be given to blocking effect of louvers grilles or screens protecting openings Screens used shall not be smaller than 1 4 in mesh and shall be readily accessible for cleaning If free area through a design of louver or grille is known it shall be used in calc...

Page 5: ...efer to ANSI NFPA 211 Chimney Fireplaces Vents and Solid Fuel Burning Appliances and or CSA B139 Installation Code This furnace is certified for use with Type L vent maximum flue gas temperature 575 F Vent System Inspection Before furnace is installed it is highly recommended that any existing vent system be completely inspected For any chimney or vent this should include the following 1 Inspectio...

Page 6: ...al Code CSA C22 1 or subauthorities having jurisdiction Do not connect aluminum wire between disconnect switch and furnace Use only copper wire Failure to follow this caution will lead to intermittent electrical operation and or fire hazard The control system depends on correct polarity of power supply Connect HOT wire H and NEUTRAL wire N as shown in Fig 3 or 4 A separate line voltage supply MUST...

Page 7: ...required to determine thermal efficiency of fur nace 6 An oil filter should be installed as close to burner as possible with ALL oil burners and is essential on lower firing rate burners We recommend the use of a low pressure drop oil filter such as the General Filter Inc model 1A 25A or equivalent 7 The oil pressure regulator is factory set to give oil pressure of 130 psig for the model having 10...

Page 8: ...Fig 3 Wiring Diagram For 105 12 A03164 X04031 Rev A 8 ...

Page 9: ...Fig 4 Wiring Diagram For 120 20 A03165 X04032 Rev A 9 ...

Page 10: ...o keep this furnace in good operating condition and to maintain its warranty the furnace MUST be serviced on an annual basis This servicing includes a nozzle change a burner inspection a visual check of tube passages through flue outlet and cleanout ports and a visual inspection of combustion chamber when burner is removed Depending on above inspection service could also include a cleaning and vac...

Page 11: ...ed 8 After cleaning replace flue silencer flue collar and oil burner 9 Readjust burner for proper operation Step 4 Blower Removal To remove blower from furnace 1 Turn off all oil and electrical supplies upstream of furnace 2 Remove blower access door 3 Remove air filters 4 Remove blower retaining wing nuts 5 Slide blower on rails toward rear of unit 6 Reverse items 1 through 5 to reinstall blower ...

Page 12: ...31 58cla5si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 535 80122 Printed in U S A Form 58CLA 5SI Pg 12 11 03 Replaces 58CLA 4SI ...

Reviews: