![Carrier 09VE Installation, Operation And Maintenance Instructions Download Page 12](http://html1.mh-extra.com/html/carrier/09ve/09ve_installation-operation-and-maintenance-instructions_2562681012.webp)
11 - AC FAN MOTOR ASSEMBLIES
11.1 - AC motor protection
■ All the motors are equipped with a thermal cut-out, which is available in the motor terminal box. Wiring for the thermal cut-out is
optional
11.2 - Fan with AC motor (3-ph 230 V/400 V 50 Hz)
■ On a 3-ph/400 V/50 Hz network, the motors have 2 rotation speeds, via star (Y) or delta connection (Δ).
-
Low speed with Y connection
-
High speed with Δ connection
■ On a 3-ph/230 V/50 Hz electrical network, the motors have 1 rotation speed via delta connection (Δ):
-
Low speed with Δ connection
Impeller diameter
mm
910
800
Motor type
A9A
A9B
A9C
A9D
A8A
A8B
A8C
3-PH/230 V supply
Δ
-
Δ
-
Δ
-
Δ
-
Δ
-
Δ
-
Δ
-
3-PH/400 V supply
Y
Δ
Y
Δ
Y
Δ
Y
Δ
Y
Δ
Y
Δ
Y
Δ
Speed(s)
rpm
690 900 980 1280 680 890 700 900 700 900 560 690 300 440
Weight of im motor
kg
23
-
28
-
28
19
-
Weight of fan motor assembly
kg
70
59
66
59
52
48
38
Min. room temperature for storage
°C
-40
Min. operating temperature
°C
-40
Insulation class
F
Sealing class
IP 54
Number of starts
Max. 50 / hour
11.3 - Fan with AC motor 3-ph 208 V and 3-ph/400 V to 480 V 60 Hz
■ On a 3-ph 208 V/60 Hz and 230 V/50 Hz electrical network, the motors have 1 rotation speed via delta connection (Δ).
■ On a 3-ph/400 to 480 V/60 Hz electrical network, the motors have 1 rotation speed via star connection (Y):
Impeller diameter
mm
910
800
Motor type
B9A
B9B
B9C
B8A
B8B
B8C
B8D
3-ph 208 V/60 Hz supply
Δ
Δ
Δ
-
-
Δ
Δ
3-ph/400 to 480 V/60 Hz supply
Y
Y
Y
Y
Y
Y
Y
Speed(s)
rpm
1100
1000
800
1100
1050
840
520
Weight of im motor
kg
28
25
25
23
23
19
19
Weight of fan motor assembly
kg
69
66
66
51
51
47
47
Min. room temperature for storage
°C
-40
Min. operating temperature
°C
-40
Insulation class
F
Sealing class
IP 54
Number of starts
Max. 50 / hour
12
Summary of Contents for 09VE
Page 2: ...2...