1-8-2. Method of charging nitrogen gas
This instruction describes the procedure to charge nitrogen gas (hereinafter called N
2
gas) to the
Chiller.
(1) Equipment use
a) N
2
gas : Required volume
Content volume
b) Pressure regulator
c) Pressure proof hose
d) Adjustable wrench
e) Valve key for N
2
gas cylinder
f) Vacuum gauge (0-100kPa)
(2) Standard
The pressure in the Chiller is charged until 50kPa at generator pressure gauge.
(3) Precautions
a) Since the N
2
gas cylinders are pressurized up to 15MPa, pay attention to handle them.
b) Do not suddenly raise the primary or secondary pressure of the pressure regulator.
c) Fix the N
2
gas cylinder so that it does not fall over.
d) Be sure not to open V1, V2 during this work.
Model
Volume
Model
Volume
LJ-
(litter)
LJ-
(litter)
11E
1,640
31E
5,030
12E
1,580
32E
4,830
13E
2,510
41E
6,150
14E
2,380
42E
5,910
21E
3,150
51E
8,240
22E
3,010
52E
9,350
23E
4,210
53E
10,350