Motor Controllers AC Variable Frequency Drives
Type Variflex
3
RVFF
Specifications are subjected to change without notice.
50
Group 12 Monitoring Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
12-00 Display screen selection
00000~77777
From the leftmost bit, it displays
the screen when press DSP key in
order.
0: No display
1: Output current
2: Output voltage
3: DC Bus voltage
4: Heatsink temperature
5: PID Feedback
6: AI1 input
7: AI2 input
00321
-
O
O
O
*1 *5
12-01 PID feedback display mode
0: Display the feedback value by
integer (xxx)
0
O
O
O
*5
1: Display the feedback value by
the value with one decimal place
(xx.x)
2: Display the feedback value by
the value with two decimal
places (x.xx)
12-02
PID feedback display unit
setting
0: xxxxx (no unit)
0
O
O
O
*5
1: xxxPb (pressure)
2: xxxFL (flow)
12-03 Line speed value
0~65535
1800 RPM O
O
O
*5
12-04 Line speed display mode
0: Display inverter output
frequency
0
O
O
O
*1 *5
1: Line speed display as integer.
(xxxxx)
2: Line speed display with one
decimal place. (xxxx.x)
3: Line speed display with two
decimal places. (xxx.xx)
4: Line speed display with three
decimal places. (xx.xxx)
12-05
Status display of digital input
terminal
LED display is shown as below
no input
correspondences to input and
output
-
-
O
O
O