![CARLO GAVAZZI VariFlex3 RVFFA3400400F Quick Start Manual Download Page 41](http://html1.mh-extra.com/html/carlo-gavazzi/variflex3-rvffa3400400f/variflex3-rvffa3400400f_quick-start-manual_2558654041.webp)
Motor Controllers AC Variable Frequency Drives
Type Variflex
3
RVFF
Specifications are subjected to change without notice.
40
Group 07 Start /Stop Parameters
Code
Parameter Name
Setting Range
Default Unit
Control Mode Attribute
V/F SLV PM
SLV
07-04 Direct running after power up
0: Enable direct running after
power up
1
-
O
O
O
1: Disable direct running after
power up
07-05 Direct starting delay-on timer
after power up
1.0~300.0
3.5
S
O
O
O
07-06 DC Injection braking starting
frequency
0.0~10.0
0.5
Hz
O
O
O
07-07 DC Injection braking current
0~100
50
%
O
O
O
07-08
DC Injection braking time at
stop
0.00~10.00
0.50
s
O
O
O
07-09 Stop mode selection
0: Deceleration to stop
0
-
O
O
O
1: Coast to stop
O
O
O
2: DC Braking stop in all fields
O
O
X
3: Coast to stop with timer
O
O
O
07-10
~
07-12
Reserved
07-13 Low voltage detection level
300~600
380
V
O
O
O
07-14 Pre-excitation time
0.00~10.00
2.00
s
X
O
X
07-15 Pre-excitation level
50~200
100
%
X
O
X
*6
07-16
DC Injection braking time at
start
0.00~100.00
0.00
s
O
O
O
07-17
Reserved
07-18 Minimum base block time
0.1~5.0
1.4
S
O
O
O
07-19
Speed direction search
operating current
0~100
50
%
O
O
X
07-20
Speed search operating
current
0~100
20
%
O
O
X
07-21
Integral time of speed
searching
0.1~10.0
2.0
S
O
O
X
07-22 Delay time of speed searching 0.0~20.0
0.2
S
O
O
X
07-23 Voltage recovery time
0.1~5.0
2.0
S
O
O
X
07-24
Bidirection speed search
selection
0: Disable
1
-
O
O
X
1: Enable
07-25 Low voltage detection time
0.00~1.00
0.02
S
O
O
O
07-26 Mechanical braking selection
0: Disable
0
-
X
O
X
1: Enable
07-27
Start selection after fault during
SLV mode
0: Start with speed search
0
-
X
O
O
1: Normal start
07-28 Start after external base block
0: Start with speed search
0
-
O
O
X
1: Normal start
07-29
Run command select when DC
braking
0: Don’t allow to start when
proceeding
0
-
O
X
X
1: Allow to start when proceeding
07-30
Reserved
07-31