3.8.5 RVDF Size B Installation
T1 T2 T3
3 Pha
s
e
s
IM
220-240V
380-480V
S
ingle/ThreePha
s
e
s
DATA
FUN
DSP
ENT
RUN
RESET
STOP
REV-0-FWD
S
WITCH
210.0mm
4xM4
274.5mm
Potentiometer
POWER
S
WITCH
L1(L) L2(N) L3
NOTE:
1. Power supply cable:
220V #12AWG (3.5mm2)
400V #16AWG (1.25mm2)
2. Motor cable:
220V #14AWG (2.0mm2)
400V #16AWG (1.25mm2)
3. Torque value of Screw:
(1).Power/Motor cable (TM1, TM3)
Terminal: 8 kgf-cm (6.94in-lb)
(2).Remote control wire: 4kgf-cm (3.47in-lb)
(3).Outer Cover (M4): 8kgf-cm(6.94 in-lb)
3
PHA
S
E
IM
10V
VI
0V
FW
RE
12V
L1 (L)
L2 (N)
L3
T1
T2
T3
POWER
S
WITCH
REV -0-FWD
S
WITCH
Potentiometer
200
~
240
380
~
480
50/60HZ
NOTE:
(1). Input source:single-phase(L1(L),L2(N), )
ensuring that it is connected to a 200/240
supply or three-plase (L1 (L), L2 (N), L3, )
ensuring that it is connected to a
200/240, 380/480V supply.
(2). Output Motor: three-phase ( , T1, T2,
T3).
Caution:
•
Do not start or stop the inverter using the
main circuit power.
•
Please always remain REV-0-FWD switch
at 0 position. In order to keep inverter
has no running signal before power-on
again after power supply interrupted.
Otherwise, injury may result.
3.8.6 RVDF Size B Circuit Diagram
RELAY
RW
blac
k
RE
brown
R
S
10V
orange
12V
red
S
P
0V
green
Vi
yellow
FM
TM2